CEA663T - Disjoncteur automatique HAGER - Nemokama naudojimo instrukcija
Raskite įrenginio instrukciją nemokamai CEA663T HAGER PDF formatu.
Naudotojų klausimai apie CEA663T HAGER
0 klausimas apie šį prietaisą. Atsakykite į tas, kurias žinote, arba užduokite savo.
Užduokite naują klausimą apie šį prietaisą
Atsisiųskite instrukciją savo Disjoncteur automatique PDF formatu nemokamai! Raskite savo instrukciją CEA663T - HAGER ir vėl perimkite savo elektroninį įrenginį. Šiame puslapyje skelbiami visi dokumentai, reikalingi jūsų įrenginio naudojimui. CEA663T prekės ženklo HAGER.
NAUDOJIMO INSTRUKCIJA CEA663T HAGER

natural_image
Technical line drawing of a dual electrical switchgear (no text or symbols)Safety switch (RCCB's) 25 - 100A

GB For the tripping times verification tests, in an electrical installation, Hager certifies that the RCDs, of the Hager brand, conforming to standards EN 61008-2-1, EN 61009-2-1, trip under a current of 5°lΔn in accordance with the times imposed in table 41.1 of standard DIN VDE 0100-410 (VDE 0100-410) 2018-10.



text_image
14 mm max. 16 - 63 A 80 - 100 A 16 mm² 35 mm² 25 mm² 50 mm²
Safety instructions
The installation and mounting of electrical appliances must only be performed by qualified electricians, in compliance with installation standards and in accordance with the guidelines, provisions and safety and accident prevention regulations in force in the country concerned.
Electrical connection 2 pole.

text_image
L Main Neutral Link 1 3 N T E 2 4 N KM03A RCD Neutral Link L1 - circuit 1 L2 - circuit 2 L1 N1 N2 L2For an RCD where two or three circuits are to be protected, the Hager neutral link KM03A may be connected to the outgoing N terminal for the convenient splitting of the neutrals.
Please note the following
1 - The current rating per pole of the RCCB must not be exceeded by the maximum demand of the protected circuits.
2 - If RCCB trips OFF after installation, locate and repair faulty appliances (cumulative leakage from a number of appliances may exceed the RCCB tripping current, causing RCCB to trip OFF).
3 - The "main neutral" and "main earth" should be checked to ensure good connection.
4 - If RCCB trips intermittently will not reset, or test button will not work, check for low insulation resistance between neutral & earth wiring.
5 - RCCB may be fed in any position:
LOAD and LINE circuits may be connected top or bottom.
Electrical connection for P+N or for three phase only.
Three phase & neutral use or Three phase use

text_image
L1 L2 L3 N 1 3 5 7 N T E 2 4 6 8 N L1 L2 L3 NSingle phase use Two circuits

text_image
L N L N 1 3 5 7 N T E 2 4 6 8 N L N NLOne circuit

text_image
L1 T E 1 3 5 7 N 2 4 6 8 N L1 NPosition contact indication.

text_image
OFF greenEarth leakage fault indication.

text_image
or Test OFF yellow Test 1, 3, 5...12Single phase connection.

text_image
KDN180A KDN180GThree phase connection.

text_image
N KDN380A KDN380GA

B

C


text_image
A ② ②
text_image
B 3,6 Nm 3,6 Nm
text_image
C 3.6 Nm ② ③ Possible use of the RCD neutral link KM03AAuxiliary possibilities.
MZ201
MZ202
MZ203
MZ204
MZ205
MZ206

text_image
Diagram showing a switch symbol inside a rectangular block and its corresponding schematic diagram with dashed lines and arrows indicating transformation or assembly.Locking device for handle MZN175.

text_image
Ø 3,5/ 6 max.
Protection against dust
In case of work activities nearby, make sure that the electrical installation is protected against dust if the enclosure is not IP5x.