Uni-T UT279 - Measurement

UT279 - Measurement Uni-T - Free user manual and instructions

Find the device manual for free UT279 Uni-T in PDF.

📄 15 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Uni-T UT279 - page 3
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Transformer Grounding Current Tester
Brand Uni-T
Model UT279
Power Supply DC 9V alkaline dry battery (6 x LR6 1.5V)
Testing Mode Clamp-shaped CT
Jaw Size 80mm x 80mm
Current Range AC 0.00mA to 100.0A
Resolution 0.01mA (0.00-0.99mA), 0.1mA (1.0-99.0mA), 1mA (100-999mA), 0.1A (1.0-100.0A)
Accuracy ±(0.5% + 5dgt) at 23°C ±3°C, <70%RH
Frequency Range 10Hz to 1000Hz
Display 3.5-inch color touch-screen LCD (320 x 240 dots)
Tester Dimensions 198mm x 100mm x 45mm
Current Clamp Dimensions 194mm x 145mm x 40mm
Weight (Tester + Battery) 450g
Weight (Current Clamp) 780g
Data Storage Capacity 200 sets of data and waveforms
Alarming Threshold Range 10mA to 99.99A
Auto Power Off Adjustable (0-999 min, default 5 min)
Interface USB for data download
Operating Temperature -10°C to 40°C
Operating Humidity <80%RH
Safety Rating CAT III 600V, Double insulation
Included Accessories Tester, current clamp, USB cable, tester box, 6 x AAA batteries, user manual

Frequently Asked Questions - UT279 Uni-T

How do I turn on the UT279?
Press the POWER button. The LCD will display the menu. If the screen is blank or flashes, the battery may be low; replace the battery.
What batteries does the UT279 use?
It uses 6 x LR6 (AAA) alkaline batteries, providing DC 9V. Pay attention to polarity when replacing.
How do I measure current with the UT279?
Connect the current clamp to the tester, then clamp the circuit under test. Navigate to Data Measurement on the touchscreen. The reading and waveform will be displayed.
What is the maximum voltage I can test?
Do not test circuits with voltage exceeding 600V. The tester is rated CAT III 600V.
How do I store measurement data?
In Data Measurement mode, tap the Data Storage icon. The tester stores current, waveform, time, and numbering. A total of 200 sets can be saved.
How do I view stored data?
On the function menu, select Data Viewing. Use the arrow keys or touch to scroll through the stored records.
Can I delete stored data?
Yes. Go to Data Deletion in the menu. Choose 'Yes' to delete all stored data at once. Note: data cannot be recovered after deletion.
How do I set the alarm threshold?
Navigate to Alarming Setting. Use the arrow keys or touch to adjust the threshold from 10mA to 99.99A. The buzzer will sound and LCD flash if exceeded.
What does the low battery symbol mean?
When battery voltage drops below 7.2V ±0.1V, the low battery symbol appears. Replace the batteries soon to ensure accurate measurements.
How do I connect the UT279 to a computer?
Use the included USB cable to connect the tester to a computer. Install the USB driver and monitoring software. Then you can download stored data or monitor in real time.

User questions about UT279 Uni-T

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Measurement in PDF format for free! Find your manual UT279 - Uni-T and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. UT279 by Uni-T.

USER MANUAL UT279 Uni-T

natural_image Abstract geometric pattern of gray squares arranged around a central square (no text or symbols)

UNI-T®

UNI-TREND TECHNOLOGY (CHINA) CO., LTD.

No. 6, Gong Ye Bei 1st Road,

Songshan Lake National High-Tech Industrial

Development Zone, Dongguan City,

Guangdong Province, China

UNI-T®

07279 Transfection Scaling Control Panel

Transformer Grounding Current Tester

UT279

Operating Manual

Uni-T UT279 - UNI-T® - 2

P/N:110401112106X

Contents

Safety Information....1

I. Introduction......2
II. Electrical Symbols....3
III. Technical Specifications .... 4
IV. External Structure....6
V. Operating Instructions ....7

  1. Power On/Off....7
  2. Data Measurement 7
  3. Clock Setting....8
  4. Data Storage....8
  5. Data Viewing......8
  6. Tested Object Numbering 8
  7. Data Deletion....8
  8. Touchscreen Calibration 9
  9. Power-off Time Setting....9
  10. Alarming Setting 9
  11. Current Waveform Testing.... 10
  12. Monitoring in Real Time 11
  13. Data Downloading 12

VI. Battery Replacement....12

VII. Packing List....13

Safety Information

Thank you for buying this product, for better use of it, please be sure of the followings:

Read the user manual carefully.

Follow all operating precautions in the user manual.

◆ Pay special attention to safety use in any case.
◆ Note the labels, texts and symbols at the tester.
◆ If the battery power is low, the tester will keep rebooting, please replace battery.
◆ Do not test circuit with voltage over 600V.
It is forbidden to use without rear cover and battery cover closed well.
◆ In case that the case or test lead cracks and then cause exposed metal during use, please stop use immediately.

◆ Please do not place and keep the tester in places with high temperature/humidity, dews and direct sunlight for an extended period of time.

◆ Maintain and clean the tester and current clamp in a regular basis, do not wipe them with corrosives and coarse materials.

◆ Avoid the iron core of current clamp from deforming, deformed iron core will affect testing accuracy.

◆ Please note the battery polarity when replacing battery, and remove the battery if not used for a long time.

◆ Use, disassembly and repair must be performed by authorized eligible personnel.

◆ If danger may occurs due to the tester, please stop using the tester and seal it, then send it to authorized qualified agency for maintenance.

◆ The symbols “⚠️” at the tester and user manual represent danger warning, indicating user must perform safe operation according to the warnings.
◆ The symbol “?” in the user manual represents warning of super danger, indicating user must perform safe operation according to the warnings.

I. Introduction

UT279 Transformer Grounding Current Tester is designed and manufactured to perform on-line test on the grounding current and the leakage current of transformer iron core in power system on site, the tester is designed with current clamp, monitoring software, communication line, etc. The transformer is an important electrical equipment in the power system, if the transformer is malfunctioned, that will cause severe consequence to the power system. The transformer iron core under normal operation is grounded in the way of single point, if grounded in the way of two or multiple points, current loop will occur between the iron core and the ground, the maximum current in the loop can reach several tens of amperes, which will cause partial area of the iron core to be overheated or even burnt. The tester can find out potential fault in transformer, which makes it an ideal tool to ensure safe operation and daily maintenance of transformer. The tester is capable of resisting interference, applicable in environment with strong magnetic field near transformer, mainly used for leakage current test performed on the “clamp” (a device to fix the iron core of electrical equipment) and electrical equipment such as transformer, electric reactor and others in transformer station and power generating plant. The tester also applies to current test and leakage current test of circuits or equipment in electric power, communication, meteorology, railway, oil field, architecture, metrology, scientific research and teaching institute, industrial and mining enterprises, and other fields.

The tester is designed with high-speed microprocessor and 3.5-inch color touchscreen LCD, enabling smart touch operation and easy use, it can display the value and waveform of measured current in real time. With FFT, digital filtering and other technologies employed, the tester makes measured data more accurate. UT279 has multiple functions such as alarming threshold setting and warning indication, data & time and “Setting”, auto power off, setting of numbering of tested object, it is able to save 200 sets of data and waveforms, the stored data can be imported to computer via the USB interface of the tester.

As the iron core of current clamp is made with permalloy and magnetic shielding technology, it is not susceptible to influence and interference from external magnetic field, ensuring continuous measurement of high accuracy, stability and reliability. The internal diameter of the clamp jaw is 80mm×80mm, which allows it to clamp cable or grounding wire of 80mm below, or 96mm×4mm grounding wire of flat steel. The clamp jaw features portable design and realizes non-contact, safe and rapid measurement without the circuit under test disconnected.

The monitoring software has multiple functions such as on-line monitoring in real time, data viewing, data storage, data printing, dynamic display, waveform indication, alarming threshold setting, alarm indication, and more.

II. Electrical Symbols

Uni-T UT279 - Electrical Symbols - 1Super dangerous! The user must stringently observe the safety regulations, otherwise it may pose a risk of shock and cause personal injury and death.
Uni-T UT279 - Electrical Symbols - 2Danger! The user must stringently observe the safety regulations, otherwise it may pose a risk of shock and cause personal injury anddeath.
⚠️Warning! The user must stringently observe the safety regulations, otherwise it can cause personal injury or damage to equipment.
Double insulated
~Alternating current (AC)
— —Direct current (DC)

III. Technical Specifications

FunctionGrounding current test, AC leakage current on-line test, AC current on-line test.
Power supplyDC 9V alkaline dry battery (LR6 1.5V×6)
Testing modeClamp-shaped CT
Jaw size80mm×80mm (The jaw can clamp 80mm lead, or 96mm×4mm grounding wire of flat steel)
Current rangeAC 0.00mA~100A
ResolutionAC 0.00mA~0.99mA; resolution: 0.01mA
AC 1.0mA~99.0mA; resolution: 0.1mA
AC 100mA~999mA; resolution: 1mA
AC 1.0A~100.0A; resolution: 0.1A
Accuracy±(0.5%+5dgt)23°C±3°C, <70%RH, test lead is centered within the clamp jaw.
Frequency range10HZ~1000HZ
Display mode3.5-inch color touch-screen LCD (320dots × 240dots)
Operating modeSmart touch and button control
Tester dimension198mm×100mm×45mm
Current clamp dimension194mm×145mm×40mm
WeightTester: 450g (battery included); current clamp: 780g
LCD sizeDisplay area: 71mm×53mm
Electromagnetic interferenceWhen the current clamp induces electric field of 100A at a distance of 10mm, induced current of 10mA will be generated.
Sampling rateOnce per second
Data storage200 sets of data (Data will not be lost when battery is replaced or power is down)
Date and clockDate and clock displays, clock setting
Tested object numberingSetting of numbering of test points
Auto power offThe tester will power off automatically after it is started up after 5 minutes by default.
Touchscreen calibrationThe tester has function of touchscreen calibration.
USB interfaceThe tester has a USB interface, via which the stored data in tester can be imported to computer.
Alarming settingAlarming threshold range: 10mA~99.99A
Alarming indicationThe LCD flashes and the buzzer sounds when the tested value exceed the alarming threshold.
Voltage of tested circuit
Overrange indication“OL” is displayed
Battery voltageWhen battery voltage drops to 7.2V±0.1V, the low battery symbol will be displayed, indicating battery replacement. The measured data is accurate under low battery condition.
Rated current180mA at most
Lead length2 meters
Operating temperature & humidity-10°C~40°C; <80%rh
Storage temperature & humidity-10°C~60°C; <70%rh
Insulation strengthAC 2kV/rms (between screw and casing)
Suitable Category ratingIEC1010-1, IEC1010-2-032, Pollution Class 2, CAT III 600V, IEC61326 (EMC standard)

IV. External Structure

1 2 3 4 5 6 MEM 100.5mA

  1. Connector for current clamp
    Uni-T UT279 - External Structure - 2
  1. USB interface

  2. 3.5-inch color touch-screen LCD

  3. ↑↓←→ button and MEM button
  4. Coil tap
  5. Shielded layer
  6. Output lead
  7. Trigger

  8. Tester

  9. POWER button

  10. Coil tap

  11. Audio plug
  12. Current clamp

v. Operating Instructions

1. Power On/Off

When POWER is pressed, the tester will be turned on and the LCD will display the menu. If blank screen occurs and the LCD keeps flashing after the tester is turned on, that indicates the battery power may be low, please press POWER to turn off the tester and then replace the battery. The time of powering off the tester automatically can be set, the time range is 000 to 999(min), if the time is set at "000", the tester will not power off automatically. The tester will power off automatically after it is turned on for 5 minutes by default.

2. Data Measurement

In function menu page, press ←→ to move the cursor to "Data Measurement" icon, and press MEM or tap "Data Measurement" icon to enter data measurement page, then press ↑↓ to move the cursor to "Return" icon, next, press MEM or tap "Return" icon to return to function menu pate.

Uni-T UT279 - Data Measurement - 1

In function menu page, press ←→ to move the cursor to “Clock Setting” icon, and press MEM or tap “Clock Setting” icon to enter clock setting page, press ←→ or tap “ ” icon to move the cursor to year, month, day, hour, minute, press ↑↓ or tap “ ” icon to adjust date and time. Press ↑↓ to move the cursor to “Return” icon, then press MEM or tap “Return” icon to return to function menu page.

4. Data Storage

In data measurement page, when pressing or tapping "Data Storage" icon, the tester will enter data storage status and the LCD will display "NO.XXXHD", the tester stores the current, waveform, time, tested object numbering to the memory, "NO.XXX" represents the number of groups of stored data, press again or tap other icons to exit.

5. Data Viewing

In function menu page, press ←→ to move the cursor to "Data Viewing", then press MEM or tap "Data Viewing" icon to enter data viewing page, press ↑↓ to scroll through data. Press ↑↓ to move the cursor to "Return" icon, then press MEM or tap "Return" icon to return to function menu page.

6. Tested Object Numbering

In function menu page, Press ←→ to move the cursor to “Tested Object Numbering” icon, then press MEM or tap “Tested Object Numbering” icon to enter the page of tested object numbering, press ←→ or tap “ ” icon to move the cursor, press ↑↓ or tap “ ” icon to change the numbering of tested object, press ↑↓ to move the cursor to “Return” icon, then press MEM or tap “Return” icon to return to function menu page.

7. Data Deletion

In function menu page, press ←→ to move the cursor to "Data Deletion" icon, then

press MEM or tap "Data Deletion" icon to enter data deletion page. When the cursor is at "Yes", press MEM or tap "Yes" icon to delete the stored data. If pressing MEM or tapping "No" icon when the cursor is at "No", the stored data will not be deleted and the present page will return to function menu page. Press ↑↓ to move the cursor to "Return" icon, then press MEM or tap "Return" icon to return to function menu page.

Data cannot be recovered after deletion!
The operation of data deletion represents all stored data are deleted at a time.

8. Touchscreen Calibration

In function menu page, press ←→ to move the cursor to “Touchscreen calibration” icon, and press MEM or tap “Touchscreen calibration” icon to enter touchscreen calibration page, then tap the symbol “+” in sequence. Return to function menu page after calibration.

9. Power-off Time Setting

In function menu page, press ←→ to move the cursor to “Power-off Time Setting” icon, then press MEM or tap “Power-off Time Setting” icon to enter power off setting page, press ←→ or tap “←→” icon to move the cursor, press ↑↓ or tap “↑↓” icon to change the power-off time, the tester will not power off if the time is set at “000”, press ↑↓ to move the cursor to “Return” icon, then press MEM or tap “Return” icon to return to function menu page. The time of powering off automatically is set at from 000 to 999 minutes, the tester will automatically power off after it is turned on for 5 minutes by default.

10. Alarming Setting

In function menu page, press ←→ to move the cursor to “Alarming Setting” icon, then press MEM or tap “Alarming Setting” icon to enter alarming setting page,

press ←→ or tap“←→” icon to move the cursor, press ↑↓ or tap “↑↓” icon to change the alarming threshold, press ↑↓ to move the cursor to “Return” icon, the press MEM or tap “Return” icon to return to function menu page. The scope of alarming threshold is 00.00A\~99.99A.

The default alarming threshold at startup is “00.00”A, which means the tester will not alarm.
The buzzer sounds if the current exceeds the alarming threshold.

11. Current Waveform Testing

Uni-T UT279 - Current Waveform Testing - 1Danger! Electric shock! Operation must be performed by authorized trained eligible personnel, the operator must stringently observe safety regulations. Otherwise it may pose a risk of electric shock and cause personnel injury or equipment damage.
Do not test circuit with voltage of over 600V, otherwise it may pose a risk of electric shock, cause personnel injury or equipment damage.

1) Connect the current clamp and the tester, then turn on the meter to enter "Data Measurement" mode.
2) Clamp the measured circuit through the current clamp, then observe the reading, if "OL" is displayed, that indicates the measured current exceeds the upper limit specified by the tester.
3) The tester has a function to zoom in/out the waveform, do not judge the current value according to waveform amplitude.

Diagram illustrating power distribution and grounding system with transformers, meters, and electrical connections

A B C N

To measure the leakage current of the grounding wire of electrical equipment, please clamp the grounding wire.
To measure the current of the circuit, please clamp the live or neutral wire individually.
To measure single-phase leakage current, please clamp the live and neutral wires together.
To measure the leakage current of 3 three-phase wires, please clamp the 3 three-phase wires.
To measure the leakage current of 4 three-phase wires, please clamp the 4 three-phase wires.
To measure the leakage current of 5 three-phase wires, please clamp the 5 three-phase wires.
For safety, please remove the measured lead from the tester after high voltage/current test.

12. Monitoring in Real Time

Turn on the tester to enter test status, connect the tester with the computer via the equipped USB communication cable, operate the monitoring software installed

in computer, if the communication is normal, the computer can monitor on-line current in real time.

The monitoring software has multiple features such as on-line real-time monitoring, history querying, dynamic display, waveform indication, alarming threshold setting and alarming indication, and has multiple functions including data reading, access, storage, printing, etc.

13. Data Downloading

Please follow the operating steps below:

• Install the USB driver and "Monitoring Software".
- Connect the tester with computer via the equipped USB communication cable.
- Turn on the tester.
- Allow the monitoring software to operate.
- Select history querying and read the data.

VI. Battery Replacement

Uni-T UT279 - Battery Replacement - 1Install battery according to the correct polarity, otherwise it may cause damage to the tester.
If the battery power is low, please replace it immediately.
New and used batteries cannot be applied together.

1) When the battery voltage is 7.2V ± 0.1V below, the tester will display low battery symbol to indicate insufficient battery power, please replace the battery.
2) Press POWER button to turn off the tester, and open the battery cover after the tester is confirmed power-off, then, replace the batteries with new qualified ones and close the battery cover, last, turn on the tester to confirm if the replacement is complete. Please pay special attention to battery specification and polarity. (See figures below)

Loosen battery cover

Tighten

VII. Packing List

ItemQuantity (pcs)
Tester1
Current clamp1
USB cable1
Tester box1
Alkaline dry battery (AAA 1.5V )6
User manual1

The company is not responsible for other losses caused by use.

The content of this user manual cannot be used as a reason for using the product for special purposes.

The company reserves the right to modify the contents of the user manual. If there are changes, no further notice will be given.

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Uni-T

Model : UT279

Category : Measurement