DAIKIN EKDICMPAL - Controller

EKDICMPAL - Controller DAIKIN - Free user manual and instructions

Find the device manual for free EKDICMPAL DAIKIN in PDF.

📄 144 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice DAIKIN EKDICMPAL - page 7
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Intelligent Chiller Manager (iCM) Controller
Model EKDICMPAL
Dimensions (L x H x W) 600 x 800 x 300 mm
Weight 40 kg
Power Supply 1-phase, 50-60 Hz, 230 VAC +/-10%
Output Voltage 24 VAC
Nominal Current 40 A
Peak Current 10 kA
Power Consumption Max 161 VA, typical 150 VA
IP Rating (External/Internal) IP66 / IP20
IK Rating IK08
Operating Temperature -20 to 60 °C
Storage Temperature -40 to 70 °C
Humidity <90% RH (non-condensing)
Communication Interfaces Modbus RTU/RS485, BACnet/IP, IP Service (Ethernet)
Main Functions Chiller sequencing, pump control, bypass valve control, temperature setpoint, alarming, remote monitoring via Daikin On Site
HMI Options Built-in LCD, Remote HMI, Web HMI
Max Chillers Supported Up to 8
Maintenance Clean exterior with dry cloth; avoid water ingress; check connections periodically
Safety Precautions Installation by qualified personnel only; disconnect power before servicing; comply with local electrical codes
Spare Parts / Repairability Contact Daikin representative for spare parts; replace only with approved components

Frequently Asked Questions - EKDICMPAL DAIKIN

What is the Daikin EKDICMPAL intelligent Chiller Manager used for?
The EKDICMPAL is an Intelligent Chiller Manager (iCM) that centralizes control and monitoring of chiller plant systems, including chillers, pumps, valves, and sensors. It supports up to 8 chillers and integrates with BMS via BACnet or Modbus.
How do I connect the iCM to Daikin On Site cloud service?
Ensure the controller has internet connectivity via the built-in 3G router. On the HMI, navigate to ConfigMode > SystemSetting > Network > DaikinOnSite and set it to Enable. Then configure the IP settings under MainController.
What is the maximum number of chillers that can be registered?
Up to 8 chillers can be registered. Each chiller can be associated with evaporator and condenser shut-off valves. Registration is done under ConfigMode > DeviceRegistration > Chiller.
How do I set the system to Config Mode?
From the Main Menu, select ConfigMode. Ensure the system is OFF (system ON/OFF must be OFF). Then set ConfigMode to ON. This allows equipment registration, trial runs, and configuration changes.
What type of sensors are supported for temperature measurement?
The iCM supports NTC10K and 4-20mA temperature sensors. Chilled water sensors are NTC10K (supplied). For other sensors, the port type can be configured in DeviceConfig > SensorConfig.
How do I perform a trial run for connected equipment?
After putting the system in Config Mode, go to ConfigMode > TrialRun. Select I/O Trial Run or Chiller Trial Run. Follow the on-screen prompts to send commands and verify responses.
How can I reset an alarm on the iCM?
Press the Alarm Button on the HMI to view active alarms. Navigate to Alarming > Alarm List. Select the alarm and choose Reset Alarm. Some alarms may require clearing the cause first.
What is the password for accessing hidden menus?
The default password is 0000 (four zeros). Enter it in the Password menu from the Main Menu. If forgotten, contact Daikin support. The system logs out automatically after 10 minutes of inactivity.
Can the iCM control variable frequency drives (VFD) for pumps?
Yes. In DeviceCtrlParam > PrimaryPump Ctrl, set PumpType to VFD. Then configure PI parameters, setpoint, and staging thresholds for differential pressure control.
How do I back up the configuration settings?
Insert an SD card into the controller. From ConfigMode > Backup/Restore, select Backup to save configuration data. To restore, use the same menu and select Restore.

User questions about EKDICMPAL DAIKIN

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Controller in PDF format for free! Find your manual EKDICMPAL - DAIKIN and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EKDICMPAL by DAIKIN.

USER MANUAL EKDICMPAL DAIKIN

Intelligent Chiller Manager (iCM)

Revision History

VersionDateiCM versionRemarks
1.02016/4/21iCM_AM_Ver1.00First version
2.02017/2/3iCM_Ver2.00-00.03Available for Air/Water-Cooled Chillers

Index

Revision History 1

Index 3

  1. Introduction 6

  2. Functional Overview of iCM....7

2.1. System Topology 7

  1. Technical Overview....9

3.1. Electrical Panel 9

3.2. Controllers 10

3.2.1. Main Controller....10

3.2.2. BACnet Module (Optional)....11

3.2.3. MODbus Module (Optional)....11

3.2.4. I/O Modules....11

3.3. I/O Mapping ....11

3.4. Networks....11

3.4.1. Modbus® / RS485 (Chiller Network)....11

3.4.2. BACnet....11

  1. Electrical Installation 15

4.1. General specifications....15

4.2. Operator's responsibility ....15

  1. Mechanical Installation....16

5.1. Control Panel installation 16

5.2. Temperature sensor installation....17

5.3. Differential Pressure sensor installation....17

  1. Description of Operation....19

6.1. Menu Structure 19

6.2. Basic Parts and Operation 21

6.3. LCD Panel Display....22

6.4. Setting Address of Extension I/O Modules 24

6.5. Password Protection....25

  1. Scenario of Interaction 26

7.1. Workflow for Initial Configuration / Commissioning....26

7.1.1. On Site 26

7.1.2. Off Site 27

7.2. Workflow for Monitoring 28

7.2.1. Status Monitoring....28

7.2.2. Alarm Monitoring 28

7.3. Workflow for Operation 29

7.3.1. Commanding....29

7.3.2. Parameter Tuning....29

7.4. Workflow for Maintenance....30

7.4.1. Equipment Maintenance....30

7.4.2. HVAC System Component Change....30

  1. Configuration....31

8.1. Password Input....31

8.2. Setting System to Config Mode....32

8.3. System Configuration Setting....34

8.3.1. Setting Unit....34

8.3.2. Setting Current Time / Date 36

8.3.3. Changing Network Setting of Main Controller 36

8.3.4. Changing Network Setting of BACnet Module 38

8.3.5. Changing Network Setting of Daikin On Site (DoS: Cloud Connection) .....40

8.3.6. Showing information of iCM....41

8.4. Equipment Registration....42

8.4.1. Chiller Registration 44

8.4.2. PrimaryPump Registration....45

8.4.3. CondenserPump Registration....45

8.4.4. CTBypassValve Registration 46

8.4.5. Sensors Registration 47

8.4.6. ExtI/O Registration 48

8.4.7. BACnet_Module Registration....49

8.5. Equipment Configuration....50

8.5.1. System Configuration 52

8.5.2. Chiller Configuration 52

8.5.3. Evaporator Shut Off Valve Configuration 54

8.5.4. Condenser Shut Off Valve Configuration 54

8.5.5. Primary Pump Configuration....55

8.5.6. Condenser Pump Configuration....56

8.5.7. Sensor Configuration....57

8.5.8. Modbus Communication Setting 61

8.5.9. Ai Threshold Setting 63

  1. Equipment Control Setting 64

9.1. Chiller Control Setting 66

9.1.1. Setting sequence order when using fixed order sequencing....68

9.1.2. Setting detailed options for staging up / down....68

9.2. Primary Pump Control Setting....71

9.2.1. Setting PI Parameters for Pump VFD Control....72

9.2.2. Setting periodical pump staging for rotation....73

9.2.3. Setting minimum / maximum number of operating pumps for each piping group 73

9.3. Bypass Valve Control Setting....74

9.3.1. Setting PI Parameters for Bypass Valve Control....75

9.4. Condenser Pump Control Setting....75

9.4.1. Setting DT_PI Parameters for Pump VFD Control....77

9.4.2. Setting DP_PI Parameters for Pump VFD Control....77

9.4.3. Setting minimum / maximum number of operating pumps for each piping group 78

9.5. Cooling Tower Bypass Valve Control Setting....79

9.5.1. Setting PI Parameters for Cooling Tower Bypass Valve Control 80

9.6. System Control Setting 81

9.6.1. Power Failure Recovery 82

9.6.2. Protect System 83

9.6.3. Double Temperature Setpoint....84

9.6.4. Pull Down Rate Control 85

9.6.5. Setpoint reset 86

9.7. Source of Input Setting 88

  1. Trial Run 91

10.1. Chiller Trial Run....93

10.2. I/O Trial Run 93

10.3. BACnet Module Trial Run 100

  1. Saving / Loading Configuration Data....101

  2. Monitoring....103

12.1. Showing Current Status of System 103

12.2. Showing Current Status of Chillers 104

12.2.1. Showing the overview of chillers....104

12.2.2. Showing the detailed view of chillers 105

12.3. Showing Current Status of Evaporator Side Shut Off Valve 106

12.3.1. Showing the detailed view of Evaporator Side Shut Off Valve 106

12.4. Showing Current Status of Condenser Side Shut Off Valve 107

12.4.1. Showing the detailed view of Condenser Side Shut Off Valve 107

12.5. Showing Current Status of Primary Pumps....108

12.5.1. Showing the detailed view of Primary Pumps 108

12.6. Showing Current Status of Bypass Valve....109

12.7. Showing Current Status of Condenser Pumps 109

12.7.1. Showing the detailed view of Condenser Pumps....109

12.8. Showing Current Status of Cooling Tower Bypass Valve 110

12.9. Showing Current Status of Sensors 110

12.10. Showing Current Status of I/O 111

12.11. Showing Current Status of Controls....111

12.11.1. Show current status of chiller control 112

12.11.2. Show current status of primary pump control....112

  1. Operation....113

13.1. Basic Commanding....113

13.2. Resetting emergency stop 114

13.3. Setting Chillers to "Maintenance" 115

  1. Alarming....117

14.1. Showing Current List of Alarms....117

14.2. Showing History of Alarms....118

14.3. Deleting History of Alarms....119

14.4. Resetting Alarms 120

  1. APPENDIX – Alarms....123

15.1. Alarm Codes....123

15.1.1. Alarm for the chiller system 123

15.1.2. Alarms for individual equipment....126

  1. APPENDIX – BACnet Integration Data (Main Controller) 127

  2. APPENDIX – HMI Monitoring and Command....128

  3. APPENDIX - I/O Mapping....130

  4. APPENDIX – Compatibility List .....139

  5. APPENDIX – Integrated Modbus Points....140

20.1.Global chillers....140

20.2. U.S. Chillers....141

1. Introduction

READ THIS MANUAL CAREFULLY BEFORE INSTALLING AND STARTING UP THE UNIT. IMPROPER INSTALLATION COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT OR INJURE TO PEOPLE. THE UNIT MUST BE INSTALLED BY A PROFESSIONAL OPERATOR/TECHNICIAN UNIT STARTUP HAS TO BE PERFORMED BY AUTHORIZED AND TRAINED PROFESSIONAL ALL ACTIVITIES HAVE TO BE PERFORMED ACCORDING TO LOCAL LAWS AND REGULATION. UNIT INSTALLATION AND START UP IS ABOSOLUTELY FORBIDDEN IF ALL INSTRUCTION CONTAINED IN THIS MANUAL ARE NOT CLEAR. IF CASE OF DOUBT CONTACT THE MANUFACTURER REPRESENTATIVE FOR ADVICE AND INFORMATION.

2. Functional Overview of iCM

2.1. System Topology

The system topology for the package of iCM is described below.

Table 1 - Equipment overview

AvailabilityDrivePipingCooling type
CSDVFDManifoldedDedicatedAir-cooledWater-cooled
ChillerYesYesYes--YesYes
Evaporator pumpsYesYesYesYesYes--
Shut-off valves (evaporator side)Yes------
Bypass valve (evaporator side)Yes------
Condenser pumpsYesYesYesYesYes--
Shut-off valves (condenser side)Coming Soon------
Bypass valve (condenser side)Coming Soon------

CSD: Constant Speed Driver
VFD: Variable Frequency Driver

DAIKIN EKDICMPAL - System Topology - 1

flowchart
graph TD
    A["Daikin On Site"] -->|Internet connection| B["Internet"]
    B --> C["Web HMI"]
    C --> D["Ethernet"]
    D --> E["Remote HMI"]
    E --> F["Modbus / RS485"]
    F --> G["I/O Modules"]
    G --> H["Dalkin chillers"]
    H --> I["Up to 8 Chillers"]
    I --> J["Connect DAIKIN chillers through Modbus"]
    K["General BAS/BMS"] --> L["BACnet / IP"]
    L --> M["Modbus Module"]
    N["Modbus / RS485 integration"] --> O["BACnet module"]
    P["Main Controller"] --> Q["Basic control capability"]
    P --> R["Alarming"]
    P --> S["In-built HMI"]
    T["DiDc AlAc"] --> U["I/O Modules"]
    V["Evap. Pumps (VFD / CSD), Cond. Pumps (VFD / CSD) Cooling Towers (VFD / CSD), Bypass Valves, sensors etc."] --> W["Modbus / RS485"]

Figure 1 - System Topology of iCM

☐ BACnet / IP connectivity is offered through BACnet Module for integration with general BAS/BMS
☐ Built-in HMI, Remote HMI and Web HMI (on Daikin on Site; DoS) is available for monitoring and configuration
From main controller, connectivity to "Daikin on Site" (DoS: Cloud platform), remote monitoring and service

3. Technical Overview

iCM (intelligent Chiller manager) consists of:

Electrical Panel
☐ Temperature sensors
☐ 3G router for internet connectivity
☐ Optional devices:

o Communication modules for BMS integration

- By-pass valve on primary loop

3.1. Electrical Panel

Table 2 Electrical panel technical data

EKDICMPABEKDICMPALEKDICMPAF
Environmental conditionsOperating air temperature-20...60°C
Storage temperature-40...70°C
Humidity<90%Rh (without condensation)
Air pressuremin. 700KPa, corresponding to max. 3000m above sea level
DimensionPanelMetal
External doorN/ALexan
Internal doorMetal with lampsMetal with HMI and lamps and three position selector
Size (L x H x W)500x700x250600x800x300800x1000x300
Weight30Kg40Kg50Kg
IP Code (International protection)IP54 (external)IP66 (external)IP66 (external)
IP20 (internal)IP20 (internal)IP20 (internal)
IK Code (mechanical protection)IK08
Power SupplyPhase1 phase
Frequency50...60 Hz
Input Voltage230 VAC +/- 10%
Output Voltage24VAC
Nominal Current40A
Peak Current10kA
Power ConsumptionController + ModulesMax: 161 VATypical: 150 VA
CommunicationsMODbus RTU for chiller networkRS-485:

3.2. Controllers

With the Microtech III family of controllers, Daikin offers maximum flexibility in the control and monitoring of chiller plant systems. Comprehensive system functions such as alarm management, time scheduling and trend data storage cover all requirements associated with the operation of a chiller plant room system.

□ Main controller
☐ Daikin on Site (DoS) through IP Service Port and internet connectivity
☐ Daikin Chiller Management through in-built MODbus RTU/RS485
☐ Integration by BMS (Building Management Station)
BACnet communication module
MODbus communication module
□ I/O modules

DAIKIN EKDICMPAL - Controllers - 1

natural_image Collection of electronic devices including PLCs, relays, and control panels (no visible text or labels)

DAIKIN EKDICMPAL - Controllers - 2

flowchart
graph TD
    A["Modbus RS485"] --> B["Peripheral Bus"]
    C["System integration"] --> D["IP Service interface"]
    D --> E["User/Tool Interface"]
    B --> F["Computer with 'e'"]
    E --> G["Computer with 'e'"]
    F --> H["Computer with 'e'"]
    G --> I["Computer with 'e'"]

Figure 2 Controller architecture

3.2.1. Main Controller

The main controller provide the following functions

□ Control functions
□ Built-in HMI for monitoring and setting
☐ Onboard Modbus / 485 for connection with Chiller Modbus network as Master device.
☐ Onboard IP Service Interface port for connection with Ethernet network
Onboard I/O's
☐ Provision for adding extension I/O modules
☐ Provision for adding communication modules

Tiger Performance Ground Mina Ground Mina Ground Mina Ground Mina

3.2.2. BACnet Module (Optional)

The BACnet module provides BACnet / IP integration when connected to the main controller.

DAIKIN EKDICMPAL - BACnet Module (Optional) - 1

3.2.3. MODbus Module (Optional)

The MODbus module provides Modbus RTU/ RS-485 integration as Slave device when connected to the main controller.

DAIKIN EKDICMPAL - MODbus Module (Optional) - 1

3.2.4. I/O Modules

The I/O modules provide additional I/O points by connecting to the main controller sensors, valve actuators, pumps and cooling towers are connected through the I/O module. The types of I/O points include the following.

☐ Analog Outputs: 4-20mA
☐ Analog Inputs: NTC 10K
☐ Digital Outputs: Potential free contacts (Non-Voltage)
☐ Digital Inputs are: Potential free / Potential contacts (Voltage)

The number of I/O modules needed varies depending on the system configuration..

DAIKIN EKDICMPAL - I/O Modules - 1

natural_image Exterior view of a Siemens industrial control unit (no visible text or symbols on the device body)

3.3. I/O Mapping

The mapping of I/O's on the main controller and the extension I/O modules is predefined. You can find the full list of I/O mapping in the appendix to this document (18 APPENDIX - I/O Mapping)

3.4. Networks

There are three communication Networks in the iCM:

Modbus® / RS485 for the integration of chiller data into the iCM controller
☐ BACnet / IP or Modbus®RTU / RS485 for the connection between the iCM controller and a general BAS/BMS
☐ IP Service interface over Ethernet for communication with Daikin on Site through Internet connection.

3.4.1. Modbus® / RS485 (Chiller Network)

The data residing in the chillers are integrated into the iCM controller using Modbus® / RS485. The set of Modbus® data point varies slightly with the chiller type. iCM has Modbus data map for Daikin global standard chillers pre-included, allowing for easy Modbus / RS485 connection through just simple configuration. (19 APPENDIX – Compatibility List)

In the appendix of this document you will find an overview of which Modbus® points that are integrated into the iCM (20 APPENDIX – Integrated Modbus Points)

3.4.2. BACnet

For general integration of the iCM and a BAS/BMS workstation, BACnet is available.

You can find the full list of BACnet points for iCM in the appendix to this document (16 APPENDIX – BACnet Integration Data (Main Controller)) Modbus®

For general integration of the iCM and a BAS/BMS workstation, MODbus RTU can be provided under request.

Providing an internet connectivity to the controller through onboard IP service interface, it is possible to take advantage of the Daikin On Site service.

Daikin On Site makes use of the benefits offered by the cloud technology that allows remote access and servicing at any time from any location. All data from the system plant-room are constantly collected and automatically stored in the cloud server. Customer can access and

☐ monitor in real time the system through a graphical interface
☐ manage the stored data to create trend
☐ download the data from the server.

Daikin On site permits system diagnostic in real time, simple maintenance, energy efficiency evaluation and optimization.

3.5. Human Machine Interface (HMI)

Depended on the sold solution the system comes with one or more of the following HMI's:

□ Built-in HMI on the controller
Remote HMI
WEB HMI

You can find the list of points that can be monitored and commanded from the HMI in the appendix (17 APPENDIX – HMI Monitoring and Command)

NOTE: Remote HMI is not provided with EKDICMPAB

3.5.1. Built-in HMI

Built-in HMI is the HMI directly on the iCM main controller. Built-in HMI is capable of full operation of the iCM.

It has an LCD display for text and icons. The push dial and buttons allows for easy operation.

3.5.2. Remote HMI

The Remote HMI is capable of full operation and configuration of the iCM.

The remote HMI has a high-resolution illuminated LCD display for text and graphics, push dial and buttons for operation, and a common alarm indicator.

The Remote HMI can be mounted e.g. in the operators office or at the iCM panel door.

MOSER MOUNT Entry Password Quick Menu Unit System Access Data Output Data AHD

DAIKIN EKDICMPAL - Remote HMI - 2

natural_image Front view of a white electronic device with a green screen and control buttons (no visible text or symbols)

3.5.3. Web HMI

With its integrated Internet technology, the embedded Web server allows full plant operation of the iCM using standard Web browsers.

3.6. Temperature sensors

Two immersion temperatures sensors are included in the kit to measure the entering and leaving water temperature of the system.

Table 3 Temperature sensors technical data

Technical dataTypeImmersion temperature sensor
Sensing elementNTC10K
Immersion length100mm
Functional dataMeasuring rate-30...125°C
Time constant30s
AccuracyRefer to sensor datasheet
Nominal pressurePN16
Degree of protectionProtection classIII according to EN 60730-1
Electrical connectionsScrew terminals1 x 2,5 mm ^2 or 1,5 mm ^2
ConnectionsInterchangeable
Environmental conditionsOperationClass 3K5
Temperature-25...70°C
Humidity5...95% r.h.

3.7. Wireless Router

Providing internet connectivity to the controller, it is possible to start the Daikin on Site service for remote monitoring and data storing.

The 3G router is part of the iCM standard package.

Table 4 Wireless Router technical data

Technical dataWireless 3G ModemVODAFONE MachineLink_3G
RF AntennaPANORAMA ANTENNAS MAR-7-21-2SP
ConnectionsRJ45 Ethernet10/100 base T
Power supplyMEAN WELL10W AC/DC
Input Voltage115/230VAC
Output Voltage12VDC
Environmental conditionsAmbient temperature-30...70°C
Ambient humidity90% r.h. @ 60°C

3.8. Differential Pressure sensor (Optional)

In case of primary loop variable flow and consequently control of variable frequency driver on the primary pumps, a differential pressure sensor must be installed in the chiller plant-room to allow iCM perform the correct control logic.

Table 5 Differential Pressure Sensor Technical data

Technical dataTypeDifferential pressure sensor
For neutral or midly corrovise liquids
Measuring elementCeramic
Functional dataMeasuring range0...1.6 bar0...2.5 bar0...4 barAccording to requested range
Accuracy0.1% Full scale
Response time<5ms
Admissible temperature of medium-15...80°C
Operating voltageDC 11...33V
Output signalDC 4...20mA
Degree of protectionProtection classIP65
ConnectionElectrical cablePlug with seals and PG9 cable glands included
Pressure connectionsMale-threaded G1/8" with screwed fitting for copper pipes, 6mm diameter
Environmental conditionAmbient temperature-15...85°C
Ambient humidity<95% r.h. (non-condensing)

4. Electrical Installation

4.1. General specifications

All electrical connections to the unit must be carried out in compliance with laws and regulations in force.

All installation, management and maintenance activities must be carried out by qualified personnel.

Refer to the specific wiring diagram for the unit you have bought. Should the wiring diagram not be on the control panel or should it have been lost, please contact your manufacturer representative, who will send you a copy.

In case of discrepancy between wiring diagram and electrical panel/cables, please contact the manufacturer representative.

Only use copper conductors. Failure to use copper conductors could result in overheating or corrosion at connection points and could damage the control panel.

To avoid interference, all control wires must be connected separately from the power cables. Use different electrical passage ducts for this purpose.

Particular care must be taken when realizing wire connections to the switchbox; if not properly sealed, cable entries may allow ingress of water into the switchbox which may cause damage to the equipment inside.

Before any installation and connection works, the unit must be switched off and secured.

This product complies with EMC standards for industrial environments. Therefore it is not intended for use in residential areas, e.g. installations where the product is connected to a low voltage public distribution system. Should this product need to be connected to a low voltage public distribution system, specific additional measures will have to be taken to avoid interference with other sensitive equipment.

4.2. Operator's responsibility

It is essential that the operator is appropriately trained and becomes familiar with the system before operating the panel. In addition to reading this manual, the operator must study the databook for functional overview and the wiring diagram in order to understand start-up sequence, operation, management of the peripherals connected to the control panel.

5. Mechanical Installation

5.1. Control Panel installation

Control panel can be installed free standing taking care of the following minimum clearance requirements:

Front View Minimum Clearance Top Side: 150mm Minimum Clearance Bottom Side: 150mm

Top View Rear Wall Minimum Clearance Lateral Side: 150mm External Door Minimum Clearance Front Side: 600mm Frontal Wall

Figure 3 Minimum Clearance Requirements

Cable entry hole is on the bottom side of the panel

NOTE: dimension of the external door are shown in Table 2 Electrical panel technical data

For the hanging installation on a wall, please use the brackets shown in the following picture, provided with panel:

DAIKIN 4x Rear Bracket

Figure 4 Brackets position

NOTE: Weight of different sizes of the panel are shown in Table 2 Electrical panel technical data

5.2. Temperature sensor installation

The sensors should be located on the supply header and on return header.

The location should be chosen such that the water must be well mixed where the temperature is acquired.

The sensor should be mounted such that the cables does not enter from the top (only by side).

The immersion length must be at least 60mm.

Technical diagram showing various pipe fitting and mounting mechanisms with labeled parts and dimensions

Figure 5 Temperature sensor mounting

For more information, please refer to datasheet and installation guide provided with sensor.

5.3. Differential Pressure sensor installation

Differential pressure sensors must be mounted between the inlet and outlet water pipes of the furthest load in the system.

DAIKIN EKDICMPAL - Differential Pressure sensor installation - 1

flowchart
graph TD
    A["Load"] --> B["DP1"]
    B --> C["TEW1"]
    B --> D["TEW2"]
    C --> E["Chiller"]
    D --> F["Chiller"]
    E --> G["Chiller"]
    F --> H["Chiller"]
    G --> I["VFD"]
    H --> J["VFD"]
    I --> K["VFD"]
    J --> L["VFD"]
    M["iCM"] --> N["Control Unit"]
    style A fill:#f9f,stroke:#333
    style M fill:#bbf,stroke:#333

Figure 6 Differtial pressure sensor position

The sensor must be always mounted lower than the pressure measuring points.

DAIKIN EKDICMPAL - Differential Pressure sensor installation - 2

flowchart
graph LR
    A["Supply"] --> B["Process Unit 1"]
    B --> C["Return"]
    D["P1"] --> E["Feedback Loop"]
    E --> F["P2"]
    F --> G["Output"]
    style A fill:#f9f,stroke:#333
    style G fill:#bbf,stroke:#333

Figure 7 DP Sensor mounting

For detailed information, please refer to the datasheet and installation guide provided with sensor.

6. Description of Operation

6.1. Menu Structure

The menu structure of iCM is described below.

□ Status

○ Command
Emergency Stop Reset
○ Chiller Status
- Chiller#01 Detail
...
- Chiller#08 Detail
- EvShutOffValve Status
- EvSO_Valve01 Detail
...
- EvSO_Valve08 Detail
○ CndShutOffValve Status
- CndSO_Valve01 Detail
...
- CndSO_Valve08 Detail
o Primary Pump Status
■ Primary Pump#01 Detail
...
■ Primary Pump#08 Detail
○ Bypass Valve Status
- CondenserPump Status
- CondenserPump01 Detail
...
- CondenserPump08 Detail
- CTBypassValve Status
- Sensors Status
- I/O Status
- Control Status
- ChillerCtrl Status
- PriPpCtrl Status

Setting

- System Control Parameters

■ Double Temperature Setpoint

■ Pull Down Rate Control

■ Power Failure Recovery

- SetptReset

- Protect System

○ Device Control Parameters

- Chiller Control

■ Primary Pump Control

■ Bypass Valve Control

- CondenserPump Control

- CTBypassValve Control

- Control Mode Setting

- System Setting

- Date/Clock

Network

- Main NetworkSetting

- BACnet NetworkSetting

• Daikin On Site Status

• HMI for Web Setting

- About

□ Config Mode

○ Device Config

  • System Config
  • Chiller Config
    ■ Primary Pump Config
  • Sensors Config
    ■ Modbus Comm. Setting

○ Trial Run

  • Chiller Trial Run
    ■ I/O Trial Run (#1 to #17)

○ Device Registration

  • Chiller Registration
    ■ Primary Pump Registration
    ■ CondenserPump Registration
    ■ CTBypassValve Registration
  • Sensors Registration
    ■ ExtI/O Registration

- Backup/Restore

- Data Management

\*Special menus

Password

- Enter Password

□ Alarm entry

○ Alarm List overview
- Alarm History overview

6.2. Basic Parts and Operation

Basic parts and operation of iCM controller are described below.

LCD 4 Rows 22 A. B. C. D. E. F.

Figure 8 - Controller description
A) Alarm Button: Used to jump to "Alarming" Screen
B) Home Button: Used to jump to "MainMenu" Screen
C) Back Button: Used to go back one screen or Discard input value
D) value Click-dial: Turn: Select Next/Previous row or Change input

Push: Jump to linked page or Validate input value
*When using the click-dial, turning the dial faster enables bigger digit of input value to change.
E) BSP Indicator LED:
This LED indicates the status of the controller

ModeLED status
SW update mode (download active on a new BSP, application)Every second alternating between red and yellow
Application runningGreen on
Application loaded but not runningYellow on
Application not loadedYellow flashing (50 ms on, 1000 ms off)
BSP error (software error)Red blinking at 2 Hz
Hardware errorRed on

F) Bus Indicator LED: This LED only indicates the status of the integrated modem communication.

ModeLED status
No modem connected, or LED disabledOff
Modem connected and initialized no communication activeYellow on
Modem connected and communication activeGreen on
Modem connected but errors active (like provider missing, no initialization possible)Red on
BSP error (software error)Red blinking at 2Hz
Hardware errorRed on

6.3. LCD Panel Display

Below, basic composition of LCD panel display is explained.

DAIKIN EKDICMPAL - LCD Panel Display - 1

flowchart
graph TD
    A["Screen1"] --> B["5-14"]
    C["ParentCategory"] --> D["#04"]
    E["Option1"] --> F["E-1"]
    G["Link"] --> H["F"]
    I["Screen2"] --> J["C-2"]
    K["Setting"] --> L["Option1"]
    M["Status"] --> N["#04"]
    O["ParentCategory"] --> P["ON"]

A. Hidden row indicator

▼ : Hidden rows exist below
◆ : Hidden rows exist below and above
▲ : Hidden rows exist above

B. Screen title

Title of the currently displayed screen

C. Row number

C-1) Current row / Available rows on each screen is displayed
C-2) Only current row is shown when alarm sign 📄s displayed

D. Item name

Item name is displayed on the left side

E. Value

Current status or setting is displayed on the right side.

E-1) Unchangeable values display the status
E-2) Changeable values can be modified by selecting the row then clicking on the click-dial

DAIKIN EKDICMPAL - LCD Panel Display - 2

F. Link

: Link to another page available. You can jump to the linked page by clicking on the click-dial

G. Current row

Currently selected row is shown with inverted cursor. The cursor can be moved by turning the click-dial

G-1) Only item name or “-” character is inverted for rows with unchangeable value

G-2) Whole row is inverted for rows with changeable value

H. Hierarchy

Item name with “-” indicate that it is a child of the above item.

I. Alarm

Alarm sign ☐s shown when there is an active alarm. You can check the details of the alarm by pushing the alarm button ☐

6.4. Setting Address of Extension I/O Modules

For each extension I/O module, predefined address needs to be set via DIP switches on the modules as shown below.

ON DIP 1 2 3 4 5 6

Figure 9 - DIP Switches

Table 6 DIP Switch Setting

NameAddr.DIP switch setting
Switch1Switch2Switch3Switch4Switch5Image
Ext. Module1P.P.1PrimPmp 1-21OFFOFFOFFOFFONDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 2
Ext. Module2P.P.2PrimPmp 3-42OFFOFFOFFONOFFDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 3
Ext. Module3P.P.3PrimPmp 5-63OFFOFFOFFONONDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 4
Ext. Module4P.P.4PrimPmp 7-84OFFOFFONOFFOFFDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 5
Ext. Module5S.V.1ShutOffVlv 1-45OFFOFFONOFFONDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 6
Ext. Module6S.V.2ShutOffVlv 5-86OFFOFFONONOFFDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 7
Ext. Module9CW.Sns.1CoolingSns 1-29OFFONOFFOFFONDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 8
Ext. Module10CW.Sns.2CoolingSns 3-410OFFONOFFONOFFDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 9
Ext. Module11CW.P.1CoolingPmp 1-211OFFONOFFONONDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 10
Ext. Module12CW.P.2CoolingPmp 3-412OFFONONOFFOFFDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 11
Ext. Module13CW.P.3CoolingPmp 5-613OFFONONOFFONDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 12
Ext. Module14C.W.P.4CoolingPmp 7-814OFFONONONOFFDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 13
Ext. Module15CW.S.V.1ShutOffVlv 1-415OFFONONONONDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 14
Ext. Module16CW.S.V.2ShutOffVlv 5-816ONOFFOFFOFFOFFDAIKIN EKDICMPAL - Setting Address of Extension I/O Modules - 15

6.5. Password Protection

iCM has password protection functionality to avoid unauthorized changes in the setting.

7. Scenario of Interaction

Table 7 illustrates overview of workflow for working with iCM. Detail of each scenario is described in the following pages.
Table 7 Scenario of Interaction

A. Initial configuration / Commissioning7.1.1 On Site
7.1.2 Off Site
B. Monitoring7.2.1 Status Monitoring
7.2.2 Alarm Monitoring
C. Operation7.3.1 Commanding
7.3.2 Parameter Tuning
D. Maintenance7.4.1 Equipment Maintenance
7.4.2 HVAC System Component Change

7.1. Workflow for Initial Configuration / Commissioning

7.1.1. On Site

Table 8 illustrates steps for initial configuration of iCM on site.

Table 8 Workflow for Initial Configuration / Commissioning On Site

StepNameDescriptionReference chapter
1Password inputInput password to show service menu8.1 Password Input
2Set system to Config ModeSet system to Config Mode to enable equipment registration etc8.2 Setting System to Config Mode
3System ConfigurationSetting of IP address, date and time etc8.3 System Configuration Setting
4Equipment registrationRegistration of equipment for control from iCM8.4 Equipment Registration
5Equipment Initial settingInitial setting for each equipment8.5 Equipment Configuration
6Equipment control settingSetting of parameters for equipment control (e.g. chiller staging, pump VFD control etc)9 Equipment Control Setting
7System control settingSetting of parameters for system control (e.g. double setpoint, pull down rate control etc)9.6 System Control Setting
8Source of input settingSetting of source of input for each command9.7 Source of Input Setting
9Trial runSend command to each equipment to check connection10 Trial Run
10Backup configurationBackup configuration data to SD card11 Saving / Loading Configuration Data
11Unset Config ModeUnset system from config mode to enable system operation8.2 Setting System to Config Mode

7.1.2. Off Site

Table 9 illustrates steps for initial configuration of iCM off site.

Table 9 Workflow for Initial Configuration / Commissioning Off Site

StepNameDescriptionReference chapter
With Off-site iCM1Password inputInput password to show service menu8.1 Password Input
2Set system to Config ModeSet system to Config Mode to enable equipment registration etc8.2 Setting System to Config Mode
3System settingSetting of IP address, date and time etc8.3 System Configuration Setting
4Equipment registrationRegistration of equipment for control from iCM8.4 Equipment Registration
5Equipment Initial settingInitial setting for each equipment8.5 Equipment Configuration
6Equipment control settingSetting of parameters for equipment control (e.g. chiller staging, pump VFD control etc)9 Equipment Control Setting
7System control settingSetting of parameters for system control (e.g. double setpoint, pull down rate control etc)9.6 System Control Setting
8Source of input settingSetting of source of input for each command9.7 Source of Input Setting
9Save configurationSave off-site configuration data to SD card11 Saving / Loading Configuration Data
With On-site iCM10Set system to Config ModeSet system to Config Mode to enable trial run menu8.2 Setting System to Config Mode
11Load configurationLoad configuration to on-site iCM11 Saving / Loading Configuration Data
12System ConfigurationSetting of IP address, date and time which could not be done off-site8.3 System Configuration Setting
13Trial runSend command to each equipment to check connection10 Trial Run
14Backup configurationBackup configuration data to SD card11 Saving / Loading Configuration Data
15Unset Config ModeUnset system from config mode to enable system operation8.2 Setting System to Config Mode

7.2. Workflow for Monitoring

7.2.1. Status Monitoring

Table 10 illustrates steps for status monitoring on iCM
Table 10 Workflow for Status Monitoring

StepNameDescriptionReference chapter
1Monitor StatusMonitor status of system and each equipment to find potential problems12.1 Showing Current Status of System12.2 Showing Current Status of Chillers12.3 Showing Current Status of EvaporatorSide Shut Off Valve12.4 Showing Current Status of CondenserSide Shut Off Valve12.5 Showing Current Status of Primary Pumps12.6 Showing Current Status of Bypass Valve12.7 Showing Current Status of CondenserPumps12.8 Showing Current Status of Cooling Tower Bypass Valve12.9 Showing Current Status of Sensors12.10 Showing Current Status of I/O

7.2.2. Alarm Monitoring

Table 11 illustrates steps for alarm monitoring on iCM
Table 11 Workflow for Alarm Monitoring

StepNameDescriptionReference chapter
1Check AlarmCheck to see which alarm is active14 Alarming
2Make Corrective ActionsMake necessary changes, actions- Not done from iCM
3Monitor StatusMonitor status of system and each equipment to ensure the system is operating correctly12 Monitoring
4Alarm ResetReset Alarm from iCM as needed14.4 Resetting Alarms

7.3. Workflow for Operation

7.3.1. Commanding

Table 12 illustrates steps for alarm monitoring from iCM
Table 12 Workflow for commanding from iCM

StepNameDescriptionReference chapter
1Source of input settingSet source of input for desired command to manual9.7 Source of Input Setting
2CommandSend various commands from HMI13 Operation

7.3.2. Parameter Tuning

Table 13 illustrates steps for tuning of control parameters from iCM
Table 13 Workflow for Parameter Tuning

StepNameDescriptionReference chapter
1Monitor StatusMonitor status of system and each equipment to find potential problems12 Monitoring
2Password inputInput password to show service menu8.1 Password Input
3Equipment control settingSetting of parameters for equipment control (e.g. chiller staging, pump VFD control etc)9 Equipment Control Setting
4System control settingSetting of parameters for system control (e.g. double setpoint, pull down rate control etc)8.3 System Control Setting
5Monitor StatusMonitor status of system and each equipment to find potential problems12 Monitoring

7.4. Workflow for Maintenance

7.4.1. Equipment Maintenance

Table 14 illustrates steps for maintenance of equipment.
Table 14 Workflow for Maintenance of Equipment

StepNameDescriptionReference chapter
1Set equipment as Not AvailableSet equipment as “Not Available” from iCM to exclude from controls13.3 Setting Chillers to “Maintenance”
2Maintenance of equipmentDo needed maintenance of equipment- Not done from iCM
3Set equipment as AvailableAfter needed maintenance is done, set equipment as “Available” from iCM to be included by controls.13.3 Setting Chillers to “Maintenance”

7.4.2. HVAC System Component Change

Table 15 illustrates steps for HVAC system component change.
Table 15 Workflow for HVAC System Component Change

StepNameDescriptionReference chapter
1Password inputInput password to show service menu8.1 Password Input
2Source of input settingChange source of input for ON/OFF signal to manual if necessary in order to stop the system9.7 Source of Input Setting
3Stop the systemStop the system from HMI13 Operation
4Set system to Config ModeSet system to Config Mode to enable equipment registration etc8.2 Setting System to Config Mode
5Equipment registrationRegistration of new equipment or unregister unnecessary equipment8.4 Equipment Registration
6Equipment ConfigurationInitial setting for each of the new equipment8.5 Equipment Configuration
7Equipment control settingSetting of parameters for equipment control (e.g. chiller staging, pump VFD control etc)9 Equipment Control Setting
8Trial runSend command to each equipment to check connection10 Trial Run
9Backup configurationBackup configuration data to SD card11 Saving / Loading Configuration Data
10Unset Config ModeUnset system from config mode to enable system operation8.2 Setting System to Config Mode

8. Configuration

Menu structure of related screens is shown below.

  • Password.... Input screen for password to show hidden menu
    ConfigMode....Set system to Config Mode in order to do initial configuraiton

8.1. Password Input

Steps for inputting the password to show normally hidden menu are described below.

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial Ⓞ to select "Password" menu then press down on the click-dial to jump to "Password" screen.
MainMenu4/4
Status
Setting
ConfigMode
Password
  1. On the "Password" screen, turn the click-dial to select "Enter Password" menu then press down on the click-dial to jump to "Enter Password" screen.
Password1/2
Enter Password
Close Account
  1. On the "Enter Password" screen, turn the click-dial Ⓞ to select "Entry" menu then press down on the click-dial Ⓥ to jump to input mode screen for "Entry".

Enter Password 2/2 Entry ****

  1. On the input mode screen for "Entry", for each of the four digits of the password, turn the click-dial to change value and press down on the click-dial to validate your command.

When all four digits have been input, the scree will automatically jump to "MainMenu". Note: If 10 minutes passes without any user operation, the system automatically logs out from password login and the password needs to be input again to log in. Log out can be done manually by entering 0000 as the password.

8.2. Setting System to Config Mode

To do initial configuration such as registering equipment and sending command to equipment manually for trial run purposes, iCM needs to be put into "Config Mode"

Note: To put iCM into "Config Mode" system ON/OFF status needs to be OFF. Also while in "Config Mode", you cannot change the system status to ON as displayed in Figure 10.

DAIKIN EKDICMPAL - Setting System to Config Mode - 1

flowchart
graph LR
    A["Config Mode ON"] -->|Setting to Config Mode| B["System OFF"]
    B -->|Unsetting Config Mode| C["System OFF"]
    C -->|System Stop command| D["System ON"]
    D -->|System Run command| C

Figure 10 System Status Transition

Steps for putting iCM to "Config Mode" are described below.
1. Press the Home Button ☐ to show the "MainMenu" screen.

MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "ConfigMode" menu then press down on the click-dial to jump to "ConfigMode" screen.

DAIKIN EKDICMPAL - Setting System to Config Mode - 2

Status
Setting
ConfigMode
Password
  1. On the "ConfigMode" screen, turn the click-dial ⏻ to select "ConfigMode" menu then press down on the click-dial ⏻ to jump to input mode screen for "ConfigMode" menu.
ConfigMode1/8
ConfigModeOFF
SystemSetting
DeviceRegistration
DeviceConfig
  1. On the input mode screen for "ConfigMode" menu, turn the click-dial to select "ON" then press down on the click-dial to validate the command.
ConfigMode1/1
ConfigModeOFF
ConfigMode1/1
ConfigModeON

8.3. System Configuration Setting

Various parameters related to iCM system such as language setting, unit settings can be done from system setting menu.

Menu structure and items which can be set are described below.

○ ConfigMode
- SystemSetting

□ SystemSetting

○ Language......Switch between Japanese/English
Unit .... Switch between Metric / imperial unit system
- Date / Clock....Set date, time, and UTC time difference setting
○ Network ...... Set network related settings
- MainController......Set IP address, DHCP, G/W, subnet mask, and cloud
- BACneModule......Set IP address, DHCP, G/W, subnet mask, and device ID
- Cloud ....Set password
○ About .... About iCM

8.3.1. Setting Unit

Steps for changing current time / date settings are described below.

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial ⏻ to select "Setting" menu then press down on the click-dial ⏻ to jump to "Setting" screen.
MainMenu2/4
Status
Setting
ConfigMode
Password
  1. On the "Setting" screen, turn the click-dial to select "SystemSetting" menu then press down on the click-dial to jump to "System Setting" screen.
Setting4/5
SystemCtrlParam
DeviceCtrlParam
CtrlModeSetting
SystemSetting
  1. On the "System Setting" screen, turn the click-dial Ⓞ to select "Unit" menu, then press down on the click-dial Ⓥ to jump to input mode screen for "Unit" menu.
SystemSetting2/5
LanguageEnglish
UnitMetric
Date/Clock
Network
  1. On the input mode screen for "Unit" menu, turn the click-dial to select "Metric" or "Imperial" then press down on the click-dial to validate the command.
Unit1/1
UnitMetric
ConfigMode1/1
UnitImperial

8.3.2. Setting Current Time / Date

(Used screen: MainMenu → ConfigMode → Setting → System Setting → Date/Clock)

Steps for changing current time / date settings are described below.

  1. On the "Date/Clock" screen, turn the click-dial to select "Setting" menu then press down on the click-dial to jump to "Date/Clock Setting" screen.
Date/Clock1/4
Setting
Date(M/D/Y)01/16/2015
Time(H:M:S)17:33:25
UTC_TimeDiff-360min
  1. On the "Date/Clock Setting" screen, date and clock setting for the controller can be changed.
Date/Clock Setting1/4
Date(M/D/Y)01/16/2015
Time(H:M:S)17:33:25
UTC_TimeDiff-360min
Reset-

8.3.3. Changing Network Setting of Main Controller

(Used screen: MainMenu → ConfigMode → Setting → System Setting → Network)

Steps for changing network settings are described below.

- On the "Network" screen, current setting for network related setting of the Main controller can be checked.

Network1/12
MainController
-Setting
-IP192.168.0.3
-Mask255.255.255.0
-G/W192.168.0.1
-DHCPPassive
BACnet_Module
-Status/Setting
Daikin On Site
-Status
HMIforWeb
-Status

- On the "Network" screen turn the click-dial Ⓞ to select "Setting" menu under "MainController" then press down on the click-dial Ⓞ to jump to "MainController Network" screen.

Network2/12
MainController
-Setting
-IP192.168.0.3
-Mask255.255.255.0
-G/W192.168.0.1
-DHCPPassive
BACnet_Module
-Status/Setting
Daikin On Site
-Status
HMIforWeb
-Status

- On the "MainController Network" screen, network related setting for the main controller can be changed.

Main Network1/8
Gvn IP192.168.0.9
Gvn Mask255.255.255.0
Gvn G/W192.168.0.13
DHCPPassive
PrimDNS000.000.000.000
SecDNS000.000.000.000
MAC00-00-00-00-00-00
Reset-

- After setting is complete, it is required to reset the controller to reflect the setting. On the "MainController Network" screen, turn the click-dial 🔓 to select "Reset" menu then press down on the click-dial 🔓 to jump to input mode screen for "Reset"

Main Network8/8
Gvn IP192.168.0.130
Gvn Mask255.255.255.0
Gvn G/W192.168.0.254
DHCPPassive
PrimDNS000.000.000.000
SecDNS000.000.000.000
MAC00-00-00-00-00-00
Reset-

- On the input mode screen for "Reset", turn the click-dial to change value to "Reset" then press down on the click-dial to validate your setting. The controller will restart and your settings will be reflected.

Caution: By resetting the controller, the system will stop until the controller has finished restarting.

8.3.4. Changing Network Setting of BACnet Module

(Used screen: MainMenu → ConfigMode → Setting → System Setting → Network)

Steps for changing current BACnet settings are described below. Make sure the BACnet Module is connected correctly before changing the network setting.

  1. On the "Network" screen, current setting for network related setting of BACnet Module can be checked.
Network1/12
MainController
-Setting
-IP192.168.0.3
-Mask255.255.255.0
-G/W192.168.0.1
-DHCPPassive
BACnet_Module
-Status/Setting
Daikin On Site
-Status
HMIforWeb
-Status
  1. On the "Network" screen turn the click-dial ⏻ to select "Setting" menu under "BACnetModule" then press down on the click-dial ⏻ to jump to "BACnet NetworkSetting" screen.
Network8/12
MainController
-Setting
-IP192.168.0.3
-Mask255.255.255.0
-G/W192.168.0.1
-DHCPPassive
BACnet_Module
-Status/Setting
DaikinOnSite
-Status
HMIforWeb
-Status
  1. On the "BACnet NetworkSetting" screen, network related setting for the BACnet Module can be changed.
BACnet IP Card1/19
StateHardware
Comm FailureActive
BACnet:
Device name
-
Device ID1
Port0
TCP/IP
DHCPPassive
Actual IP192.168.0.9
Actual Mask255.255.255.0
Act Gateway192.168.0.13
Given IP192.168.0.9
Given Mask255.255.255.0
Giv Gateway192.168.0.13
Write settingsPassive
General
Software Version
Reset-

Note: To overwrite the current settings “Write settings” must be turned into “Active”, before resetting the controller.

BACnet IP Card19/19
Write settingsActive
General
Software Version
Reset
  1. After setting is complete, it is required to reset the controller to reflect the setting.

8.3.5. Changing Network Setting of Daikin On Site (DoS: Cloud Connection)

(Used screen: MainMenu → ConfigMode → Setting → System Setting → Network)

  1. On the "Network" screen turn the click-dial Ⓞ to select "DaikinOnSite" then press down on the click-dial Ⓞ to jump to input mode screen for "DaikinOnSite"

On the input mode screen for "DaikinOnSite", turn the click-dial Ⓞ to change value to "Enable" then press down on the click-dial ⏻ to validate your setting.

DAIKIN EKDICMPAL - Changing Network Setting of Daikin On Site (DoS: Cloud Connection) - 1

flowchart
graph TD
    A["Network 1/1"] --> B["DaikinOnSite Disabled"]
    B --> C["Network 1/1"]
    D["DaikinOnSite Enable"] --> E["End"]
  1. On the "Network" screen turn the click-dial Ⓞ to select "Status" menu under "Daikin On Site" then press down on the click-dial Ⓥ to jump to "Cloud Status" screen.

Network 15/17 MainController -Setting ▶ -IP 192.168.0.3 -Mask 255.255.255.0 -G/W 192.168.0.1 -DHCP Passive BACnet_Module -Status/Setting ▶ Daikin on Site Enable -Status ▶ HMIforWeb Enable -Status ▶ Daikin On Site Status 1/8 ComState - CCLState - Activation Key XCHE-CNBI-NCAJ...

8.3.6. Showing information of iCM

(Used screen: MainMenu → ConfigMode → Setting → System Setting)

  1. On the "System Setting" screen, turn the click-dial to select "About" menu, then press down on the click-dial to jump to input mode screen for "About" menu.
SystemSetting5/5
UnitMetric
Date/Clock
Network
About
  1. The "About" menu displays versions of iCM and BSP.
About1/3
iCM-
-ApplicationiCM
-Datedd/mm/yyyy
-Version2.**.**
iCM_Ver_2.**.**
HMI-
-Verson
iCMd_Ver2.**.**
-GUID
4518B7BC-69D9-43A9-ABF0-945...
Controller
-BSP10.36
-SerialNr9554

8.4. Equipment Registration

Number and types of equipment which are controlled from iCM can be set from equipment registration menu.

Menu structure and items which can be set are described below.

○ ConfigMode

■ DeviceRegistration

□ DeviceRegistration

○ Chiller ......Register available chillers
○ PrimaryPump ...... Register available primary pumps
- CondenserPump ...... Register available condenser pumps
- CTBypassValve ....Register available CT bypass valves
- Sensors ...... Register available sensors
- ExtI/O...... Register available ext. modules
○ BACnet_Module......Register availability of BACnet module

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "ConfigMode" menu then press down on the click-dial to jump to "ConfigMode" screen.
MainMenu3/4
Status
Setting
ConfigMode
Password
  1. On the "Setting" screen, turn the click-dial to select "DeviceRegistration" menu then press down on the click-dial to jump to "DeviceRegistration" screen.
ConfigMode3/8
ConfigMode
SystemSetting
DeviceRegistration
DeviceConfig
  1. "DeviceRegistration" screen is shown. From this screen, you can register different equipment
DeviceRegistration1/14
Chiller
PrimaryPump
CondenserPump
CTBypassValve
Sensors
ExtI/O
BACnet_ModuleIgnoreCommError
Reset-

← 8.4.1 Chiller Registration
← 8.4.2 PrimaryPump Registration
← 8.4.3 CondenserPump Registration
← 8.4.4 CTBypassValve Registration
← 8.4.5 Sensors Registration
← 8.4.6 ExtI/O Registration
← 8.4.7 BACnet_Module Registration

NOTE: After registration of all equipment is complete, it is required to reset the controller to reflect the chenages before keeping on configuration.

- On the input mode screen for "Reset", turn the click-dial to change value to "Reset" then press down on the click-dial to validate your setting. The controller will restart and your settings will be reflected.

Caution: By resetting the controller, the system will stop until the controller has finished restarting.

8.4.1. Chiller Registration

(Used screen: MainMenu > ConfigMode > DeviceRegistration > Chiller Registration)

  1. From "DeviceRegistration" screen, turn the click-dial to select "Chiller" menu then press down on the click-dial to jump to "Chiller Registration" screen.
DeviceRegistration1/9
Chiller
PrimaryPump
CondenserPump
CTBypassValve
  1. "Chiller Registration" screen is displayed. Here, maximum of 8 chillers with respective evaporator and condenser side shut-off valves can be registered by setting the value to "Enable".
Chiller Registration1/25
-#01Enable
-EvShutOffValveDisable
-CndShutOffValveDisable
-#02Disable
-EvShutOffValveDisable
-CndShutOffValveDisable
-#03Disable
-EvShutOffValveDisable
-CndShutOffValveDisable
-#04Disable
-EvShutOffValveDisable
-CndShutOffValveDisable
-#05Disable
-EvShutOffValveDisable
-CndShutOffValveDisable
-#06Disable
-EvShutOffValveDisable
-CndShutOffValveDisable
-#07Disable
-EvShutOffValveDisable
-CndShutOffValveDisable
-#08Disable
-EvShutOffValveDisable
-CndShutOffValveDisable
Reset-

NOTE: In case of registration of air-cooled chiller CndShutOffValve must be set "Disable"

8.4.2. PrimaryPump Registration

(Used screen: MainMenu → ConfigMode → DeviceRegistration → PrimaryPump Registration)

NOTE: At least one primary pump (as dummy pump) must be registered, even if iCM does not have any management.

  1. From "DeviceRegistration" screen, turn the click-dial ⏻ to select "PrimaryPump" menu then press down on the click-dial ⏻ to jump to "PriPump Registration" screen.
DeviceRegistration2/9
Chiller
PrimaryPump
CondenserPump
CTBypassValve
  1. "PriPump Registration" screen is displayed. Here, maximum of 8 primary pumps can be registered by setting the value to "Enable".
PriPump Registration1/9
-#01Enable
-#02Disable
-#03Disable
-#04Disable
-#05Disable
-#06Disable
-#07Disable
-#08Disable
Reset-

8.4.3. CondenserPump Registration

(Used screen: MainMenu → ConfigMode → DeviceRegistration → CondenserPump)

NOTE: This menu displays on HMI, but hardware of models EKDICMPA* does not support this function.

NOTE: At least one condenser pump (as dummy pump) must be registered, even in case of air-cooled chiller plant room

  1. From "DeviceRegistration" screen, turn the click-dial Ⓞ to select "CondenserPump" menu then press down on the click-dial Ⓞ to jump to "CondenserPump Registration" screen.
DeviceRegistration3/9
Chiller
PrimaryPump
CondenserPump
CTBypassValve
  1. "CondenserPump Registration" screen is displayed. Here, maximum of 8 condenser pumps can be registered by setting the value to "Enable".
CondenserPump Registration1/9
-#01Enable
-#02Disable
-#03Disable
-#04Disable
-#05Disable
-#06Disable
-#07Disable
-#08Disable
Reset-

8.4.4. CTBypassValve Registration

(Used screen: MainMenu → ConfigMode → DeviceRegistration → CTBypassValve)

NOTE: This menu displays on HMI, but hardware of models EKDICMPA* does not support this function.

  1. From "DeviceRegistration" screen, turn the click-dial ⏻ to select "CTBypassValve" menu then press down on the click-dial ⏻ to jump to "CTBypassValve Registration" screen.
DeviceRegistration4/9
Chiller
PrimaryPump
CondenserPump
CTBypassValve
  1. "CTBypassValve Registration" screen is displayed. Here, maximum of 4 cooling tower bypass valves can be registered by setting the value to "Enable".
CTBypassValve Registration1/5
-#01Enable
-#02Disable
-#03Disable
-#04Disable
Reset-

8.4.5. Sensors Registration

(Used screen: MainMenu → ConfigMode → DeviceRegistration)

  1. From "DeviceRegistration" screen, turn the click-dial Ⓞ to select "Sensors" menu then press down on the click-dial Ⓥ to jump to "Sensors Registration" screen.
DeviceRegistration5/9
CTBypassValve
Sensors
ExtI/O
-Reset
  1. "Sensors Registration" screen is displayed. Here, sensors for each of the condenser piping groups (up to four) can be registered by setting the value to "Enable".
Sensors Registration1/18
OutdoorTempEnable
CndPipingGroup1
-CndWtLvgTempDisable
-CndWtEntTempDisable
-CndDiffPressEnable
CndPipingGroup2
-CndWtLvgTempDisable
-CndWtEntTempDisable
-CndDiffPressDisable
CndPipingGroup3
-CndWtLvgTempDisable
-CndWtEntTempDisable
-CndDiffPressDisable
CndPipingGroup4
-CndWtLvgTempDisable
-CndWtEntTempDisable
-CndDiffPressDisable
ResetReset

NOTE: This menu displays on HMI, but hardware of models EKDICMPA* does not support this function.

8.4.6. ExtI/O Registration

(Used screen: MainMenu → ConfigMode → DeviceRegistration)

  1. From "DeviceRegistration" screen, turn the click-dial to select "ExtI/O" menu then press down on the click-dial to jump to "ExtI/O Registration" screen.
DeviceRegistration6/9
CTBypassValve
Sensors
ExtI/O
-Reset
  1. From "ExtI/O Registration" screen, availability of 8 ExtI/O modules can be set. If ExtI/O is set as available but connection is not found, iCM will be in alarm status.
ExtI/O Registration1/18
-#01Disable
-#02Disable
-#03Disable
-#04Disable
-#05Disable
-#06Disable
-#09Disable
-#10Disable
-#11Disable
-#12Disable
-#13Disable
-#14Disable
-#15Disable
-#16Disable
-Reset-

← Availability of ExtIO #1
← Availability of ExtIO #2
← Availability of ExtIO #3
← Availability of ExtIO #4
← Availability of ExtIO #5
← Availability of ExtIO #6
← Availability of ExtIO #9
← Availability of ExtIO #10
← Availability of ExtIO #11
← Availability of ExtIO #12
← Availability of ExtIO #13
← Availability of ExtIO #14
← Availability of ExtIO #15
← Availability of ExtIO #16

8.4.7. BACnet\_Module Registration

(Used screen: MainMenu → ConfigMode → DeviceRegistration)

  1. From "DeviceRegistration" screen, availability of BACnet module can be set. If BACnet is set as available but connection is not found, iCM will be in alarm status.
DeviceRegistration8/9
PrimaryPump
ExtI/O
-Reset
BACnet_ModuleIgnoreCommError

← Availability of BACnet Module

8.5. Equipment Configuration

Initial setting of attributes for each equipment can be done from this menu. Menu structure and items which can be set are described below.

○ Config

■ DeviceConfig

□ DeviceConfig

  • System .... Set temperature setpoint
    ○ Chiller ....Set chiller type, capacity, run hours
  • EvShutOffValve .... Set whether feedback signal is available
    ○ CndShutOffValve ....Set availability for condenser pump shutoff valves
    o PrimaryPump....Set run hours, whether feedback signal is available
  • CondenserPump....Set piping groups for condenser pumps
  • Sensor .... Set input type for sensor
    ○ ModbusCommSetting ...... Set Modbus BaudRate, Parity, Stop Bits, and Time out
    ○ AiThreshold...... Set threshold for judging open loop of Ai signal

  • Press the Home Button ☐ to show the "MainMenu" screen.

MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "ConfigMode" menu then press down on the click-dial to jump to "ConfigMode" screen.
MainMenu3/4
Status
Setting
ConfigMode
Password
  1. On the "Setting" screen, turn the click-dial to select "DeviceConfig" menu then press down on the click-dial to jump to "DeviceConfig" screen.
ConfigMode3/4
ConfigMode
SystemSetting
DeviceRegistration
DeviceConfig
  1. "DeviceConfig" screen is shown. From this screen, you can do initial setting of equipment.
DeviceConfig1/12
System
Chiller
EvShutOffValve
-StatusSignalAvail
CndShutOffValve
-StatusSignalAvail
PrimaryPump
CondenserPump
Sensor
ModbusCommSetting
AiThreshold
-mA1.0mA

← 8.5.1 System Configuration
← 8.5.2 Chiller Configuration
← 8.5.3 Evaporator Shut Off Valve Configuration
← 8.5.4 Condenser Shut Off Valve
← 8.5.5 Primary Pump
← 8.5.6 Condenser Pump
← 8.5.7 Sensor
← 8.5.8 Modbus Communication Setting
← 8.5.9 Ai Threshold Setting

NOTE: After configuration of all equipment is complete, it is required to reset the controller to reflect the chenages before keeping on setting.

- On the input mode screen for "Reset", turn the click-dial to change value to "Reset" then press down on the click-dial to validate your setting. The controller will restart and your settings will be reflected.

8.5.1. System Configuration

(Used screen: MainMenu → ConfigMode → DeviceConfig → System Config)

  1. From "DeviceConfig" screen, turn the click-dial Ⓞ to select "System" menu then press down on the click-dial Ⓥ to jump to "System" screen.
DeviceConfig1/12
System
Chiller
EvShutOffValve
-StatusSignalAvail
  1. "System Config" screen is displayed. Here, you can configure attributes of chillers.
System Config1/3
TempSetPt
-MaxOutput48.9°C← a.
-MinOutput12.2°C← b.

Table 16 List of parameters which can be set from "Chiller Config" screen

IDNameDefinition
a.-MaxOutputMaximum temperature setpoint of system
b.-MinOutputMinimum temperature setpoint of system

8.5.2. Chiller Configuration

(Used screen: MainMenu → ConfigMode → DeviceConfig → Chiller Config)

  1. From "DeviceConfig" screen, turn the click-dial to select "Chiller" menu then press down on the click-dial to jump to "Chiller" screen.
DeviceConfig2/12
System
Chiller
EvShutOffValve
-StatusSignalAvail
  1. "Chiller Config" screen is displayed. Here, you can configure attributes of chillers.
Chiller Config1/65
Status SignalAvail
#01
-ChillerTypeMQ_GB
-CoolingMaxCap100kW
-Runhours10h
-PipingGroup1
-MinPumpReq1
-CndPipingGroup1
-CndMinPumpReq1
#02
-ChillerTypeMQ_GB
-CoolingMaxCap100kW
-Runhours10h
-PipingGroup1
-MinPumpReq1
-CndPipingGroup1
-CndMinPumpReq1
#03
-ChillerTypeMQ_GB
-CoolingMaxCap100kW
-Runhours10h
-PipingGroup1
-MinPumpReq1
-CndPipingGroup1
-CndMinPumpReq1
#04
-ChillerTypeMQ_GB
-CoolingMaxCap100kW
-Runhours10h
-PipingGroup1
-MinPumpReq1
-CndPipingGroup1
-CndMinPumpReq1
#05
-ChillerTypeMQ_GB
-CoolingMaxCap100kW
-Runhours10h
-PipingGroup1
-MinPumpReq1
-CndPipingGroup1
-CndMinPumpReq1
#06
-ChillerTypeMQ_GB
-CoolingMaxCap100kW
-Runhours10h
-PipingGroup1
-MinPumpReq1
-CndPipingGroup1
-CndMinPumpReq1
#07
-ChillerTypeMQ_GB
-CoolingMaxCap100kW
-Runhours10h
-PipingGroup1
-MinPumpReq1
-CndPipingGroup1

← h.

-CndMinPumpReq1
#08
-ChillerTypeMQ_GB
-CoolingMaxCap100kW
-Runhours10h
-PipingGroup1
-MinPumpReq1
-CndPipingGroup1
-CndMinPumpReq1

Table 17 List of parameters which can be set from "Chiller Config" screen

IDNameDefinition
a.StatusSignalAvailability of feedback signal for chiller ON/OFF status
b.-ChillerTypeChiller type to decide type of communication protocol
c.-CoolingMaxCapMaximum capacity (100% actual capacity) value of chiller
d.-RunhoursTotal run hours of chiller as initial value
e.PipingGroupPiping group of chiller to be associated with pumps
f.MinPumpReqMinimum number of pumps required from chiller
g.CndPipingGroupPiping group of chiller to be associated with condenser pumps
h.CndMinPumpReqMinimum number of condenser pumps required from chiller

NOTE: in case no primary pumps or condenser pumps are connected and managed by iCM, user have to set:

  • MinPumpReq = 0
  • CndMinPumpReq = 0

8.5.3. Evaporator Shut Off Valve Configuration

(Used screen: MainMenu → ConfigMode → DeviceConfig)

  1. From "DeviceConfig" screen, you can configure availability of feedback signal for valve Open/Close status.
DeviceConfig4/12
Chiller
EvShutOffValve
-StatusSignalAvail
CndShutOffValve

8.5.4. Condenser Shut Off Valve Configuration

(Used screen: MainMenu → ConfigMode → DeviceConfig)

NOTE: This menu displays, but hardware of models EKDICMPA* does not support this function.

  1. From "DeviceConfig" screen, you can configure availability of feedback signal for valve Open/Close status.
DeviceConfig6/12
EvShutOffValve
-StatusSignalAvail
CndShutOffValve
-StatusSignalAvail

NOTE: with models EKDICMPA* "StatusSignal" must be set as "Not Avail".

8.5.5. Primary Pump Configuration

(Used screen: MainMenu → ConfigMode → DeviceConfig → PrimaryPump Config)

  1. From "DeviceConfig" screen, turn the click-dial to select "PrimaryPump" menu then press down on the click-dial to jump to "PrimaryPump" screen.
DeviceConfig7/12
PrimaryPump
CondenserPump
Sensor
ModbusCommSetting
  1. "PrimaryPump Config" screen is displayed. Here, you can configure attributes of primary pumps.
PrimaryPump Config1/25
StatusSignalAvail
#01
-Runhours10h
-PipingGroup1
#02
-Runhours10h
-PipingGroup1
#03
-Runhours10h
-PipingGroup1
#04
-Runhours10h
-PipingGroup1
#05
-Runhours10h
-PipingGroup1
#06
-Runhours10h
-PipingGroup1
#07
-Runhours10h
-PipingGroup1
#08
-Runhours10h
-PipingGroup1

Table 18 List of parameters which can be set from "PrimaryPump Config" screen

IDNameDefinition
a.StatusSignalAvailability of feedback signal for pump ON/OFF status
b.-RunhoursTotal run hours of pump as initial value
c.-PipingGroupPiping group the pump belongs to

8.5.6. Condenser Pump Configuration

(Used screen: MainMenu → ConfigMode → DeviceConfig → CondenserPump Config)

NOTE: This menu displays, but hardware of models EKDICMPA\* does not support this function.

  1. From "DeviceConfig" screen, turn the click-dial to select "CondenserPump" menu then press down on the click-dial to jump to "CondenserPump" screen.
DeviceConfig7/12
PrimaryPump
CondenserPump
Sensor
ModbusCommSetting
  1. "CondenserPump Config" screen is displayed. Here, you can configure attributes of condenser pumps.
CondenserPump Config1/25
StatusSignalAvail
#01
-Runhours10h
-PipingGroup1
#02
-Runhours10h
-PipingGroup1
#03
-Runhours10h
-PipingGroup1
#04
-Runhours10h
-PipingGroup1
#05
-Runhours10h
-PipingGroup1
#06
-Runhours10h
-PipingGroup1
#07
-Runhours10h
-PipingGroup1
#08
-Runhours10h
-PipingGroup1

NOTE: with models EKDICMPA* "StatusSignal" must be set as "Not Avail".

Table 19 List of parameters which can be set from "CondenserPump Config" screen

IDNameDefinition
a.StatusSignalAvailability of feedback signal for pump ON/OFF status
b.-RunhoursTotal run hours of pump as initial value
c.-PipingGroupPiping group the pump belongs to

8.5.7. Sensor Configuration

(Used screen: MainMenu → ConfigMode → DeviceConfig → SensorConfig)

  1. From "DeviceConfig" screen, turn the click-dial Ⓞ to select "Sensor" menu then press down on the click-dial Ⓥ to jump to "SensorConfig" screen.
Device Config9/12
PrimaryPump
CondenserPump
Sensor
ModbusCommSetting
  1. "SensorsConfig" menu is displayed. Here you can set attributes of sensors. Note: sensor type for differential pressure sensor is fixed to mA type.
SensorsConfig1/12
ChWtLvgTemp
-PortTypemA← a.
ChWtEntTemp
-PorttypemA← b.
CndWtLvgTemp
-PortTypemA← c.
CndWtEntTemp
-PorttypemA← d.
OATemp
-PortTypemA← e.
SensorConversionParam← 8.5.7.1 Setting sensor conversion parameter when using mA type
NTCSensorConversionParam← 8.5.7.2 Setting sensor conversion parameter when using NTC10K type
IDNameDefinition
a.-PortTypePortType for Chilled Water Leaving Temperature sensor (mA / NTC10K)
b.-PortTypePortType for Chilled Water Entering Temperature sensor (mA / NTC10K)
c.-PortTypePortType for Condensed Water Leaving Temperature sensor (mA / NTC10K)
d.-PortTypePortType for Condensed Water Entering Temperature sensor (mA / NTC10K)
e.-PortTypePortType for Outdoor Air Temperature sensor (mA/NTC10K)

Table 20 List of parameters which can be set from "SensorsConfig" screen

NOTE: Chilled Water temperature sensor are NTC10K sensors and are supplied with panel.

NOTE: Condenser Water Temperature sensors setting display, but hardware of models EKDICMPA* does not support this equipment

8.5.7.1. Setting sensor conversion parameter when using mA type

Image of sensor conversion when using mA type is shown on Figure 11.

DAIKIN EKDICMPAL - Setting sensor conversion parameter when using mA type - 1

line | X | Y | |------------|-------| | 0 | MaxOutput | | 4mA | MinOutput | | 20mA | MaxOutput |

Figure 11 Sensor value conversion of 4-20mA

  1. From "MainMenu > ConfigMode > SensorsConfig" screen, turn the click-dial Ⓞ to select "SensorConversionParam" menu then press down on the click-dial Ⓞ to jump to "SensorConvParam" screen.
SensorsConfig11/12
OATemp
-PorttypemA
SensorConversionParam
NTCSensorConversionPara m
  1. "SensorConvParam" screen is shown. Here, parameters for conversion of mA sensor input can be done
SensorConvParam1/21
ChWtLvgTemp
-MaxOutput75.0°Ca.
-MinOutput-25.0°Cb.
ChWtEntTemp
-MaxOutput75.0°Cc.
-MinOutput-25.0°Cd.
DiffPress
-MaxOutput683kPae.
-MinOutput0kPaf.
CndWtLvgTemp
-MaxOutput75.0°Cg.
-MinOutput-25.0°Ch.
CndWtEntTemp
-MaxOutput75.0°Ci.
-MinOutput-25.0°Cj.
CndDiffPress
-MaxOutput683kPak.
-MinOutput0kPal.
OATemp
-MaxOutput75.0°Cm.
-MinOutput-25.0°Cn.

Table 21 List of parameters which can be set from "SensorConvParam" screen

IDNameDefinition
a.-MaxOutputLinear output value of chilled water leaving temperature corresponding to 20mA input
b.-MinOutputLinear output value of chilled water leaving temperature corresponding to 4mA input
c.-MaxOutputLinear output value of chilled water entering temperature corresponding to 20mA input
d.-MinOutputLinear output value of chilled water entering temperature corresponding to 4mA input
e.-MaxOutputLinear output value of differential pressure corresponding to 20mA input
f.-MinOutputLinear output value of differential pressure corresponding to 4mA input
g.-MaxOutputLinear output value of condensed water leaving temperature corresponding to 20mA input
h.-MinOutputLinear output value of condensed water leaving temperature corresponding to 4mA input
i.-MaxOutputLinear output value of condensed water entering temperature corresponding to 20mA input
j.-MinOutputLinear output value of condensed water entering temperature corresponding to 4mA input
k.-MaxOutputLinear output value of condenser differential pressure corresponding to 20mA input
l.-MinOutputLinear output value of condenser differential pressure corresponding to 4mA input
m.-MaxOutputLinear output value of outdoor air temperature corresponding to 20mA input
n.-MinOutputLinear output value of outdoor air temperature corresponding to 4mA input

8.5.7.2. Setting sensor conversion parameter when using NTC10K type

Image of sensor conversion when using mA type is shown on Figure 11.

DAIKIN EKDICMPAL - Setting sensor conversion parameter when using NTC10K type - 1

line | X [Ω] | Y [°C] | |-------|--------| | 0 | MaxOutput | | 500 | MinOutput | | >500 | Determined by C1, C2, C3 |

Figure 12 Sensor value conversion of NTC10K
The non-linear part of conversion is modelled by Steinhart-Hart equation as described below. Parameters C1, C2, C3 are required to be set to determine the shape of the equation.

$$ T e m p e r a t u r e o u t p u t = \frac {1}{C _ {1} \times 1 0 ^ {- 4} + C _ {2} \times 1 0 ^ {- 4} \times \ln (x) + C _ {3} \times 1 0 ^ {- 8} \times \ln {(x)} ^ {3} - 2 7 3 . 1 5} $$

Equation 1 Steinhart-Hart Equation

  1. From "MainMenu > ConfigMode > SensorsConfig" screen, turn the click-dial to select "NTCSensorConversionParam" menu then press down on the click-dial to jump to "NTCSensorConvParam" screen.
SensorsConfig6/6
OATemp
-PorttypemA
SensorConversionParam
NTCSensorConversionPara m
  1. "SensorConvParam" screen is shown. Parameters for conversion of NTC sensor input can be done.
NTCSensorConvParam1/30
ChWtLvgTemp
-C1 E-411.3510
-C2 E-42.3296
-C3 E-89.3665
-MaxOutput75.0°C
-MinOutput-25.0°C
ChWtEntTemp
-C1 E-411.3510
-C2 E-42.3296
-C3 E-89.3665
-MaxOutput75.0°C
-MinOutput-25.0°C
CndWtLvgTemp
-C1 E-411.3510
-C2 E-42.3296
-C3 E-89.3665
-MaxOutput75.0°C
-MinOutput-25.0°C
CndWtEntTemp
-C1 E-411.3510
-C2 E-42.3296
-C3 E-89.3665
-MaxOutput75.0°C
-MinOutput-25.0°C
OATEmp
-C1 E-411.3510
-C2 E-42.3296
-C3 E-89.3665
-MaxOutput75.0°C
-MinOutput-25.0°C

Table 22 List of parameters which can be set from "NTCSensorConvParam" screen

IDNameDefinition
a.-C1 E-4Steinhart-Hart coefficient
b.-C2 E-4Steinhart-Hart coefficient (In(X) term)
c.-C3 E-8Steinhart-Hart coefficient (In(X) ^3 term )
d.-MaxOutputMaximum output value
e.-MinOutputMinimum output value

NOTE: The default values refer to NTCK10 sensor supplied with panel.

8.5.8. Modbus Communication Setting

(Used screen: MainMenu → ConfigMode → DeviceConfig → ModbusCommSetting)

  1. From "DeviceConfig" screen, turn the click-dial to select "ModbusCommSetting" menu then press down on the click-dial to jump to "ModbusCommSetting" screen.
DeviceConfig10/12
PrimaryPump
CondenserPump
Sensor
ModbusCommSetting
  1. "ModbusCommSetting" screen is displayed. Here, you can configure Modbus communication between iCM and chiller.
ModbusCommSetting1/4
BaudRate19200bps
ParityNone
StopBits1bit
ResponseTimeout1000ms

← a.
← b.
← C.
← d.

Table 23 List of parameters which can be set from "ModbusCommSetting" screen

IDNameDefinition
a.BaudRateBaud rate setting of RS485
b.ParityParity bit setting of RS485
c.StopBitsStop bit setting of RS485
d.ResponseTimeoutWait time for response on each command before time out

NOTE: Modbus communication parameter must match with Communication setting on chiller controller

8.5.9. Ai Threshold Setting

(Used screen: MainMenu → ConfigMode → DeviceConfig)

You can set threshold for judging open loop of Ai signal. The setting is common for all Ai signal. If open loop is detected, iCM will be in alarm status.

DeviceConfig12/12
Sensor
ModbusCommSetting
AiThreshold
-mA1.0mA ← a.

Table 24 List of parameters which can be set from "DeviceConfig" screen

IDNameDefinition
a.-mAThreshold for detecting open loop. If Input is less that this value, it is considered open loop.

NOTE: If users want to disable open loop detection for Ai signal, set "0.0mA" to this parameter.

9. Equipment Control Setting

Setting of various control parameters for each equipment can be done from this menu. Menu structure and items which can be set are described below.

○ Setting

- DeviceCtrlParam

□ DevcieCtrlParam

○ Chiller ....Set sequencing type, staging type, min/max operating chillers
etc
o PrimaryPump....Set PI parameters, setpoint etc for pump VFD control
○ BypassValve....Set PI parameters, setpoint etc for bypass valve control
○ CondenserPump....Set PI parameters, setpoint etc for pump VFD control
- CTBypassValve ....Set PI parameters, setpoint etc for bypass valve control

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "Setting" menu then press down on the click-dial to jump to "Setting" screen.
MainMenu2/4
Status
Setting
ConfigMode
Password
  1. On the "Setting" screen, turn the click-dial to select "DeviceCtrlParam" menu then press down on the click-dial to jump to "DeviceCtrlParam" screen.
Setting2/5
SystemCtrlParam
DeviceCtrlParam
CtrlModeSetting
SystemSetting
  1. DeviceCtrlParam screen is shown. From this screen, you can jump to control parameter setting for different equipment.
DeviceCtrlParam1/5
Chiller
PrimaryPump
BypassValve
CondenserPump
CTBypassValve

← 9.1 Chiller Control Setting
← 9.2 Primary Pump Control Setting
← 9.3 Bypass Valve Control Setting
← 9.4 Condenser Pump Control Setting
← 9.5 Cooling Tower Bypass Valve Control Setting

9.1. Chiller Control Setting

(Used screen: MainMenu > Setting > DeviceCtrlParam > ChillerCtrlParam)

  1. From "MainMenu > Setting > DeviceCtrlParam" screen, turn the click-dial 🔒 to select "Chiller" menu then press down on the click-dial 🔒 to jump to "ChillerCtrlParam" screen.
DeviceCtrlParam1/5
Chiller
PrimaryPump
BypassValve
CondenserPump
  1. "ChillerCtrlParam" screen is displayed. Here, various options for chiller control can be set.
Chiller Ctrl1/20
Sequencing
-TypeFixedOrder
-Order
-PonyChCtlDisable
-PonyChNo1
-StgDnWaitTime5min
Staging
-TypeTemp
-StgByTargetLoadDisable
-StgForRotationDisable
-WaitTime24h
-MinRunningCh1
-MaxRunningCh1
-Detail
StabilizeTime
-up-up5min
-dn-up10min
-dn-dn3min
-up-dn10min
TempDiff(SoftLoad)1.0°C

Table 25 shows the list of parameters which can be set from "ChillerCtrl" screen
Table 25 List of parameters which can be set from "Chiller Ctrl" screen

IDNameRangeDefinition
a.-TypeFixedOrder TimeOrderType of chiller sequencing (Fixed order / operation hours based)
b.-PonyChCtlEnable DisableEnable / disable pony chiller (Pony chiller is a chiller that operates first and stops when second chiller operates)Note: pony chiller control can only be used when enabling sequencing based on operation hours.
c.-PonyChNo1...8Chiller ID specified as pony chiller
d.-StgDnWaitTime1...30 minWait time before Pony chiller is staged down after second chiller is staged up.
e-TypeTmp Ld&TmpDecide staging type (temperature only / temperature and load)
f.-StgByTargetLoadEnable DisableEnable / disable optimal stage up method in addition to e.Type: temperature and load
g.-StgForRotationEnable DisableEnable / disable periodical staging for rotation
h.-WaitTime24...720 hHow long to wait before conducting staging for rotation
i.-MinRunningCh1...8Minimum number of operating chillers settingNote: please set this value smaller than j.
j.-MaxRunningCh1...8Maximum number of operating chillers settingNote: please set this value bigger than i.
k.-up-up1...30minStablizing (no stage up or stage down) period when staging up after a stage up
l.-dn-up1...30minStablizing (no stage up or stage down) period when staging up after a stage down
m.-dn-dn1...30minStablizing (no stage up or stage down) period when staging down after a stage down
n.-up-dn1...30minStablizing (no stage up or stage down) period when staging down after a stage up
o.TempDiff(SoftLoad)0.0...5.0 dKTemperature differential from temperature setpoint to judge end of initial startup (only related to status display)

9.1.1. Setting sequence order when using fixed order sequencing

When using fixed order staging method, manual order setting for each chiller needs to be done. 1. From "MainMenu > Setting > DeviceCtrlParam > Chiller Ctrl" screen, follow below steps to reach "Chiller FixedOrder" screen. Here, priority of sequence for manual sequencing can be set with 1 being highest priority.

NOTE: If multiple chillers are set as same priority, the sequence of the chillers will be decided according to operation hours among chillers. So chiller with lower operation hours and higher priority is selected for stage up, whereas chiller with lower priority and higher operation hours for stage down.

DAIKIN EKDICMPAL - Setting sequence order when using fixed order sequencing - 1

flowchart
graph TD
    A["Chiller Ctrl 3/20"] --> B["Sequencing"]
    B --> C["-Type FixedOrder"]
    C --> D["-Order ▶"]
    D --> E["-PonyChCtl Disable"]
    F["Chiller FixedOrder 1/8"] --> G["#01 1"]
    G --> H["#02 2"]
    H --> I["#03 3"]
    I --> J["#04 4"]
    J --> K["#05 5"]
    K --> L["#06 5"]
    L --> M["#07 5"]
    M --> N["#08 5"]

9.1.2. Setting detailed options for staging up / down

  1. From "MainMenu > Setting > DeviceCtrlParam > Chiller Ctrl" screen, follow below steps to reach "ChillerStg Detail" screen. Here, detailed settings for each method of staging up / down can be done.
ChillerCtrlParam14/20
-MinRunningCh1
-MaxRunningCh1
-Detail
StabilizeTime

DAIKIN EKDICMPAL - Setting detailed options for staging up / down - 1

ChillerStg Detail1/14
StgByLoadLimit
-StgUpWaitTime180s
-StgDnWaitTime10min
-Full/LowLoad Setting
StgByTemp
-StgUpWaitTime5min
-StgDnWaitTime5min
-StgUpDiff1.0 dK
-StgDnDelta3.5 D°C
-WaitTime(SuddenLoad)6min
-TempDiff(SuddenLoad)1.0 dK
StgByTargetLoad
-TargetLoad50%
-StgUpWaitTime180s

← a.

← b.

← 9.1.2.1 Setting full / low load for each chiller

← C.

← d.

← e.

← f.

← g.

← h.

← i.

← j.

Table 26 List of parameters which can be set from “Chiller StgUpToOptimal” screen

IDNameDefinition
a.-StgUpWaitTime1...600 secWait time BEFORE stage up based on full load is confirmed
b.-StgDnWaitTime1...600 secWait time BEFORE stage down based on low load is confirmed
c.-StgUpWaitTime1...30 minWait time BEFORE stage up based on chilled water temperature is confirmed
d.-StgDnWaitTime1...30 minWait time BEFORE stage down based on chilled Delta temperature is confirmed
e.-StgUpDiff0.0...5.0 dKTemperature differential for deciding threshold of stage up based on Supply water temperature
f.-StgDnDelta0.0...99.0 D°CDELTA Temperatura (EWT-LWT) for deciding setpoint below that staging down will be confirmed
g.-WaitTime(SuddenLoad)1...30 minBase Wait time BEFORE stage up based on chilled water temperature (sudden load)
h.-TempDiff(SuddenLoad)0.0...5.0 dKTemperature differential for deciding threshold of staging based on supply water temperature (sudden load)
i.-TargetLoad1...100%Target optimal load target for chiller when using staging up based on optimal chiller load
j.-StgUpWaitTime1...600 secWait time BEFORE stage up based on optimal chiller load is confirmed

9.1.2.1. Setting full / low load for each chiller

  1. From "MainMenu > Setting > DeviceCtrlParam > ChillerCtrlParam > ChillerStg Detail" screen, follow below steps to reach "Full/LowLoadSetting" screen. Here, full load and low load setting for each chiller can be done.
ChillerStg Detail4/14
Full/LowLoad Setting
StgByTemp
-StgUpWaitTime5min
-StgDnWaitTime5min
Full/LowLoadSetting1/24
#01
-FullLoad90%
-LowLoad10%
#02
-FullLoad90%
-LowLoad10%
#03
-FullLoad90%
LowLoad10%
#04
-FullLoad90%
-LowLoad10%
#05
-FullLoad90%
-LowLoad10%
#06
-FullLoad90%
-LowLoad10%
#07
-FullLoad90%
-LowLoad10%
#08
-FullLoad90%
-LowLoad10%

NOTE: Please DO NOT set LowLoad threshold higher than FullLoad threshold.

9.2. Primary Pump Control Setting

(Used screen: MainMenu > Setting > DeviceCtrlParam > PrimaryPump Ctrl)

  1. From "DeviceCtrlParam" screen, turn the click-dial to select "PrimaryPump" menu then press down on the click-dial to jump to "PrimaryPump Ctrl" screen.
DeviceCtrlParam2/5
Chiller
PrimaryPump
BypassValve
CondenserPump
  1. "PrimaryPump Ctrl" screen is displayed. Here, various options for primary pump control can be set.
PrimaryPump Ctrl1/14
PumpTypeCSD
Setpt13kPa
-ActiveValue13kPa
VFD_Control
-MaxCapacity100%
-MinCapacity30%
-PI_Param
Staging
-StgUpWaitTime60s
-StgDnWaitTime60s
-StgUpDiff20kPa
-StgDnDiff20kPa
-StgForRotation
OperationRange

← 9.2.2 Setting periodical pump staging for rotation
← 9.2.3 Setting minimum / maximum number of operating pumps for each piping group

Table 27 List of Parameters which can be Set from "PrimaryPump Ctrl" screen

IDNameDefinition
a.PumpTypeVDF CSDSet to VFD when VFD control of pumps is needed Set to CSD if constant flow is needed
b.Setpt1...999 kPaTarget setpoint for VFD / CSD pump control
c.-ActiveValueStatus display of actual setpoint (for future optimization control)
d.MaxCapacity0...100 %Maximum output for VFD control
e.MinCapacity0...100 %Minimum output for VFD control
f.-StgUpWaitTime1...600 secWait time BEFORE stage up is confirmed
g.-StgDnWaitTime1...600 secWait time BEFORE stage down is confirmed
h.-StgUpDiff0...100 kPaPressure differential for deciding threshold of CSD pump staging up
i.-StgDnDiff0...100 kPaPressure differential for deciding threshold of CSD pump staging down

9.2.1. Setting PI Parameters for Pump VFD Control

  1. From "MainMenu > Setting > DeviceCtrlParam > PrimaryPump Ctrl" screen, follow below steps to reach "PriPpDiffPress PI_Param" screen. Here, PI parameter for pump VFD control can be set.

DAIKIN EKDICMPAL - Setting PI Parameters for Pump VFD Control - 1

flowchart
graph TD
    A["PrimaryPump Ctrl 7/14"] --> B["VFD_Control"]
    B --> C["-MaxCapacity 100%"]
    C --> D["-MinCapacity 30%"]
    D --> E["-PI_Param"]
    E --> F["DiffPress"]
    F --> G["PriPump PI_Param 1/1"]
    G --> H["PropBand 40kPa"]
    H --> I["IntegralTime 20.0s"]

Table 28 List of parameters which can be set from "PrimaryPump Ctrl" screen

IDNameDefinition
a.PropBand0...999 kPaProportional band setting of PI control
b.IntegralTime0.0...999.0 secIntegral time setting of PI control

9.2.2. Setting periodical pump staging for rotation

  1. From "MainMenu > Setting > DeviceCtrlParam > PrimaryPump Ctrl" screen, follow below steps to reach "StgForRotation" screen. Here, periodical pump staging for rotation can be set.

DAIKIN EKDICMPAL - Setting periodical pump staging for rotation - 1

flowchart
graph TD
    A["PrimaryPump Ctrl 13/14"] --> B["-StgDnWaitTime 60s"]
    B --> C["-StgUpDiff 20kPa"]
    C --> D["-StgDnDiff 20kPa"]
    D --> E["-StgForRotation ▶"]
    F["StgForRotation 1/8"] --> G["PipingGroup01 Disable ← a."]
    F --> H["-WaitTime 24h ← b."]
    G --> I["PipingGroup02 Disable"]
    G --> J["-WaitTime 24h"]
    I --> K["PipingGroup03 Disable"]
    I --> L["-WaitTime 24h"]
    K --> M["PipingGroup04 Disable"]
    K --> N["-WaitTime 24h"]

Table 29 List of parameters which can be set from "StgForRotation" screen

IDNameDefinition
a.PipingGroup[X]Enable DisableEnable / disable periodical staging for rotation
b.-WaitTime24...720 hHow long to wait before conducting staging for rotation

9.2.3. Setting minimum / maximum number of operating pumps for each piping group

From "MainMenu > Setting > DeviceCtrlParam > PrimaryPump Ctrl" screen, follow below steps to reach "OperationRange" screen. Here, minimum / maximum number of operating pumps for each piping group can be set.

DAIKIN EKDICMPAL - Setting minimum / maximum number of operating pumps for each piping group - 1

flowchart
graph TD
    A["PrimaryPump Ctrl 14/14"] --> B["-StgUpDiff 20kPa"]
    B --> C["-StgDnDiff 20kPa"]
    C --> D["-StgForRotation ▶"]
    D --> E["OperationRange ▶"]
    E --> F["OperationRange 1/12"]
    F --> G["PipingGroup01"]
    G --> H["-MaxPumpOnNum 2"]
    H --> I["-MinPumpOnNum 1"]
    I --> J["PipingGroup02"]
    J --> K["-MaxPumpOnNum 2"]
-MinPumpOnNum2
PipingGroup03
-MaxPumpOnNum3
-MinPumpOnNum0
PipingGroup04
-MaxPumpOnNum4
-MinPumpOnNum4

Table 30 List of parameters which can be set from "OperationRange" screen

IDNameDefinition
a.MaxPumpOnNumMaximum number of operating pumps for each piping group setting
b.MinPumpOnNumMinimum number of operating pumps for each piping group setting

NOTE: Please set this value "a" bigger than "b".

9.3. Bypass Valve Control Setting

(Used screen: MainMenu > Setting > DeviceCtrlParam > BypasValve Ctrl)

  1. From "DeviceCtrlParam" screen, turn the click-dial to select "BypassValve" menu then press down on the click-dial to jump to "BypassValve Ctrl" screen.
DeviceCtrlParam3/5
Chiller
PrimaryPump
BypassValve
CondenserPump
  1. "Bypass Ctrl" screen is displayed. Here, various options for bypass valve control can be set.
BypassValve Ctrl1/4
MaxCapacity100%
MinCapacity0%
PI_Param
-DiffPress

← a.
← b.
← 9.3.1 Setting PI Parameters for Bypass Valve Control

Table 31 List of parameters which can be set from “BypassValve Ctrl” screen

IDNameDefinition
a.MaxCapacity0...100 %Maximum output value for PI control
b.MinCapacity0...100 %Minimum output value for PI control

9.3.1. Setting PI Parameters for Bypass Valve Control

  1. From "MainMenu > Setting > DeviceCtrlParam > BypassValve Ctrl" screen, follow below steps to reach "BypValveDiffPress PI-Pa" screen. Here, PI parameter for bypass valve control can be set.
BypassValve Ctrl4/4
MaxCapacity100%
MinCapacity0%
PI_Param
DiffPress

DAIKIN EKDICMPAL - Setting PI Parameters for Bypass Valve Control - 1

BypValveDiffPress PI_Pa1/5
DiffPress
-Setpt13kPa
-ActiveValue13kPa
-PropBand50kPa
-IntegralTime60.0s

← a.

← b.

← C.

← d

Table 32 List of parameters which can be set from "BypValveDiffPress PI_Pa" screen

IDNameDefinition
a.-Setpt1...999 kPaTarget setpoint for bypass valve control
b.-ActiveValueStatus display of actual setpoint (for future optimization control )
c.-PropBand0...999 kPaProportional band setting of PI control
d-IntegralTime0.0...999.0 secIntegral time setting of PI control

9.4. Condenser Pump Control Setting

(Used screen: MainMenu > Setting > DeviceCtrlParam > CondenserPump Ctrl)

  1. From "DeviceCtrlParam" screen, turn the click-dial ⏻ to select "CondenserPump" menu then press down on the click-dial ⏻ to jump to "CondenserPump Ctrl" screen.
DeviceCtrlParam4/5
PrimaryPump
BypassValve
CondenserPump
CTBypassValve
  1. "CondenserPump Ctrl" screen is displayed. Here, various options for condenser pump control can be set.
CondenserPump Ctrl1/4
CndPipingGroup1
CndPipingGroup2
CndPipingGroup3
CndPipingGroup4
  1. For each "CondenserPump Ctrl", press down on the click-dial Ⓞ to jump to "CndPump Ctrl" screen, which is shown below. (Example shown is CndPipingGroup1)
Gr1 CndPump Ctrl1/21
PumpTypeVFD
CtrlTypeDiffTemp
SetptDiffTemp5.0°C
-ActiveValue5.0°C
SetptDiffPress13kPa
-ActiveValue13kPa
VFD Control
-MaxCapacity100%
-MinCapacity0%
-DT_PI_Param
-DP_PI_Param
Staging
-StgUpWaitTime60s
-StgDnWatTme60s
-StgUpDiffTemp1.0°C
-StgDnDiffTemp1.0°C
-StgUpDiffPress5kPa
-StgDnDiffPress5kPa
-StgForRotationEnable
-WaitTime24h
-OperationRange

← a.

← b.

← C.

← d.

← e.

← f.

← g.

← h.

← 9.4.1 Setting DT_PI Parameters for Pump VFD Control

← 9.4.2 Setting DP_PI Parameters for Pump VFD Control

← i.

← i.

← k.

← |.

← m.

← n.

← 0.

← p.

← 9.4.3 Setting minimum / maximum number of operating pumps for each piping group

Table 33 List of parameters which can be set from "CndPump Ctrl" screen

IDNameDefinition
a.PumpTypeVDFCSDSet to VFD when VFD control of pumps is neededSet to CSD if constant flow is needed
b.CtrlType1...999 kPaSelect from temperature differential or pressure differential
c.SetptDiffTemp0.0...99.0D°CTarget setpoint of temperature differential for VFD / CSD pump control
d.-ActiveValueStatus display of actual setpoint (for future optimization control )
e.SetptDiffPress0...999 kPaTarget setpoint of pressure differential for VFD / CSD pump control
f.-ActiveValueStatus display of actual setpoint (for future optimization control )
g.-MaxCapacity0...100 %Maximum output for VFD control
h.-MinCapacity0...100 %Minimum output for VFD control
i.-StgUpWaitTime1...600 secWait time BEFORE stage up is confirmed
j.-StgDnWatTme1...600 secWait time BEFORE stage down is confirmed
k.-StgUpDiffTemp0.0...99.0 dKTemperature differential for deciding threshold of CSD pump staging up
l.-StgDnDiffTemp0.0...99.0 dKTemperature differential for deciding threshold of CSD pump staging down
m.-StgUpDiffPress0...100 kPaPressure differential for deciding threshold of CSD pump staging up
n.-StgDnDiffPress0...100kPaPressure differential for deciding threshold of CSD pump staging down
o.-StgForRotationEnable/disable staging for rotation
p.-WaitTime24...720 hWait time BEFORE staging is confirmed

9.4.1. Setting DT\_PI Parameters for Pump VFD Control

  1. From "MainMenu > Setting > DeviceCtrlParam > CondenserPump Ctrl" screen, follow below steps to reach "Gr# CndPpDT_PI_Param" screen. Here, PI parameter for pump VFD control can be set. (Gr1 is shown as an example.)
Gr1 CndPump Ctrl10/21
VFD_Control
-MaxCapacity100%
-MinCapacity0%
DT_PI_Param

DAIKIN EKDICMPAL - Setting DT\_PI Parameters for Pump VFD Control - 1

Gr1 CndPpDT PI Param1/2
PropBand10.0°C ← a.
IntegralTime20.0s ← b.

Table 34 List of parameters which can be set from "PrimaryPump Ctrl" screen

IDNameDefinition
a.PropBandProportional band setting of PI control
b.IntegralTimeIntegral time setting of PI control

9.4.2. Setting DP\_PI Parameters for Pump VFD Control

  1. From "MainMenu > Setting > DeviceCtrlParam > CondenserPump Ctrl" screen, follow below steps to reach "Gr# CndPpDP_PI_Param" screen. Here, PI parameter for pump VFD control can be set. (Gr1 is shown as an example.)
Gr1 CndPump Ctrl11/21
-MaxCapacity100%
-MinCapacity0%
-DT_PI_Param
DP_PI_Param

DAIKIN EKDICMPAL - Setting DP\_PI Parameters for Pump VFD Control - 1

Gr1 CndPpDP PI Param1/2
PropBand10kPa
IntegralTime20.0s

Table 35 List of parameters which can be set from "PrimaryPump Ctrl" screen

IDNameDefinition
a.PropBandProportional band setting of PI control
b.IntegralTimeIntegral time setting of PI control

9.4.3. Setting minimum / maximum number of operating pumps for each piping group

  1. From "MainMenu > Setting > DeviceCtrlParam > CondenserPump Ctrl" screen, follow below steps to reach "OperationRange" screen. Here, minimum / maximum number of operating pumps for each piping group can be set.
PrimaryPump Ctrl21/21
-StgDnDffPress5kPa
-StgForRotationEnable
-WaitTime24h
-OperationRange
Gr1 OperationRange1/2
MaxPumpOnNum2
MinPumpOnNum1

Table 36 List of parameters which can be set from "OperationRange" screen

IDNameDefinition
a.MaxPumpOnNumMinimum number of operating pumps for each piping group setting
b.MinPumpOnNumMaximum number of operating pumps for each piping group setting

NOTE: Please DO NOT set value "b" bigger than "a".

9.5. Cooling Tower Bypass Valve Control Setting

(Used screen: MainMenu > Setting > DeviceCtrlParam > CTBypasValve Ctrl)

  1. From "DeviceCtrlParam" screen, turn the click-dial ⏻ to select "CTBypassValve" menu then press down on the click-dial ⏻ to jump to "CTBypassValve Ctrl" screen.
DeviceCtrlParam5/5
PrimaryPump
BypassValve
CondenserPump
CTBypassValve
  1. "CTBypass Ctrl" screen is displayed. Here, various options for bypass valve control can be set.
CTBypassValve Ctrl1/4
CndPipingGroup1
CndPipingGroup2
CndPipingGroup3
CndPipingGroup4
  1. Turn the click-dial Ⓞ to select "Gr# CTBypassValve Ctrl" menu for each condenser piping group number, then then press down on the click-dial to 'hmp to the' screen. (Gr1 is shown as an example)
Gr1 CTBypassValve Ctrl1/4
MaxCapacity100%
MinCapacity0%
PI Param
-CndWtEntTemp

Table 37 List of parameters which can be set from "CTBypassValve Ctrl" screen

IDNameDefinition
a.MaxCapacityMaximum output value for PI control
b.MinCapacityMinimum output value for PI control

9.5.1. Setting PI Parameters for Cooling Tower Bypass Valve Control

  1. From "MainMenu > Setting > DeviceCtrlParam > CTBypassValve Ctrl>Gr# CTBypassValve Ctrl" screen, follow below steps to reach "CTBypValveDiffPress PI-Pa" screen. Here, PI parameter for bypass valve control can be set.
Gr1 CTBypassValve Ctrl4/4
MaxCapacity100%
MinCapacity0%
PI Param
CndWtEntTemp
Gr1 CTBypValve_PI_Param1/5
CndWtEntTemp
-Setpt13kPa← a.
-ActiveValue13kPa← b.
-PropBand50kPa← c.
-IntegralTime60.0s← d.

Table 38 List of parameters which can be set from "CTBypValveDiffPress PI_Pa" screen

IDNameDefinition
a.-SetptTarget setpoint for bypass valve control
b.-ActiveValueStatus display of actual setpoint (for future optimization control )
c.-PropBandProportional band setting of PI control
d-IntegralTimeIntegral time setting of PI control

9.6. System Control Setting

Setting of various control parameters for system control can be done from this menu.

Menu structure and items which can be set are described below.

○ Setting

- SystemCtrlParam

□ SystemCtrlParam

PowerFailureRecov....Set parameters for power failure recovery control
- DblTempSetpt....Set parameters for double setpoint control
○ ProtectSystem ....Set pump frequency when recycling, pump frequency for

force pump on, chiller on delay time, pump off delay time etc.

- PullDownRateCtrl...... Set parameters for pull down rate control

- SetptReset....Set parameters for setpoint reset

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial Ⓞ to select "Setting" menu then press down on the click-dial Ⓞ to jump to "Setting" screen.
MainMenu2/4
Status
Setting
ConfigMode
Password
  1. On the "Setting" screen, turn the click-dial ⏻ to select "SystemCtrlParam" menu then press down on the click-dial ⏻ to jump to "SystemCtrlParam" screen.
Setting1/5
SystemCtrlParam
DeviceCtrlParam
CtrlModeSetting
SystemSetting
  1. SystemCtrlParam screen is shown. From this screen, you can jump to control parameter setting for different system control.

SystemCtrlParam 1/6 PowerFailureRecov ▶ ← 9.6.1 Power Failure Recovery ProtectSystem ▶ ← 9.6.2 Protect System DblTempSetpt ▶ ← 9.6.3 Double Temperature Setpoint PullDownRatectrl ▶ ← 9.6.4 Pull Down Rate Control SetptReset ▶ ← 9.6.5 Setpoint reset

9.6.1. Power Failure Recovery

(Used screen: MainMenu > Setting > SystemCtrlParam > PowerFailureRecov)

  1. From "SystemCtrlParam" screen, turn the click-dial ⏻ to select "PowerFailureRecov" menu then press down on the click-dial ⏻ to jump to "PowerFailureRecov" screen.
SystemCtrlParam1/6
PowerFailureRecov
ProtectSystem
DblTempSetpt
PullDownRateCtrl
  1. "PowerFailureRecov" screen is shown. Here, parameters for power failure recovery control can be set.

PowerFailureRecov 1/2 DetectionTime 5min ← a. RecovOption Stop ← b.

Table 39 List of parameters which can be set from "PowerFailureRecov" screen

IDNameDefinition
a.DetectionTimePower off duration to judge power failure (if power off time is less than this setting, it is considered power failure)
b.RecovOptionBehaviour of iCM when recovering from power failure. (Always recover from stop / restore sysmte ON/OFF status before power off)

9.6.2. Protect System

(Used screen: MainMenu > Setting > SystemCtrlParam > ProtectSystem)

  1. From "SystemCtrlParam" screen, turn the click-dial to select "ProtectSystem" menu then press down on the click-dial to jump to "ProtectSystem" screen.
SystemCtrlParam2/6
PowerFailureRecov
ProtectSystem
DblTempSetpt
PullDownRateCtrl
  1. "ProtectSystem" screen is shown. Here, parameters for system protection control can be set.
ProtectSystem1/18
KeepMinEvaFlwCap20%
ForcePriPpModeCap40%
ChillerOnDelayTime60s
ChillerOffDelayTime180s
PumpOnDelayTime60s
PumpOffDelayTime60s
ValveOpenDelayTime180s
RecycleDelayTime360s
KeepMinCndFlowCap20%
ForceCndPpModeCap40%
CndPumpOnDelayTime60s
CndPumpOffDelayTime60s
CndValveOpenDelayTime60s
CndValveCloseDelayTime180s
CTValveOpenDelayTime60s
CTValveCloseDelayTime180s
CTFanOnDelayTime60s
CTFanOffDelayTime180s

Table 40 List of parameters which can be set from "ProtectSystem" screen

IDNameDefinition
a.KeepMinEvaFlwCapMinimum VFD frequency for primary pump control to ensure minimum flow
b.ForcePriPpModeCapVFD frequency when using force pump on control
c.ChillerOnDelayTimeDelay time after chiller ON Status to operate auxiliaries
d.ChillerOffDelayTimeDelay time after chiller OFF Status to stop auxiliaries
e.PumpOnDelayTimeDelay time after pump ON Status to operate auxiliaries
f.PumpOffDelayTimeDelay time after pump OFF Status to stop auxiliaries
g.ValveOpenDelayTimeDelay time after valve OPEN Status to operate chillers
h.RecycleDelayTimeDelay time to operate auxiliaries after last chiller stops
i.KeepMinCndFlowCapMinimum condenser flow capacity
j.ForceCndPpModeCapCapacity when forced condenser pump mode is on
k.CndPumpOnDelayTimeDelay time to operate auxiliaries after condenser pump runs
l.CndPumpOffDelayTimeDelay time to operate auxiliaries after condenser pump stops
m.CndValveOpenDelayTimeDelay time to operate auxiliaries after condenser valve operates
n.CndValveCloseDelayTimeDelay time to operate auxiliaries after condenser valve stops
o.CTValveOpenDelayTimeDelay time to operate auxiliaries after condenser pump operates
p.CTValveCloseDelayTimeDelay time to operate auxiliaries after condenser pump stops
q.CTFanOnDelayTimeDelay time to operate auxiliaries after cooling tower fan operates
r.CTFanOffDelayTimeDelay time to operate auxiliaries after cooling tower fan stops

9.6.3. Double Temperature Setpoint

(Used screen: MainMenu > Setting > SystemCtrlParam > DblTempSetpt)

NOTE: Source of input setting for chilled water temperature setpoint needs to be “Control” for double temperature setpoint to work correctly. This is described in detail on Table 41.

Table 41 Setting vs. chilled water temperature output of double setpoint control

SettingChilled water temperature output
Source of inputEnable / DisableExternal Signal
ControlEnableONDouble Setpoint setting
OFFChilled water temperature setpoint from HMI
DisableDon't care
OtherDon't' careDon't careValue from configured source of setting
  1. From "SystemCtrlParam" screen, turn the click-dial to select "DblTempSetpt" menu then press down on the click-dial to jump to "DblTempSetpt" screen.
SystemCtrlParam3/6
PowerFailureRecov
ProtectSystem
DblTempSetpt
PullDownRateCtrl
  1. "DblTempSetpt" screen is shown. Here, parameters for double setpoint control can be set.
DblTempSetpt1/2
DblSptEnableDisable
DblTempSetpt5.0°C

Table 42 List of parameters which can be set from "ProtectSystem" screen

IDNameDefinition
a.DblSptEnableEnable / disable double setpoint control. When enabled, actual setpoint will become value specified by double setpoint when receiving I/O signal.Note: when double setpoint is enabled but not external signal from I/O, chilled water temperature set from HMI will be used.
b.DblTempSetptSet value of double setpoint

9.6.4. Pull Down Rate Control

(Used screen: MainMenu > Setting > SystemCtrlParam > PullDownRateCtrl)

Image of pull down rate control is shown on Figure 13

Stage up is inhibited when pull down rate exceeds Threshold 1 setting. Staging is allowed again when pull down rate becomes lower than Threshold 2 setting. Pull down rate is calculated every so often specified by measure band setting.

DAIKIN EKDICMPAL - Pull Down Rate Control - 1

line | Measure Band | Pulldown rate | | ------------ | ------------- | | lower | lower | | lower | higher | | upper | lower | | lower | higher | | upper | lower |

Figure 13 Pull Down Rate Control

  1. From "SystemCtrlParam" screen, turn the click-dial ☐ to select "PullDownRateCtrl" menu then press down on the click-dial ☐ to jump to "PullDownRateCtrl" screen.
SystemCtrlParam4/6
PowerFailureRecov
ProtectSystem
DblTempSetpt
PullDownRateCtrl
  1. "PullDownRateCtrl" screen is shown. Here, parameters for pull down rate control can be set.
PullDownRateCtrl1/5
PIDnRateEnableDisable ← a.
TargetWtTempEWT ← b.
MeasureBand60s ← c.
PIDnRateUpLimit0.5° C / min
PIDnRateOffset0.1° C / min

Table 43 List of parameters which can be set from "PullDownRateCtrl" screen

IDNameDefinition
a.PIDnRateEnableEnable / Disable pull down rate control
b.TargetWtTempUse entering water temperature or leaving water temperature to calculated pull down rate
c.MeasureBandWindow time duration to calculate pull down rate
d.PIDnRateUpLimitUpper limit of pull down rate before inhibiting stage up
e.PIDnRateOffsetDifferential value subtracted from upper limit when judging unlock of stage up

9.6.5. Setpoint reset

(Used screen: MainMenu > Setting > SystemCtrlParam > Setpt Reset)

  1. From "SystemCtrlParam" screen, turn the click-dial to select "Setpt Reset" menu then press down on the click-dial to jump to "PullDownRateCtrl" screen.
SystemCtrlParam5/6
DbITempSetpt
PullDownRatectrl
SetptReset
  1. "Setpt Reset" screen is shown. Here, parameters for setpoint reset can be set.
SetptReset1/5
ResetEnableEnable ← a.
TargetTempOAT ← b.
SetptDiff5.0°C ← c.
MaxReset15.0°C ← d.
NoReset25.0°C←e.

Table 44 List of parameters which can be set from "Setpt Reset" screen

IDNameDefinition
a.ResetEnableEnable / Disable setpoint reset
b.Target TempUse outdoor air temperature or cooled water return temperature to calculate setpoint reset
c.SetptDiffTemprature differential when executing setpoint reset
d.MaxResetMaximum temperature to enable setpoint reset
e.NoResetTempreature setpoint to disable setpoint reset

9.7. Source of Input Setting

It is possible to specify, for each setpoint / command, which input to be effective. Setting of which source of input to be active for each item can be done from this menu.

Menu structure and items which can be set are described below.

○ Setting

- CtrlModeSetting

CtrlModeSetting

  • Run/Stop....Set source of input for Run/Stop command
    TempSetpt....Set source of input for chilled water temperature
  • ForcePriPumpMode ....Set source of input for force primary pump on command
    ○ ForceCondPumpMode......Set source of input for force condenser pump on command
    o PriPpDiffPressSetpt ....Set source of input for primary pump VFD differential pressure setpoint
    Gr# CndPpCtrlSetpt....Set source of input for condenser pump piping group control
    setpoint for each group (1 to 4)
    ○ BpVlvDiffPressSetpt......Set source of input for bypass valve differential pressure
    Setpoint
    Gr# CndBpVlvTempSetpt....Set source of input for condenser bypass valve temperature
    setpoint for condenser piping group (1 to 4)

Steps for selecting source of input are described below

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial Ⓞ to select "Setting" menu then press down on the click-dial Ⓞ to jump to "Setting" screen.
MainMenu2/4
Status
Setting
ConfigMode
Password
  1. On the "Setting" screen, turn the click-dial to select "CtrlModeSetting" then press down on the click-dial to jump to "CtrlModeSetting" screen.
Setting3/5
SystemCtrlParam
DeviceCtrlParam
CtrlModeSetting
SystemSetting
  1. On the "CtrlModeSetting" screen, source of input for various commands can be changed. Please refer to Table 44 for available source of input for each command.
CtrlModeSetting1/12
Run/StopManual
TempSetptManual
ForcePriPumpModeManual
ForceCondPumpModeManual
PriPpDiffPressSetptManual
Gr1CndPpCtrlSetptManual
Gr2CndPpCtrlSetptManual
Gr3CndPpCtrlSetptManual
Gr4CndPpCtrlSetptManual
BpVlvDiffPressSetptManual
Gr1CndBpVlvTempSetptManual
Gr2CndBpVlvTempSetptManual
Gr3CndBpVlvTempSetptManual
Gr4CndBpVlvTempSetptManual

Name of command

Manual: Manual Input from HMI is valid
I/O: Input from I/O is valid
Control: Input from internal control such as double setpoint is valid,
BACnet: Input from BACnet is valid
AutoCloud: Input from cloud is valid (for future use)

Table 45 illustrates available source of input for each command.
Table 45 List of Available Source of Input for Each Command

NameDescriponManualAuto
I/OControlBACnetAutoCloud
Run/StopRun/Stop commandYYNYY
TempSetptChilled water temperature setpointYYYYY
ForcePriPumpModeForce primary pump on commandYYNYY
ForceCondPumpModeForce condenser pump on commandYYNYY
PriPpDiPressSetptDierenal pressure setpoint for primary pump VFD controlYNNNY
CndPpCtrlSetptCondenser pump control setpointYNNNY
BpVlvDiPressSetptDierenal pressure setpoint for bypass valve controlYNNNY
CndBpVlvTempSetptTemperature setpoint for condenser side bypass valveYNNNY

CAUTION: Please DO NOT set control mode to source of input shown as "N": NOT available" (e.g. Setting Control as source of input for Run/Stop). Resulting output and iCM behaviour is not guaranteed.

10. Trial Run

Sending command manually to various equipment in order to check connection can be done from this menu.

Note: the system needs to be in "Config Mode" when using trial run menu.

Menu structure and items which can be set are described below.

○ ConfigMode ■ Trialrun

TrialRun

○ Chiller ...... Send temperature setpoint manually to chiller
- I/O....Check connection of each ext. module, check input of each
input I/O port, and send manual signal from each output I/O port
○ BACnet_Module......Check connection status of BACnet Module.

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "ConfigMode" menu then press down on the click-dial to jump to "ConfigMode" screen.
MainMenu3/4
Status
Setting
ConfigMode
Password
  1. On the "ConfigMode" screen, turn the click-dial to select "TrialRun" menu then press down on the click-dial to jump to "TrialRun" screen.
ConfigMode5/8
TrialRun
Backup/Restore
DataManagement
Reset-
  1. "TrialRun" screen is shown. From this screen, you can jump to trial run menu of different equipment.
TrialRun1/4
Chiller← 10.1 Chiller Trial Run
I/O← 10.2 I/O Trial Run
BACnet ModuleNoError← 10.3 BACnet Module Trial

NOTE: Trial Run operation works when the system is in "Config Mode"

10.1. Chiller Trial Run

(Used screen: MainMenu > ConfigMode > TrialRun > Chiller TrialRun)

  1. "Chiller TrialRun" screen is shown. From this screen, you can send temperature setpoint command to individual chiller to ensure connection is establish.
Chiller TrialRun1/16
#01
-TempSetptcmd 0.0^ C
#02
-TempSetptcmd 0.0^ C
#03
-TempSetptcmd 0.0^ C
#04
-TempSetptcmd 0.0^ C
#05
-TempSetptcmd 0.0^ C
#06
-TempSetptcmd 0.0^ C
#07
-TempSetptcmd 0.0^ C
#08
-TempSetptcmd 0.0^ C

10.2. I/O Trial Run

(Used screen: MainMenu > ConfigMode > TrialRun > I/O TrialRun)

  1. From "MainMenu > ConfigMode > TrialRun" screen, turn the click-dial Ⓞ to select "I/O" menu then press down on the click-dial Ⓞ to jump to "I/O TrialRun" screen.
I/O TrialRun1/36
BaseController
-CheckPorts
Extl/O#1NoError
-CheckPorts
Extl/O#2NoError
-CheckPorts
Extl/O#3NoError
-CheckPorts
Extl/O#4NoError
-CheckPorts
Extl/O#5NoError
-CheckPorts
Extl/O#6NoError
-CheckPorts

← AChecking individual ports of base controller
← a.
← B Checking individual ports of extension I/O #1
← b.
← C Checking individual ports of extension I/O #2
← C.
← D Checking individual ports of extension I/O #3
← d.
← Checking individual ports of extension I/O #4
← e.
← F Checking individual ports of extension I/O #5
← f.
← G Checking individual ports of extension I/O #6

ExtI/O#9NoError
-CheckPorts
ExtI/O#10NoError
-CheckPorts
ExtI/O#11NoError
-CheckPorts
ExtI/O#12NoError
-CheckPorts
ExtI/O#13NoError
-CheckPorts
ExtI/O#14NoError
-CheckPorts
ExtI/O#15NoError
-CheckPorts
ExtI/O#16NoError
-CheckPorts

Table 46 List of parameters which can be set from "I/O TrialRun" screen

IDNameDefinition
a.Extl/O#1Error is displayed if Extl/O#1 is registered but no connection found
b.Extl/O#2Error is displayed if Extl/O#2 is registered but no connection found
c.Extl/O#3Error is displayed if Extl/O#3 is registered but no connection found
d.Extl/O#4Error is displayed if Extl/O#4 is registered but no connection found
e.Extl/O#5Error is displayed if Extl/O#5 is registered but no connection found
f.Extl/O#6Error is displayed if Extl/O#6 is registered but no connection found
i.Extl/O#9Error is displayed if Extl/O#9 is registered but no connection found
j.Extl/O#10Error is displayed if Extl/O#10 is registered but no connection found
k.Extl/O#11Error is displayed if Extl/O#11 is registered but no connection found
l.Extl/O#12Error is displayed if Extl/O#12 is registered but no connection found
m.Extl/O#13Error is displayed if Extl/O#13 is registered but no connection found
n.Extl/O#14Error is displayed if Extl/O#14 is registered but no connection found
o.Extl/O#15Error is displayed if Extl/O#15 is registered but no connection found
p.Extl/O#16Error is displayed if Extl/O#16 is registered but no connection found

A. Checking individual ports of base controller

User screen: MainMenu > ConfigMode > TrialRun > I/O TrialRun > BaseController CheckPort

  1. From "BaseController Ports" screen you can perform point check against I/Os.
BaseController Ports1/12
X1Run/StopOFF ← a.
X2TempSetpt7.0°C
X3EmgStopON
X4OpenRateCmd0%
X5DblSptOFF
X6ChWtLvgTemp-99.0°C
-AlarmDeviceError
X7ChWtEntTemp-99.0°C
-AlarmDeviceError
X8DiffPress0kPa
-AlarmDeviceError
DO1SysRun/StopOFF
DO2SysAlarmOFF
DI1ForcePriPumpModeON
DI2ForceCndPumpModeOFF

Table 47 List of parameters which can be set from "BaseController Ports" screen

IDNameDefinition
a.Run/StopDisplay status of DI signal
b.TempSetptDisplay status of AI signal
c.EmgStopDisplay status of DI signal
d.OpenRateCmdManually send AO signal
e.DblSptDisplay status of DI signal
f.ChWtLvgTempDisplay status of AI signal
g.-AlarmDisplay alarm status
h.ChWtEntTempDisplay status of AI signal
i.-AlarmDisplay alarm status
j.DiffPressDisplay status of AI signal
k.-AlarmDisplay alarm status
l.SysRun/StopManually send DO signal
m.SysAlarmManually send DO signal
n.ForcePriPumpModeDisplay status of DI signal
o.ForceCndPumpModeDisplay status of DI signal

B. Checking individual ports of extension I/O #1

User screen: MainMenu > ConfigMode > TrialRun > I/O TrialRun > ExtI/O#01 CheckPort

  1. From "ExtI/O#01 Ports" screen, you can perform point check against I/Os.
ExtI/O#01 Ports1/8
X1PriPp1CapCmd0%
X2PriPp1Run/StopOFF
X3PriPp1AlarmOFF
X4PriPp1CapCmd0%
X5PriPp1Run/StopOFF
X6PriPp1AlarmOFF
DO1PriPp1ONOFFOFF← g.
DO2PriPp2ONOFFOFF← h

Table 48 List of parameters which can be set from "Extl/O#01 Ports" screen

IDNameDefinition
a.PriPp1CapCmdManually send AO signal
b.PriPp1Run/StopDisplay status of DI signal
c.PriPp1AlarmDisplay status of DI signal
d.PriPp1CapCmdManually send AO signal
e.PriPp1Run/StopDisplay status of DI signal
f.PriPp1AlarmDisplay status of DI signal
g.PriPp1ONOFFManually send DO signal
h.PriPp2ONOFFManually send DO signal

C. Checking individual ports of extension I/O #2
D. Checking individual ports of extension I/O #3
E. Checking individual ports of extension I/O #4

Please refer for these extension modules to B Checking individual ports of extension I/O #1

F. Checking individual ports of extension I/O #5

User screen: MainMenu > ConfigMode > TrialRun > I/O TrialRun > ExtI/O#05 CheckPort

  1. From "ExtI/O#05 Ports" screen, you can perform point check against I/Os.
ExtI/O#05 Ports1/12
X1EvSO_Vv1O/COFF
X2EvSO_Vv2O/COFF
X3EvSO_Vv3O/COFF
X4EvSO_Vv4O/COFF
X5EvSO_Vv1AlarmOFF
X6EvSO_Vv2AlarmOFF
X7EvSO_Vv3AlarmOFF
X8EvSO_Vv4AlarmOFF
DO1EvSO_Vv1ONOFFOFF
DO2EvSO_Vv2ONOFFOFF
DO3EvSO_Vv3ONOFFOFF
DO4EvSO_Vv4ONOFFOFF

Table 49 List of parameters which can be set from "Extl/O#05 Ports" screen

IDNameDefinition
a.EvSO_Vv1O/CDisplay status of DI signal
b.EvSO_Vv2O/CDisplay status of DI signal
c.EvSO_Vv3O/CDisplay status of DI signal
d.EvSO_Vv4O/CDisplay status of DI signal
e.EvSO_Vv1AlarmDisplay status of DI signal
f.EvSO_Vv2AlarmDisplay status of DI signal
g.EvSO_Vv3AlarmDisplay status of DI signal
h.EvSO_Vv4AlarmDisplay status of DI signal
i.EvSO_Vv1ONOFFManually send DO signal
j.EvSO_Vv2ONOFFManually send DO signal
k.EvSO_Vv3ONOFFManually send DO signal
l.EvSO_Vv4ONOFFManually send DO signal

G. Checking individual ports of extension I/O #6

Please refer for this extension module to F Checking individual ports of extension I/O #5

H. Checking individual ports of extension I/O #9

User screen: MainMenu > ConfigMode > TrialRun > I/O TrialRun > ExtI/O#09 CheckPort

  1. From "ExtI/O#09 Ports" screen, you can perform point check against I/Os.
Extl/O#09 Ports1/7
X1CndWtEntTemp125.0°C
-AlarmOFF
X2CndWtEntTemp225.0°C
-AlarmOFF
X3CndWtLvgTemp130.0°C
-AlarmOFF
X4CndWtLvgTemp230.0°C
-AlarmOFF
X5CndDiffPress1332kPa
-AlarmOFF
X6CndDiffPress2332kPa
-AlarmOFF
X7OutdoorTemp28.0°C
-AlarmOFF

Table 50 List of parameters which can be set from "Extl/O#09 Ports" screen

IDNameDefinition
a.CndWtEntTemp1Manually send AO signal
b.-AlarmDisplay alarm status
c.CndWtEntTemp2Manually send AO signal
d.-AlarmDisplay alarm status
e.CndWtLvgTemp1Manually send AO signal
f.-AlarmDisplay alarm status
g.CndWtLvgTemp2Manually send AO signal
h.-AlarmDisplay alarm status
i.CndDiffPress1Manually send AO signal
j.-AlarmDisplay alarm status
k.CndDiffPress2Manually send AO signal
l.-AlarmDisplay alarm status
m.OutdoorTempDisplay status of AI signal
n.-AlarmDisplay alarm status

I. Checking individual ports of extension I/O #10

Please refer for this extension module to H Checking individual ports of extension I/O #9

J. Checking individual ports of extension I/O #11

User screen: MainMenu > ConfigMode > TrialRun > I/O TrialRun > ExtI/O#011 CheckPort

  1. From "ExtI/O#11 Ports" screen, you can perform point check against I/Os.
ExtI/O#11 Ports1/10
X1CndPp1CapCmd0%
X2CndPp2CapCmd0%
X3BV1OpenRateCmd0%
X4BV2OpenRateCmd0%
X5CndPp1Run/StopOFF
X6CndPp2Run/StopOFF
X7CndPp1AlarmOFF
X8CndPp2AlarmOFF
DO1CndPp1ONOFFOFF
DO2CndPp2ONOFFOFF

Table 51 List of parameters which can be set from "Extl/O#11 Ports" screen

IDNameDefinition
X1CndPp1CapCmdManually send AO signal
X2CndPp2CapCmdManually send AO signal
X3BV1OpenRateCmdManually send AO signal
X4BV2OpenRateCmdManually send AO signal
X5CndPp1Run/StopManually send DO signal
X6CndPp2Run/StopManually send DO signal
X7CndPp1AlarmManually send DO signal
X8CndPp2AlarmManually send DO signal
DO1CndPp1ONOFFManually send DO signal
DO2CndPp2ONOFFManually send DO signal

K. Checking individual ports of extension I/O #12

Please refer for this extension module to J Checking individual ports of extension I/O #11

L. Checking individual ports of extension I/O #13

User screen: MainMenu > ConfigMode > TrialRun > I/O TrialRun > ExtI/O#013 CheckPort

  1. From "ExtI/O#13 Ports" screen, you can perform point check against I/Os.
ExtI/O#13 Ports1/8
X1CndPp5CapCmd0%
X2CndPp6CapCmd0%
X5CndPp5Run/StopOFF
X6CndPp6Run/StopOFF
X7CndPp5AlarmOFF
X8CndPp6AlarmOFF← f.
DO1CndPp5ONOFFOFF← g.
DO2CndPp6ONOFFOFF← h.

Table 52 List of parameters which can be set from "Extl/O#13 Ports" screen

IDNameDefinition
X1CndPp5CapCmdManually send AO signal
X2CndPp6CapCmdManually send AO signal
X5CndPp5Run/StopManually send DO signal
X6CndPp6Run/StopManually send DO signal
X7CndPp5AlarmManually send DO signal
X8CndPp6AlarmManually send DO signal
DO1CndPp5ONOFFManually send DO signal
DO2CndPp6ONOFFManually send DO signal

M. Checking individual ports of extension I/O #14

Please refer for this extension module to L Checking individual ports of extension I/O #13

N. Checking individual ports of extension I/O #15

User screen: MainMenu > ConfigMode > TrialRun > I/O TrialRun > ExtI/O#015 CheckPort

  1. From "ExtI/O#15 Ports" screen, you can perform point check against I/Os.
ExtI/O#15 Ports1/12
X1CndSO Vv1O/COFF
X2CndSO Vv2O/COFF
X3CndSO Vv3O/CON
X4CndSO Vv4O/COFF
X5CndSO Vv1AlarmOFF
X6CndSO Vv2AlarmON
X7CndSO Vv3AlarmOFF
X8CndSO Vv4AlarmOFF
DO1CndSOVv1ONOFFOFF
DO2CndSOVv2ONOFFON
DO3CndSOVv3ONOFFOFF
DO4CndSOVv4ONOFFOFF

Table 53 List of parameters which can be set from "Extl/O#15 Ports" screen

IDNameDefinition
X1CndSO Vv1O/CManually send DO signal
X2CndSO Vv2O/CManually send DO signal
X3CndSO Vv3O/CManually send DO signal
X4CndSO Vv4O/CManually send DO signal
X5CndSO Vv1AlarmManually send DO signal
X6CndSO Vv2AlarmManually send DO signal
X7CndSO Vv3AlarmManually send DO signal
X8CndSO Vv4AlarmManually send DO signal
DO1CndSO Vv1ONOFFManually send DO signal
DO2CndSO Vv2ONOFFManually send DO signal
DO3CndSO Vv3ONOFFManually send DO signal
DO4CndSO Vv4ONOFFManually send DO signal

O. Checking individual ports of extension I/O #16

Please refer for this extension module to N Checking individual ports of extension I/O #15

10.3. BACnet Module Trial Run

(Used screen: MainMenu > ConfigMode > TrialRun)

  1. From "MainMenu > ConfigMode > TrialRun" screen you can check the error status of BACnet_Module.
TrialRun4/4
Chiller
I/O
BACnet_ModuleNoError

11. Saving / Loading Configuration Data

Configuration for iCM can be saved to / loaded from SD card.

Menu structure for saving / loading configuration data is described below.

○ ConfigMode

- Backup/Restore

□ Backup/Restore

  • Backup......Save configuration data to SD card, check result
  • Restore......Load configuration data from SD card, check result

  • Press the Home Button ☐ to show the "MainMenu" screen.

MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "ConfigMode" menu then press down on the click-dial to jump to "ConfigMode" screen.
MainMenu3/4
Status
Setting
ConfigMode
Password
  1. On the "ConfigMode" screen, turn the click-dial to select "Backup/Restore" menu then press down on the click-dial to jump to "Backup/Restore" screen.
ConfigMode6/8
TrialRun
Backup/Restore
DataManagement
Result
  1. On the "Backup/Restore" screen, you can backup iCM setting to SD card or restore setting from SD card.

NOTE: Make sure SD card is inserted to main controller when performing backup / restore.

Backup/Restore1/4
Backup-
-ResultNG
Restore-
-ResultNG

Table 54 List of parameters which can be set from "Backup/Restore" screen

IDNameDefinition
a.BackupBackup setting to SD card
b.-ResultOK is displayed if backup is successful
c.RestoreRestore setting from SD card
d.-ResultOK is displayed if restore is successful

NOTE: It could be necessary to restore and reboot the controller more than once in order to enable all the devices (first restore and reset) and set all parameters (second restore and reset) from saved configuration.

12. Monitoring

12.1. Showing Current Status of System

Steps for showing the current status of whole system are described below.

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "Status" menu then press down on the click-dial to jump to "Status" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "Status" screen, statuses for whole system are displayed.
Status1/22
Command← refer to 13 Operation
-Status Standby← a.
-Alarm -← b.
-FaultType ----← c.
-StageUp Unlock← d.
-OpMode Cool← e.
-ChWtLvgTempAve 7.5°C← g.
-TempSetpt 7.0°C← h.
-SptSource Manual← i.
-ChWtEntTempAve 12.5°C← j.
-SysLoad 34%← k.
Chiller← refer to 12.2 Showing Current Status of Chillers
EvShutOffValve← refer to 12.3 Showing Current Status of Evaporator Side Shut Off Valve
CndShutOffValve← refer to 12.4 Showing Current Status of Condenser Side Shut Off Valve
PrimaryPump← refer to 12.5 Showing Current Status of Primary Pumps
BypassValve← refer to 12.6 Showing Current Status of Bypass Valve
CondenserPump← refer to 12.7 Showing Current Status of Condenser Pumps
CTBypassValve← refer to 12.8 Showing Current Status of Cooling Tower Bypass Valve
Sensor← refer to 12.9 Showing Current Status of Sensors
I/O
Control

← refer to 12.10 Showing Current Status of I/O
← refer to 12.11 Showing Current Status of Controls

Table 55 List of parameters which can be set from "Command" screen

IDNameDefinition
a.-StatusSystem status (Configuration, Standby, InitialLoading, Operation, E-stop)
b.-AlarmSystem alarm type(-, Fault)
c.-FaultTypeSystem alarm code (see 15.1 Alarm Codes for list of alarm codes)
d.-StageUpStatus of stage up inhibit (lock / unlock)
e.-OpModeOperation mode (Cooling, heating)
g.-ChWtLvgTempAveChilled water leaving temp
h.-TempSetptChilled water temperature setpoint
i.-SptSourceSource of input setting for chilled water temperature setpoint
j.-ChWtEntTempAveChilled water entering temp
k.-SysLoadLoad of current loop

12.2. Showing Current Status of Chillers

Steps for showing the current status of chillers are described below. There are 2 views for showing current status of chillers.

Overview
□ Detailed view

12.2.1. Showing the overview of chillers

(Used screen: MainMenu > Status > Chillers)

  1. On the "Chiller Status screen", statuses of chillers are displayed.

DAIKIN EKDICMPAL - Showing the overview of chillers - 1

flowchart
graph TD
    A["Chiller Status 2/9"] --> B["R/S"]
    B --> C["Stop"]
    C --> D["Alm"]
    D --> E["Cap"]
    F["#01"] --> G["R"]
    G --> H["Stop"]
    H --> I["20%"]
    J["#02"] --> K["M R"]
    K --> L["Stop"]
    L --> M["Comm"]
    M --> N["0%"]
    O["#03"] --> P["L"]
    P --> Q["Stop"]
    Q --> R["Dev"]
    R --> S["20%"]
    T["Actual Capacity"] --> U["Alarm status (Comm: Communication error, Dev: Device error, Mon Monitoring error)"]
    T --> V["Run/Stop status (Run, Stop)"]
    T --> W["Remote/Local (R: Remote, L: Local)"]
    T --> X["Maintenance status (M: Maintenance, “-”: Normal)"]
    T --> Y["Unit number"]

12.2.2. Showing the detailed view of chillers

(Used screen: MainMenu > Status > Chillers > Detail)

  1. On the "MainMenu > Status > Chiller Status" screen, turn the click-dial Ⓞ to select the chiller unit you would like to see the detailed view then press down on the click-dial Ⓡ to jump to "ChillerXX detail" screen
Chiller Status2/9
R/SAlmCap
#01RStop20%
#02M RStopComm0%
#03LStopDev20%
  1. On the "Chiller XX Detail" screen, detailed status of chiller can be monitored
Chiller XX Detail1/14
Run/StopStop
-Command-
AlarmCommError
-ErrorCode--
-AlarmReset-
Maintenance-
-State-
-Reason-
ActualCapacity50%
Remote/LocalRemote
ChWtEntTemp7.0°C
ChWtLvgTemp12.0°C
ChWtLvgTempSetpt7.0°C
OpModeCooling

← Run/Stop State (Run, Stop)
← Run/Stop Command (Run, Stop)
← Alarm Status
← Alarm code of chiller (in hexadecimal)
← Alarm Reset Command (-, Reset)
← Maintenance setting (-, Maintenance)
← Maintenance state (-, Maintenance)
← Reason for maintenance state
← Actual Capacity
← Remote/Local state of chiller (Remote, Local)
← Chilled Water Entering Temperature
← Chilled Water Leaving Temperature
← Chilled Water Setpoint
← Operation Mode (Cooling, Heating)

12.3. Showing Current Status of Evaporator Side Shut Off Valve

(Used screen: MainMenu > Status > EvShutOffValve)

  1. On the "EvShutOffValve Status" screen, statuses of valves are displayed.

DAIKIN EKDICMPAL - Showing Current Status of Evaporator Side Shut Off Valve - 1

flowchart
graph TD
    A["EvShutOffValve Status 2/9"] --> B["O/C Alm"]
    B --> C["#01 Close"]
    C --> D["#02 M Close Dev"]
    D --> E["#03 Close Mon"]
    E --> F["Alarm status (Dev: Device error, Mon: Monitoring error)"]
    F --> G["Open/Close status (Open, Close)"]
    G --> H["Maintenance status (M: Maintenance, “-”: Normal)"]
    H --> I["Unit number"]

12.3.1. Showing the detailed view of Evaporator Side Shut Off Valve

  1. On the "MainMenu > Status > EvShutOffValve Status" screen, turn the click-dial to select the valve unit you would like to see the detailed view then press down on the click-dial to jump to "EvSO_ValveXX detail" screen
EvShutOffValve Status2/9
O/CAlm
#01Close
#02 MCloseDev
#03CloseMon
  1. On the "EvSO_Valve XX Detail" screen, detailed status of Evaporator Side Shut Off Valve can be monitored
EvSO_Valve XX DetailXX/5
Open/CloseClose
-Command-
AlarmCommError
Maintenance-
-State-

← Open/Close State (Open/Close)
← Open/Close Command (Open/Close)
← Alarm Status
← Maintenance setting (-, Maintenance)
← Maintenance state (-, Maintenance)

12.4. Showing Current Status of Condenser Side Shut Off Valve

(Used screen: MainMenu > Status > CndShutOffValve)

  1. On the "EvShutOffValve Status" screen, statuses of valves are displayed.

DAIKIN EKDICMPAL - Showing Current Status of Condenser Side Shut Off Valve - 1

flowchart
graph TD
    A["CndShutOffValve Status 2/9"] --> B["01"]
    B --> C["Close"]
    C --> D["#02 M"]
    D --> E["Close"]
    E --> F["Dev"]
    F --> G["#03"]
    G --> H["Close"]
    H --> I["Mon"]
    I --> J["Alarm status (Dev: Device error, Mon: Monitoring error)"]
    J --> K["Open/Close status (Open, Close)"]
    K --> L["Maintenance status (M: Maintenance, “-”: Normal)"]
    L --> M["Unit number"]

12.4.1. Showing the detailed view of Condenser Side Shut Off Valve

  1. On the "MainMenu > Status > CndShutOffValve Status" screen, turn the click-dial to select the valve unit you would like to see the detailed view then press down on the click-dial to jump to "CndSO_ValveXX detail" screen
CndShutOffValve Status2/9
O/CAlm
01Close
#02 MCloseDev
#03CloseMon
  1. On the "CndSO_ValveXX Detail" screen, detailed status of Condenser Side Shut Off Valve can be monitored
CndSO_ValveXX DetailXX/5
Open/CloseClose
-Command-
AlarmCommError
Maintenance-
-State-

← Open/Close State (Open/Close)
← Open/Close Command (Open/Close)
← Alarm Status
← Maintenance setting (-, Maintenance)
← Maintenance state (-, Maintenance)

12.5. Showing Current Status of Primary Pumps

(Used screen: MainMenu > Status > PrimaryPump)

  1. On the "PrimaryPump Status" screen, statuses of pumps are displayed.

DAIKIN EKDICMPAL - Showing Current Status of Primary Pumps - 1

other | PrimaryPump Status | 2/9 | |---|---| | R/S | Alm Cap | | #01 Stop | 20% ▶ | | #02 M Stop | Comm 0% ▶ | | #03 Stop | Dev 20% ▶ | VFD frequency Alarm status (Comm: communication error, Dev: Device error, Mon: Monitoring error) Run/Stop status (Run, Stop) Maintenance status (M: Maintenance, “-”: Normal) Unit number

12.5.1. Showing the detailed view of Primary Pumps

  1. On the "MainMenu > Status > PrimaryPump Status" screen, turn the click-dial to select the primary pump unit you would like to see the detailed view then press down on the click-dial to jump to "PrimaryPumpXX detail" screen
PrimaryPump Status2/9
R/SAlmCap
#01Stop20%
#02 MStopComm0%
#03StopDev20%
  1. On the "PrimaryPumpXX Detail" screen, detailed status of pump can be monitored
PrimaryPumpXX Detail1/6
Run/StopStop
-Command-
AlarmCommError
Maintenance-
-State-
ActualCapacity50%

← Run/Stop State (Run, Stop)
← Run/Stop Command (Run, Stop)
← Alarm Status
← Maintenance setting (-, Maintenance)
← Maintenance state (-, Maintenance)
← Actual Capacity

12.6. Showing Current Status of Bypass Valve

(Used screen: MainMenu > Status > Bypass Valve)

  1. On the "BypassValve Status" screen, statuses of bypass valve is displayed.
BypassValve Status1/1
ActualOpenRate20%

12.7. Showing Current Status of Condenser Pumps

(Used screen: MainMenu > Status > CondenserPump)

  1. On the "CondenserPump Status" screen, statuses of pumps are displayed.

DAIKIN EKDICMPAL - Showing Current Status of Condenser Pumps - 1

other | Device | CondenserPump Status | VFD frequency | | :--- | :--- | :--- | | #01 | R/S Stop | 20% | | #02 M | Stop Comm | 0% | | #03 | Stop Dev | 20% |

12.7.1. Showing the detailed view of Condenser Pumps

  1. On the "MainMenu > Status > CondenserPump Status" screen, turn the click-dial to select the condenser pump unit you would like to see the detailed view then press down on the click-dial to jump to "CondenserPumpXX detail" screen
CondenserPump Status2/9
R/SAlmCap
#01Stop20%
#02 MStopComm0%
#03StopDev20%
  1. On the "CondenserPump XX Detail" screen, detailed status of pump can be monitored
CondenserPump XX Detail1/6
Run/StopStop
-Command-
AlarmCommError
Maintenance-
-State-
ActualCapacity50%

← Alarm Status
← Maintenance setting (-, Maintenance)
← Maintenance state (-, Maintenance)
← Actual Capacity

12.8. Showing Current Status of Cooling Tower Bypass Valve

(Used screen: MainMenu > Status > CTBypassValve)

  1. On the "CTBypassValve Status" screen, statuses of cooling tower bypass valve are displayed.
CTBypassValve Status1/1
#01ActualOpenRate20%
#02ActualOpenRate20%
#03ActualOpenRate20%
#04ActualOpenRate20%

12.9. Showing Current Status of Sensors

(Used screen: MainMenu > Status > Sensors)

  1. On the "Sensors Status" screen, statuses of sensors are displayed. Displayed sensors differ depending on the system setup.
Sensors Status1/32
DiffPress50kPa
-Alarm-
ChWtLvgTemp6.6°C
-Alarm
ChWtEntTemp11.7°C
-Alarm-
CndWtEntTemp1-°C
-Alarm-
CndWtLvgTemp1-°C
-Alarm-
CndDiffPress1-kPa
-Alarm-
CndWtEntTemp2-°C
-Alarm-
CndWtLvgTemp2-°C
-Alarm-
CndDiffPress2-kPa
-Alarm-
CndWtEntTemp3-°C
-Alarm-
CndWtLvgTemp3-°C
-Alarm-
CndDiffPress3-kPa
-Alarm-

← Differential Pressure
← Alarm status for the sensor
← Supply Water Temperature
← Alarm status for the sensor
← Return Water Temperature
← Alarm status for the sensor
← Condenser Entering Water Temp. #1
← Alarm status for the sensor
← Condenser Leaving Water Temp. #1
← Alarm status for the sensor
← Condenser Differential Pressure #1
← Alarm status for the sensor
← Condenser Entering Water Temp. #2
← Alarm status for the sensor
← Condenser Leaving Water Temp. #2
← Alarm status for the sensor
← Condenser Differential Pressure #2
← Alarm status for the sensor
← Condenser Entering Water Temp. #3
← Alarm status for the sensor
← Condenser Leaving Water Temp. #3
← Alarm status for the sensor
← Condenser Differential Pressure #3
← Alarm status for the sensor

CndWtEntTemp4-° C
-Alarm-
CndWtLvgTemp4-° C
-Alarm-
CndDiffPress4-kPa
-Alarm-
OutdoorTemp-° C
-Alarm

← Condenser Entering Water Temp. #4
← Alarm status for the sensor
← Condenser Leaving Water Temp. #4
← Alarm status for the sensor
← Condenser Differential Pressure #4
← Alarm status for the sensor
← Outdoor Temperature
← Alarm status for the sensor

12.10. Showing Current Status of I/O

(Used screen: MainMenu > Status > I/O)

  1. On the "I/O Status" screen, status of I/Os are displayed.
I/O Status1/1
DblSptOFF

12.11. Showing Current Status of Controls

(Used screen: MainMenu > Status > Control )

  1. On the "Control Status" screen, status of controls is displayed.
Control Status1/2
Chiller
PrimaryPump

← 12.11.1 Show current status of chiller control
← 12.11.2 Show current status of primary pump control

12.11.1. Show current status of chiller control

  1. From the "MainMenu>Status>Control Status" screen, turn the click-dial Ⓞ to select "Chiller" menu then press down on the click-dial Ⓞ to jump to "Chiller Control Status" screen.
Control Status1/2
Chiller
PrimaryPump
  1. On the "Chiller Control Status" screen, status of chiller controls is displayed.
ChillerCtrl Status1/9
StageUp
-StgByLoadLimit100s
-StgUpDiff100s
-StgByTargetLoad100s
-StgForRotation100s
StageDown
-StgByLoadLimit100s
-StgDnDiff100s
-PonyChCtrl100s

← Timer count value for staging up for Load Condition

← Timer count value for staging up for Supply temperature condition

← Timer count value for staging up for Target load condition

← Timer count value for staging up for time without staging conditions

← Timer count value for staging down

← Timer count value for staging down

← Timer count value for staging down

12.11.2. Show current status of primary pump control

  1. From the "MainMenu>Status>Control Status" screen, turn the click-dial Ⓞ to select "PrimaryPump" menu then press down on the click-dial Ⓞ to jump to "PrimaryPump Control Status" screen.
Control Status2/2
Chiller
PrimaryPump
  1. On the "PrimaryPump Control Status" screen, status of primary pump controls is displayed.
PriPpCtrl Status1/9
StageUp100s
StageDown100s

← Timer count value for staging up

← Timer count value for staging down

13. Operation

Menu structure of related screens is displayed below.

○ Status

- Command

Command

○ SystemRun/Stop
o TempSetpt
- EmgStopReset
○ ForcePriPumpMode

13.1. Basic Commanding

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "Status" menu then press down on the click-dial to jump to "Status" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "Status" screen, turn the click-dial to select "Command" menu then press down on the click-dial to jump to "Command screen.
Status1/22
Command
-StatusStandby
-Alarm-
-FaultType----
  1. On the "Command" screen, various commands can be sent.
Command1/9
SystemRun/StopRun← a.
-ActiveValueRun← b.
TempSetpt7.0°C← c.
-ActiveValue7.0°C← d.
EmgStopReset← 13.2 Resetting emergency stop
ForcePriPumpModeOFF← e.
-ActiveValue-← f.
ForceCndPumpModeOFF← g.
-ActiveValue-← h.

Table 56 List of parameters which can be set from "Command" screen

IDNameDefinition
a.SystemRun/StopRun/Stop command for iCM system
b.-ActiveValueCurrently active command signal
c.TempSetptTemperature setpoint command
d.-ActiveValueCurrently active setpoint
e.ForcePriPumpModeON/OFF command for force primary pump run
f.-ActiveValueCurrently active command signal
g.ForceCndPumpModeON/OFF command for force condenser pump run
h.-ActiveValueCurrently active command signal

13.2. Resetting emergency stop

(Used screen: "MainMenu > Status > Command > EmgStopReset")

  1. On the "MainMenu > Status > Command" screen, turn the click-dial to select "EmgStopReset" menu then press down on the click-dial to jump to "EmgStopReset" screen.
Command5/9
-ActiveValueRun
TempSetpt7.0°C
-ActiveValue7.0°C
EmgStopReset
  1. On the "EmgStopReset" screen you can reset emergency stop. In order to reset emergency stop state, emergency stop signal input from BACnet needs to be OFF.
EmgStopReset1/3
EmgStopReset-
-StatusE-Stop
-EmgStopFromBACnetOFF

Table 57 List of parameters which can be set from "Command" screen

IDNameDefinition
a.EmgStopResetReset command for emergency stop state
b.-StatusCheck if current status is emergency stop
c.-EmgStopFromBACnetCheck current status of emergency stop command from BACnet

13.3. Setting Chillers to "Maintenance"

Steps for setting chillers to “Maintenance” mode to exclude them from staging are described below.

  1. On the "MainMenu" screen, turn the click-dial to select "Status" menu then press down on the click-dial to jump to "Status" screen.
MainMenu1/4
Status
Setting
ConfigMode
Password
  1. On the "Status" screen, turn the click-dial to select "Chiller" menu then press down on the click-dial to jump to "Chiller Status" screen.
Status13/22
Chiller
EvShutOffValve
CndShutOffValve
PrimaryPump
  1. On the "Chiller status" screen, turn the click-dial to select the chiller you need to set to "Maintenance" mode then press down on the click-dial to jump to "ChillerXX Detail" screen.
Chiller Status2/9
R/SAlmCap
#01RStop20%
#02MStopComm0%
#03LStopDev20%
  1. On the "ChillerXX Detail" screen, turn the click-dial ⏻ to select the "Maintenance" menu then press down on the click-dial ⏻ to jump to input mode screen for "Maintenance".
Chiller01 Detail5/12
Maintenance-
-State-
ActualCapacity20%
Remote/LocalRemote
  1. On the input mode screen for "Maintenance", turn the click-dial to change value ("-" for returning from Maintenance mode, or "Maintenance" to set the chiller to Maintenance mode) then press down on the click-dial to validate your setting.

DAIKIN EKDICMPAL - Setting Chillers to "Maintenance" - 1

flowchart
graph TD
    A["Chiller01 Detail"] --> B["Maintenance"]
    B --> C["Chiller01 Detail"]
    C --> D["Maintenance"]
    D --> E["1/1"]
  1. On the "ChillerXX Detail" screen, look at "-State" menu below "Maintenance" to check if the setting has successfully been processed. Be careful when setting chillers back from Maintenance mode as when chiller is under alarm, they will be forced to be Maintenance mode and can't be set back.
Chiller01 Detail5/12
MaintenanceMaintenance
-StateMaintenance
ActualCapacity20%
Remote/LocalRemote

14. Alarming

14.1. Showing Current List of Alarms

Steps for showing the current list of alarms are described below.

  1. Press the Alarm button 🔒 to show the "Alarming" screen.
Alarming1/3
AlarmList99 ▶
AlarmHistory99 ▶
-ClearHistory-
  1. On the "Alarming" screen, turn the click-dial ⏻ to select "AlarmList" menu then press down on the click-dial ⏻ to jump to "AlarmList" screen.
Alarming1/3
AlarmList99 ▶
AlarmHistory99 ▶
-ClearHistory-
  1. On the "AlarmList" screen, current list of alarms are shown. Types of alarms that are displayed are: chiller alarms, pump alarms, and system alarms. Refer to the Appendix for alarm codes for each type.
AlarmList
+127: Chiller01 Device Error
+998: Pump08 Monitoring Error
+10111: Piping Gr#01 not enough pumps available to meet minimum

←Alarm Index of chiller is shown

  1. To see the details of individual alarms, simply select the alarm on the "AlarmList" screen by turning the click-dial ⏻ and jump to the "AlarmList Detail" screen by pressing down on the click-dial ⏻

AlarmList +127: Chiller01 Device Error ▶ +998: Pump08 Monitoring Error ▶ +10111: Piping Gr#01 not enough ▶ pumps available to meet minimum AlarmList Detail +121: Chiller01 Device Error 10/15/2014 23:12:29

14.2. Showing History of Alarms

Steps for showing the history of alarms are described below.

  1. Press the Alarm button 🔒 to show the "Alarming" screen.
Alarming1/3
AlarmList99 ▶
AlarmHistory99 ▶
-ClearHistory-
  1. On the "Alarming" screen, turn the click-dial to select "AlarmHistory" menu then press down on the click-dial to jump to "AlarmHistory" screen.
Alarming1/3
AlarmList99 ▶
AlarmHistory99 ▶
-ClearHistory-
  1. On the "AlarmHistory" screen, history of alarms are shown
AlarmHistory
+127: Chiller01 Device Error
-127: Chiller01 Device Error
+10111: Piping Gr#01 not enough pumps available to meet minimum

← “+” sign indicates occurrence

← “-” sign indicates recovery

  1. To see the details of individual alarms, simply select the alarm on the "AlarmList" screen by turning the click-dial and jump to the "AlarmHistory Detail" screen by pressing down on the click-dial

AlarmHistory +127: Chiller01 Device Error ▶ -127: Chiller01 Device Error ▶ +10111: Piping Gr#01 not enough ▶ pumps available to meet minimum

AlarmHistory Detail
+127: Chiller01 Device Error
10/15/201423:12:29

← Date and time of event is shown

14.3. Deleting History of Alarms

Steps for deleting the history of alarms are described below.

  1. Press the Alarm button 🔒 to show the "Alarming" screen.
Alarming1/3
AlarmList99▶
AlarmHistory99▶
-ClearHistory-
  1. On the "Alarming" screen, turn the click-dial Ⓞ to select "-ClearHistory" menu then press down on the click-dial Ⓞ to jump to input mode screen for "-ClearHistory"
Alarming1/3
AlarmList99
AlarmHistory99
-ClearHistory-
  1. On the input mode screen for "-ClearHistory", turn the click-dial to select "clear" then press down on the click-dial to validate your command.

DAIKIN EKDICMPAL - Deleting History of Alarms - 1

flowchart
graph TD
    A["Alarming"] --> B["-ClearHistory"]
    C["1/1"] --> D["1/1"]
    E["Alarming"] --> F["-ClearHistory"]
    G["1/1"] --> H["Clear"]
  1. History of alarms will be cleared.
Alarming1/3
AlarmList99 ▶
AlarmHistory0 ▶
-ClearHistory-

14.4. Resetting Alarms

Steps for resetting alarms on chillers are described below. Chillers have 3 kinds of errors; device error, communication error and monitoring error. Amog the 3 kinds of errors, device error (Alarm detected at the chiller) can be reset from iCM. Communication error and monitoring error can be reset by restoring communication status between iCM and chillers to match command from iCM and status of each device.

There are 2 steps for resetting alarms

A. Alarm Reset

B. Setting Chillers back from maintenance status

A. Alarm Reset

  1. Press the Home Button ☐ to show the "MainMenu" screen.
MainMenu1
Status
Setting
ConfigMode
Password
  1. On the "MainMenu" screen, turn the click-dial to select "Status" menu then press down on the click-dial to jump to "Status" screen.

DAIKIN EKDICMPAL - Alarm Reset - 1

Status
Setting
ConfigMode
Password
  1. On the "Status" screen, turn the click-dial Ⓞ to select "Chiller" menu then press down on the click-dial Ⓥ to jump to "Chiller Status" screen.
Status11
Chiller
EvShutOffValve
CndShutOffValve
PrimaryPump
  1. On the "Chiller status" screen, turn the click-dial Ⓞ to select the chiller you need to reset alarm then press down on the click-dial Ⓞ to jump to "ChillerXX Detail" screen.
Chiller Status3
R/SAlmCap
#01RStop20%
#02M RStopDev0%
#03LStopComm20%
  1. On the "ChillerXX Detail" screen, turn the click-dial ⏻ to select the "Alarm reset" menu then press down on the click-dial ⏻ to jump to input mode screen for "Alarm reset".
Chiller01 Detail4
Run/StopStop
AlarmDevE
-ErrorCodeE402
-AlarmReset-
  1. On the input mode screen for "AlarmReset", turn the click-dial to change value to "Reset" then press down on the click-dial to validate your setting.
Chiller01 Detail1
-AlarmReset
Chiller01 Detail1
-AlarmResetReset
  1. On the "ChillerXX Detail" screen, look at "Alarm" menu to check if the alarm has successfully been reset.
Chiller01 Detail4
Run/StopStop
Alarm-
-ErrorCode--
-AlarmReset-

NOTE: While the conditions that triggered the alarm is true, you will not be able to reset the alarm.

15. APPENDIX – Alarms

15.1. Alarm Codes

15.1.1. Alarm for the chiller system

Alarm for the system includes hardware errors of the iCM itself or chiller system not being able to satisfy A/C load due to failure of multiple equipment.

The error code of chiller system alarm is described in a six-digits decimal alarm code e.g. 000101.

Category 0Category 1Category2Alarm textAlarm CodeDescription
Ext I/O Module Disconnect (01)101: Extension IO module#01 disconnect (ExtIO#01)000101Module Disconnected
102: Extension IO module#02 disconnect (ExtIO#02)000102Module Disconnected
103: Extension IO module#03 disconnect (ExtIO#03)000103Module Disconnected
104: Extension IO module#04 disconnect (ExtIO#04)000104Module Disconnected
105: Extension IO module#05 disconnect (ExtIO#05)000105Module Disconnected
106: Extension IO module#06 disconnect (ExtIO#06)000106Module Disconnected
109: Extension IO module#09 disconnect (ExtIO#09)000109Module Disconnected
110: Extension IO module#10 disconnect (ExtIO#10)000110Module Disconnected
111: Extension IO module#11 disconnect (ExtIO#11)000111Module Disconnected
112: Extension IO module#12 disconnect (ExtIO#12)000112Module Disconnected
113: Extension IO module#13 disconnect (ExtIO#13)000113Module Disconnected
114: Extension IO module#14 disconnect (ExtIO#14)000114Module Disconnected
115: Extension IO module#15 disconnect (ExtIO#15)000115Module Disconnected
116: Extension IO module#16 disconnect (ExtIO#16)000116Module Disconnected
Comm Module Disconnect (02)202: BACnet module disconnect (BACnet)000202Module Disconnected
Loop (1)Loop1 (01)10101: Emergency stop command On010101I/O fault
10102: All pumps are under maintenance010102I/O fault
10103: 10103: All cond. Pumps are under maintenance010103I/O fault
Loop1 (01)Shortage of flow (1)10111: PipingGr#01 not enough pumps available to meet minimum010111Pump fault
10112: PipingGr#02 not enough pumps available to meet minimum010112Pump fault
10113: PipingGr#03 not enough pumps available to meet minimum010113Pump fault
10114: PipingGr#04 not enough pumps available to meet minimum010114Pump fault
Shortage of cooling water flow (2)10121: Cond. PipingGr#01 not enough pumps available to meet minimum010121Condenser pump fault
10122: Cond. PipingGr#02 not enough pumps available to meet minimum010122Condenser pump fault
10123: Cond. PipingGr#03 not enough pumps available to meet minimum010123Condenser pump fault
10124: Cond. PipingGr#04 not enough pumps available to meet minimum010124Condenser pump fault
Ai (2)Main controller (00)20002: Leaving water temp. setpoint command port failure (Base X2)020002I/O fault
20006: Leaving water temp. sensor failure (Base X6)020006I/O fault
20007: Entering water temp. sensor failure (Base X7)020007I/O fault
20008: Header differential pressure sensor failure (Base X8)020008I/O fault
Ext9 (09)20901: Entering condenser water temp. sensor#01 failure (ExtIO#09 X1)020901I/O fault
20902: Entering condenser water temp. sensor#02 failure (ExtIO#09 X2)020902I/O fault
20903: Leaving condenser water temp. sensor#01 failure (ExtIO#09 X3)020903I/O fault
20904: Leaving condenser water temp. sensor#02 failure (ExtIO#09 X4)020904I/O fault
20905: Condenser water differential pressure sensor#01 failure (ExtIO#09 X5)020905I/O fault
20906: Condenser water differential pressure sensor#02 failure (ExtIO#09 X6)020906I/O fault
20907: Outdoor temp. sensor failure (ExtIO#09 X7)020907I/O fault
Ext10 (10)21001: Entering condenser water temp. sensor#03 failure(ExtIO#10 X1)021001I/O fault
21002: Entering condenser water temp. sensor#04 failure(ExtIO#10 X2)021002I/O fault
21003: Leaving condenser water temp. sensor#03 failure(ExtIO#10 X3)021003I/O fault
21004: Leaving condenser water temp. sensor#04 failure(ExtIO#10 X4)021004I/O fault
21005: Condenser water differential pressure sensor#03failure (ExtIO#10 X5)021005I/O fault
21006: Condenser water differential pressure sensor#04failure (ExtIO#10 X6)021006I/O fault
21001: Entering condenser water temp. sensor#03 failure(ExtIO#10 X1)021001I/O fault
Di(3)Main controller (00)30001: iCM Run/Stop command port failure (Base X1)030001I/O fault
30003: Emergency stop command port failure (Base X3)030003I/O fault
30005: Double setpoint command port failure (Base X5)030005I/O fault
30011: Force primary pump on command port failure (BaseDI1)030011I/O fault
30012: Force condenser pump on command port failure(Base DI2)030012I/O fault
Ext1 (01)30102: Pump#01 On/Off status port failure (ExtIO#01 X2)030102I/O fault
30103: Pump#01 Alarm status port failure (ExtIO#01 X3)030103I/O fault
30105: Pump#02 On/Off status port failure (ExtIO#01 X5)030105I/O fault
30106: Pump#02 Alarm status port failure (ExtIO#01 X6)030106I/O fault
Ext2 (02)30202: Pump#03 On/Off status port failure (ExtIO#02 X2)030202I/O fault
30203: Pump#03 Alarm status port failure (ExtIO#02 X3)030203I/O fault
30205: Pump#04 On/Off status port failure (ExtIO#02 X5)030205I/O fault
30206: Pump#04 Alarm status port failure (ExtIO#02 X6)030206I/O fault
Ext3 (03)30302: Pump#05 On/Off status port failure (ExtIO#03 X2)030302I/O fault
30303: Pump#05 Alarm status port failure (ExtIO#03 X3)030303I/O fault
30305: Pump#06 On/Off status port failure (ExtIO#03 X5)030305I/O fault
30306: Pump#06 Alarm status port failure (ExtIO#03 X6)030306I/O fault
Ext4 (04)30402: Pump#07 On/Off status port failure (ExtIO#04 X2)030402I/O fault
30403: Pump#07 Alarm status port failure (ExtIO#04 X3)030403I/O fault
30405: Pump#08 On/Off status port failure (ExtIO#04 X5)030405I/O fault
30406: Pump#08 Alarm status port failure (ExtIO#04 X6)030406I/O fault
Ext5 (05)30501: Shut off valve#01 Open/Close status port failure(ExtIO#05 X1)030501I/O fault
30502: Shut off valve#02 Open/Close status port failure(ExtIO#05 X2)030502I/O fault
30503: Shut o valve#03 Open/Close status port failure(ExtIO#05 X3)030503I/O fault
30504: Shut o valve#04 Open/Close status port failure(ExtIO#05 X4)030504I/O fault
30505: Shut o valve#01 Alarm status port failure (ExtIO#05 X5)030505I/O fault
30506: Shut o valve#02 Alarm status port failure (ExtIO#05 X6)030506I/O fault
30507: Shut o valve#03 Alarm status port failure (ExtIO#05 X7)030507I/O fault
30508: Shut o valve#04 Alarm status port failure (ExtIO#05 X8)030508I/O fault
Ext6 (06)30601: Shut off valve#05 Open/Close status port failure(ExtIO#06 X1)030601I/O fault
30602: Shut off valve#06 Open/Close status port failure(ExtIO#06 X2)030602I/O fault
30603: Shut o valve#07 Open/Close status port failure(ExtIO#06 X3)030603I/O fault
30604: Shut o valve#08 Open/Close status port failure(ExtIO#06 X4)030604I/O fault
30605: Shut o valve#05 Alarm status port failure (ExtIO#06 X5)030605I/O fault
30606: Shut o valve#06 Alarm status port failure (ExtIO#06 X6)030606I/O fault
30607: Shut o valve#07 Alarm status port failure (ExtIO#06 X7)030607I/O fault
30608: Shut o valve#08 Alarm status port failure (ExtIO#06 X8)030608I/O fault
Ext11 (11)31105: Cond. pump#01 On/Off status port failure (ExtIO#11 X5)031105I/O fault
31106: Cond. pump#02 On/O status port failure (ExtIO#11 X6)031106I/O fault
31107: Cond. pump#01 Alarm status port failure (ExtIO#11 X7)031107I/O fault
31108: Cond. pump#02 Alarm status port failure (ExtIO#11 X8)031108I/O fault
Ext12 (12)31205: Cond. pump#03 On/O status port failure (ExtIO#12 X5)031205I/O fault
31206: Cond. pump#04 On/Off status port failure (ExtIO#12 X6)031206I/O fault
31207: Cond. pump#03 Alarm status port failure (ExtIO#12 X7)031207I/O fault
31208: Cond. pump#04 Alarm status port failure (ExtIO#12 X8)031208I/O fault
Ext13 (13)31305: Cond. pump#05 On/Off status port failure (ExtIO#13 X5)031305I/O fault
31306: Cond. pump#06 On/Off status port failure (ExtIO#13 X6)031306I/O fault
31307: Cond. pump#05 Alarm status port failure (ExtIO#13 X7)031307I/O fault
31308: Cond. pump#06 Alarm status port failure (ExtIO#13 X8)031308I/O fault
Ext14 (14)31405: Cond. pump#07 On/Off status port failure (ExtIO#14 X5)031405I/O fault
31406: Cond. pump#08 On/O status port failure (ExtIO#14 X6)031406I/O fault
31407: Cond. pump#07 Alarm status port failure (ExtIO#14 X7)031407I/O fault
31408: Cond. pump#08 Alarm status port failure (ExtIO#14 X8)031408I/O fault
Ext15 (15)31501: Cond. shut o valve#01 Open/Close status port failure (ExtIO#15 X1)031501I/O fault
31502: Cond. shut o valve#02 Open/Close status port failure (ExtIO#15 X2)031502I/O fault
31503: Cond. shut o valve#03 Open/Close status port failure (ExtIO#15 X3)031503I/O fault
31504: Cond. shut o valve#04 Open/Close status port failure (ExtIO#15 X4)031504I/O fault
31505: Cond. shut o valve#01 Alarm status port failure (ExtIO#15 X5)031505I/O fault
31502: Cond. shut o valve#02 Alarm status port failure (ExtIO#15 X6)031506I/O fault
31503: Cond. shut o valve#03 Alarm status port failure (ExtIO#15 X7)031507I/O fault
31504: Cond. shut o valve#04 Alarm status port failure (ExtIO#15 X8)031508I/O fault
Ext16 (16)31601: Cond. shut o valve#05 Open/Close status port failure (ExtIO#16 X1)031601I/O fault
31602: Cond. shut o valve#06 Open/Close status port failure (ExtIO#16 X2)031602I/O fault
31603: Cond. shut o valve#07 Open/Close status port failure (ExtIO#16 X3)031603I/O fault
31604: Cond. shut o valve#08 Open/Close status port failure (ExtIO#16 X4)031604I/O fault
31605: Cond. shut o valve#05 Alarm status port failure (ExtIO#16 X5)031605I/O fault
31602: Cond. shut o valve#06 Alarm status port failure (ExtIO#16 X6)031606I/O fault
31603: Cond. shut o valve#07 Alarm status port failure (ExtIO#16 X7)031607I/O fault
31604: Cond. shut o valve#08 Alarm status port failure (ExtIO#16 X8)031608I/O fault
Ao(4)Main controller (00)40004: Byp. valve Open Rate command port failure (Base X4)040004I/O fault
Ext1 (01)40101: Pump#01 VFD command port failure (ExtIO#01 X1)040101I/O fault
40104: Pump#02 VFD command port failure (ExtIO#01 X4)040104I/O fault
Ext2 (02)40201: Pump#03 VFD command port failure (ExtIO#02 X1)040201I/O fault
40204: Pump#04 VFD command port failure (ExtIO#02 X4)040204I/O fault
Ext3 (03)40301: Pump#05 VFD command port failure (ExtIO#03 X1)040301I/O fault
40304: Pump#06 VFD command port failure (ExtIO#03 X4)040304I/O fault
Ext4 (04)40401: Pump#07 VFD command port failure (ExtIO#04 X1)040401I/O fault
40404: Pump#08 VFD command port failure (ExtIO#04 X4)040404I/O fault
Ext11 (11)41101: Cond. Pump#01 VFD command port failure (ExtIO#11 X1)041101I/O fault
41102: Cond. Pump#02 VFD command port failure (ExtIO#11 X2)041102I/O fault
41103: Cond. Byp. valve#01 Open Rate command port failure (ExtIO#11 X3)041103I/O fault
41104: Cond. Byp. valve#02 Open Rate command port failure (ExtIO#11 X4)041104I/O fault
Ext12 (12)41201: Cond. Pump#03 VFD command port failure (ExtIO#12 X1)041201I/O fault
41202: Cond. Pump#04 VFD command port failure (ExtIO#12 X2)041202I/O fault
41203: Cond. Byp. valve#03 Open Rate command port failure (ExtIO#12 X3)041203I/O fault
41204: Cond. Byp. valve#04 Open Rate command port failure (ExtIO#12 X4)041204I/O fault
Ext13 (13)41301: Cond. Pump#05 VFD command port failure (ExtIO#13 X1)041301I/O fault
41302: Cond. Pump#06 VFD command port failure (ExtIO#13 X2)041302I/O fault
Ext14 (14)41401: Cond. Pump#07 VFD command port failure (ExtIO#14 X1)041401I/O fault
41402: Cond. Pump#08 VFD command port failure (ExtIO#14 X2)041402I/O fault
Do(5)Main Controller(00)50021: iCM Run/Stop status port failure (Base DO1)050021I/O fault
50022: iCM Alarm status port failure (Base DO2)050022I/O fault

15.1.2. Alarms for individual equipment

Alarm for individual equipment, chillers, pumps, valves, cooling towers and sensors, is displayed in the HMI. For each type of equipment, types of errors that are displayed include all or part of the following.

□ Communication error:
Communication with the equipment is lost
□ Device error :
Alarm signal from the equipment is received.
□ Monitoring error:
The equipment did not follow a command from iCM
□ Warning:

Warning signal from the equipment is received

Types of alarms that are displayed for each equipment type and their corresponding error codes are shown in the following table.

ChillerShut off valvePump (I/O)Bypass valveCondenser pumpCT shutoff valve
ModbusI/O
Communication errorError code: 999N/AN/AN/AN/AN/AN/A
Device errorError code: Received from chillerError code: 997Error code: 997Error code: 997N/AError code: 997Error code: 997
Monitoring errorError code: 998Error code: 998Error code: 998Error code: 998N/AError code: 998Error code: 998
WarningError code: Received from chillerN/AN/AN/AN/AN/AN/A
  1. APPENDIX – BACnet Integration Data (Main Controller)
CategoryNameObj TypeDescription
SystemMonitoringAlarmiCM system alarmBIGeneral alarm
iCM system alarm codeAIiCM System Alarm List code
StatusiCM system statusMIiCM Status Global
iCM system ON/OFF statusBIiCM Syson
iCM system setpointAIActive cold setpoint
iCM system loadAISystem load
Source of input status for ON/OFFMILoc/remote mode of iCM Network on/off
Source of input status for chilled water temperature setpointMILoc/remote mode of iCM Cold setpoint
Source of input status for force primary pump onMILoc/remote mode of iCM ChW pump force on
Status of double setpoint signalBIDouble setpoint digital input
Differential pressureAIChilled water loop pressure difference
Chilled water leaving temperatureAIChilled water leaving temperature before header
Chilled water return temperatureAIChilled water return temperature before header
CommandiCM system ON/OFF commandBOiCM Network on/off
iCM chilled water temperature setpointAViCM Cold setpoint
Force primary pump onBOiCM Force Chilled water pump ON
Emergency stopBOiCM Emergency stop
Emergency stop resetBViCM Emergency stop reset
ChillerMonitoringAlarmAlarm statusBIActive Unit Alarm Ch
Alarm codeAIAlarm Code Ch
Alarm resetBOClear Alarm Ch
StatusON/OFF statusBIChiller On/Off
Actual capacityAILoad unit
Chilled water return temperatureAIChilled water return temperature unit
Chilled water leaving temperatureAIChilled water leaving temperature unit
PumpMonitoringAlarmAlarm statusBIChilled water pump Alarm
StatusON/OFF statusBIChilled water Pump On/Off
VFD capacity statusAIChilled water Pump VFD output
Bypass ValveMonitoringStatusOpen rate statusAILoad bypass valve position
Shut-off ValveMonitoringAlarmAlarm statusBIShut-off valve Alarm
StatusOpen/Close statusBIShut-off valve Open/Close

17. APPENDIX – HMI Monitoring and Command

Points available for reading and writing from HMI is described below

CategoryNameDescription
SystemMonitoringAlarmiCM system alarmGeneral alarm
iCM system alarm codeiCM System Alarm List code
StatusiCM system statusiCM Status Global
iCM system ON/OFF statusiCM Sys On
iCM system setpointActive cold setpoint
iCM system loadSystem load
Differential pressureChilled water loop pressure difference
Chilled water leaving temperatureChilled water leaving temperature before header
Chilled water return temperatureChilled water return temperature before header
Stage up inhibit statusStage up inhibit by pull-down rate control
CommandiCM system ON/OFF commandiCM Network on/off
iCM chilled water temperature setpointiCM Cold setpoint
Force primary pump oniCM Force Chilled water pump ON
Emergency stop resetiCM Emergency stop reset
ChillerMonitoringAlarmAlarm statusActive Unit Alarm Ch
Alarm codeAlarm Code Ch
Alarm resetClear Alarm Ch
StatusON/OFF statusON/OFF status of each chiller
Operation modeOperation mode of each chiller
Chilled water setpointChilled water setpoint of each chiller
Actual capacityActual capacity of each chiller
Operation hoursAccumulated operation hours of each chiller
Remote/local statusRemote/local status of each chiller
Available statusAvailable status of each chiller
Chilled water return temperatureChilled water return temperature unit
Chilled water leaving temperatureChilled water leaving temperature unit
Shut-off ValveMonitoringAlarmAlarm statusAlarm status of each shut off valve
StatusOpen/Close statusOpen/Close status of each shut off valve
Available statusAvailable status of each shut off valve
Primary PumpMonitoringAlarmAlarm statusAlarm status of each primary pump
StatusON/OFF statusON/OFF status of each primary pump
VFD capacityVFD output of each primary pump
Available statusAvailable status of each primary pump
Operation hoursAccumulated operation hour of each pri. pump
CommandON/OFF commandON/OFF command for each condenser pump
Capacity commandCapacity command for each condenser pump
Bypass Valve (Evaporator)Capacity commandCapacity command for each condenser pumpLoad bypass valve position
Bypass Valve (Cooling)MonitoringStatusBypass valve open rateLoad bypass valve position
Condenser pumpMonitoringAlarmAlarm statusAlarm status of each condenser pump
StatusON/OFF statusON/OFF status of each condenser pump
VFD capacityVFD output of each condenser pump
Available statusAvailable status of each condenser pump
Operation hoursAccumulated operation hr. of each con. pump
CommandON/OFF commandON/OFF command for each condenser pump
Capacity commandCapacity command for each condenser pump
Condenser bypass valveMonitoringStatusOpen rate statusOpen rate of each condenser bypass valve
CommandOpen rate commandOpen rate command of each condenser bypass valve

18. APPENDIX - I/O Mapping

The I/O mapping of the main controller and I/O modules are listed below.

Main Controller (POL687.70)

I/O nameSystem related I/O'sI/O typeSpecification
AI1UnusedAi
AI2UnusedAi
AI3UnusedAi
X1System ON/OFF commandDinon-voltage a-contact input
X2Temperature setpointAi4-20mA input
X3Forced stoppage inputDinon-voltage b-contact input
X4Bypass Valve Open CommandAo4 - 20mA output
X5Double Setpoint ON/OFFDinon-voltage a-contact input
X6Chilled Water Leaving TemperatureAi4 - 20mA input
X7Chilled Water Entering TemperatureAi4 - 20mA input
X8Differential PressureAi4 - 20mA input
DO1System ON/OFF statusDonon-voltage a-contact output
DO2System alarmDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DO7UnusedDo
DO8UnusedDo
DO9UnusedDo
DO10UnusedDo
DI1Primary pump force operationDinon-voltage a-contact output
DI2Cooling water pump force operationDinon-voltage a-contact output
DI3UnusedDi
DI4UnusedDi
DI5UnusedDi
DI6UnusedDi

I/O module #1 (POL965)

I/O namePrimary pumps 1 and 2I/O typeSpecification
X1Pri. pump1 VFD commandAo4 - 20mA input
X2Pri. pump1 ON/OFF statusDinon-voltage a-contact input
X3Pri. pump1 alarmDinon-voltage a-contact input
X4Pri. pump2 VFD commandAo4 - 20mA input
X5Pri. pump2 ON/OFF statusDinon-voltage a-contact input
X6Pri. pump2 alarmDinon-voltage a-contact input
X7UnusedDo
X8UnusedDo
DO1Pri. pump1 ON/OFF commandDonon-voltage a-contact output
DO2Pri. pump2 ON/OFF commandDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #2 (POL965)

I/O namePrimary pumps 3 and 4I/O typeSpecification
X1Pri. pump3 VFD commandAo4 - 20mA input
X2Pri. pump3 ON/OFF statusDinon-voltage a-contact input
X3Pri. pump3 alarmDinon-voltage a-contact input
X4Pri. pump4 VFD commandAo4 - 20mA input
X5Pri. pump4 ON/OFF statusDinon-voltage a-contact input
X6Pri. pump4 alarmDinon-voltage a-contact input
X7UnusedDo
X8UnusedDo
DO1Pri. pump3 ON/OFF commandDonon-voltage a-contact output
DO2Pri. pump4 ON/OFF commandDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #3 (POL965)

I/O namePrimary pumps 5 and 6I/O typeSpecification
X1Pri. pump5 VFD commandAo4 - 20mA input
X2Pri. pump5 ON/OFF statusDinon-voltage a-contact input
X3Pri. pump5 alarmDinon-voltage a-contact input
X4Pri. pump6 VFD commandAo4 - 20mA input
X5Pri. pump6 ON/OFF statusDinon-voltage a-contact input
X6Pri. pump6 alarmDinon-voltage a-contact input
X7UnusedDo
X8UnusedDo
DO1Pri. pump5 ON/OFF commandDonon-voltage a-contact output
DO2Pri. pump6 ON/OFF commandDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #4 (POL965)

I/O namePrimary pumps 7 and 8I/O typeSpecification
X1Pri. pump7 VFD commandAo4 - 20mA input
X2Pri. pump7 ON/OFF statusDinon-voltage a-contact input
X3Pri. pump7 alarmDinon-voltage a-contact input
X4Pri. pump8 VFD commandAo4 - 20mA input
X5Pri. pump8 ON/OFF statusDinon-voltage a-contact input
X6Pri. pump8 alarmDinon-voltage a-contact input
X7UnusedDo
X8UnusedDo
DO1Pri. pump7 ON/OFF commandDonon-voltage a-contact output
DO2Pri. pump8 ON/OFF commandDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #5 (POL965)

I/O nameEvaporator Shut-off valves 1, 2, 3 and 4I/O typeSpecification
X1Shut-off valve1 Open/Close statusDinon-voltage a-contact input
X2Shut-off valve2 Open/Close statusDinon-voltage a-contact input
X3Shut-off valve3 Open/Close statusDinon-voltage a-contact input
X4Shut-off valve4 Open/Close statusDinon-voltage a-contact input
X5Shut-off valve1 alarmDinon-voltage a-contact input
X6Shut-off valve2 alarmDinon-voltage a-contact input
X7Shut-off valve3 alarmDinon-voltage a-contact input
X8Shut-off valve4 alarmDinon-voltage a-contact input
DO1Shut-off valve1 Open/Close commandDonon-voltage a-contact output
DO2Shut-off valve2 Open/Close commandDonon-voltage a-contact output
DO3Shut-off valve3 Open/Close commandDonon-voltage a-contact output
DO4Shut-off valve4 Open/Close commandDonon-voltage a-contact output
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #6 (POL965)

I/O nameEvaporator Shut-off valves 5, 6, 7 and 8I/O typeSpecification
X1Shut-off valve5 Open/Close statusDinon-voltage a-contact input
X2Shut-off valve6 Open/Close statusDinon-voltage a-contact input
X3Shut-off valve7 Open/Close statusDinon-voltage a-contact input
X4Shut-off valve8 Open/Close statusDinon-voltage a-contact input
X5Shut-off valve5 alarmDinon-voltage a-contact input
X6Shut-off valve6 alarmDinon-voltage a-contact input
X7Shut-off valve7 alarmDinon-voltage a-contact input
X8Shut-off valve8 alarmDinon-voltage a-contact input
DO1Shut-off valve5 Open/Close commandDonon-voltage a-contact output
DO2Shut-off valve6 Open/Close commandDonon-voltage a-contact output
DO3Shut-off valve7 Open/Close commandDonon-voltage a-contact output
DO4Shut-off valve8 Open/Close commandDonon-voltage a-contact output
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #9 (POL965)

I/O nameCooling water system 1 and 2 Temperature and differential pressure sensorsI/O typeSpecification
X1Cooling water chiller entering temperature 1Ai4 - 20mA input / NTC 10K input
X2Cooling water chiller entering temperature 2Ai4 - 20mA input / NTC 10K input
X3Cooling water chiller leaving temperature 1Ai4 - 20mA input / NTC 10K input
X4Cooling water chiller leaving temperature 2Ai4 - 20mA input / NTC 10K input
X5Cooling water differential pressure 1Ai4 - 20mA input
X6Cooling water differential pressure 2Ai4 - 20mA input
X7Outdoor temperatureAi4 - 20mA input / NTC 10K input
X8Unused-
DO1UnusedDo
DO2UnusedDo
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #10 (POL965)

I/O nameCooling water system 3 and 4Temperature and differential pressure sensorsI/O typeSpecification
X1Cooling water chiller entering temperature 3Ai4 - 20mA input / NTC 10K input
X2Cooling water chiller entering temperature 4Ai4 - 20mA input / NTC 10K input
X3Cooling water chiller leaving temperature 3Ai4 - 20mA input / NTC 10K input
X4Cooling water chiller leaving temperature 4Ai4 - 20mA input / NTC 10K input
X5Cooling water differential pressure 3Ai4 - 20mA input
X6Cooling water differential pressure 4Ai4 - 20mA input
X7Unused-
X8Unused-
DO1UnusedDo
DO2UnusedDo
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #11 (POL965)

I/O nameCooling water pumps 1 and 2I/O typeSpecification
X1Cooling water pump 1 capacity commandAo4 - 20mA output
X2Cooling water pump 2 capacity commandAo4 - 20mA output
X3Cooling water bypass valve 1 open rate commandAo4 - 20mA output
X4Cooling water bypass valve 2 open rate commandAo4 - 20mA output
X5Cooling water pump 1 on/off statusDinon-voltage a-contact input
X6Cooling water pump 2 on/off statusDinon-voltage a-contact input
X7Cooling water pump 1 fault statusDinon-voltage a-contact input
X8Cooling water pump 2 fault statusDinon-voltage a-contact input
DO1Cooling water pump 1 on/off commandDonon-voltage a-contact output
DO2Cooling water pump 2 on/off commandDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #12 (POL965)

I/O nameCooling water pumps 3 and 4I/O typeSpecification
X1Cooling water pump 3 capacity commandAo4 - 20mA output
X2Cooling water pump 4 capacity commandAo4 - 20mA output
X3Cooling water bypass valve 3 open rate commandAo4 - 20mA output
X4Cooling water bypass valve 4 open rate commandAo4 - 20mA output
X5Cooling water pump 3 on/off statusDinon-voltage a-contact input
X6Cooling water pump 4 on/off statusDinon-voltage a-contact input
X7Cooling water pump 3 fault statusDinon-voltage a-contact input
X8Cooling water pump 4 fault statusDinon-voltage a-contact input
DO1Cooling water pump 3 on/off commandDonon-voltage a-contact output
DO2Cooling water pump 4 on/off commandDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #13 (POL965)

I/O nameCooling water pumps 5 and 6I/O typeSpecification
X1Cooling water pump 5 capacity commandAo4 - 20mA output
X2Cooling water pump 6 capacity commandAo4 - 20mA output
X3Unused-
X4Unused-
X5Cooling water pump 5 on/off statusDinon-voltage a-contact input
X6Cooling water pump 6 on/off statusDinon-voltage a-contact input
X7Cooling water pump 5 fault statusDinon-voltage a-contact input
X8Cooling water pump 6 fault statusDinon-voltage a-contact input
DO1Cooling water pump 5 on/off commandDonon-voltage a-contact output
DO2Cooling water pump 6 on/off commandDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #14 (POL965)

I/O nameCooling water pumps 7 and 8I/O typeSpecification
X1Cooling water pump 7 capacity commandAo4 - 20mA output
X2Cooling water pump 8 capacity commandAo4 - 20mA output
X3Unused-
X4Unused-
X5Cooling water pump 7 on/off statusDinon-voltage a-contact input
X6Cooling water pump 8 on/off statusDinon-voltage a-contact input
X7Cooling water pump 7 fault statusDinon-voltage a-contact input
X8Cooling water pump 8 fault statusDinon-voltage a-contact input
DO1Cooling water pump 7 on/off commandDonon-voltage a-contact output
DO2Cooling water pump 8 on/off commandDonon-voltage a-contact output
DO3UnusedDo
DO4UnusedDo
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #15 (POL965)

I/O nameCondenser Shut-off valves 1, 2, 3 and 4I/O typeSpecification
X1Cooling water side shut-off valve 1 open/close statusDinon-voltage a-contact input
X2Cooling water side shut-off valve 2 open/close statusDinon-voltage a-contact input
X3Cooling water side shut-off valve 3 open/close statusDinon-voltage a-contact input
X4Cooling water side shut-off valve 4 open/close statusDinon-voltage a-contact input
X5Cooling water side shut-off valve 1 faultDinon-voltage a-contact input
X6Cooling water side shut-off valve 2 faultDinon-voltage a-contact input
X7Cooling water side shut-off valve 3 faultDinon-voltage a-contact input
X8Cooling water side shut-off valve 4 faultDinon-voltage a-contact input
DO1Cooling water side shut-off valve 1 open/close commandDonon-voltage a-contact output
DO2Cooling water side shut-off valve 2 open/close commandDonon-voltage a-contact output
DO3Cooling water side shut-off valve 3 open/close commandDonon-voltage a-contact output
DO4Cooling water side shut-off valve 4 open/close commandDonon-voltage a-contact output
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

I/O module #16 (POL965)

I/O nameCondenser Shut-off valves 5, 6, 7 and 8I/O typeSpecification
X1Cooling water side shut-off valve 5 open/close statusDinon-voltage a-contact input
X2Cooling water side shut-off valve 6 open/close statusDinon-voltage a-contact input
X3Cooling water side shut-off valve 7 open/close statusDinon-voltage a-contact input
X4Cooling water side shut-off valve 8 open/close statusDinon-voltage a-contact input
X5Cooling water side shut-off valve 5 faultDinon-voltage a-contact input
X6Cooling water side shut-off valve 6 faultDinon-voltage a-contact input
X7Cooling water side shut-off valve 7 faultDinon-voltage a-contact input
X8Cooling water side shut-off valve 8 faultDinon-voltage a-contact input
DO1Cooling water side shut-off valve 5 open/close commandDonon-voltage a-contact output
DO2Cooling water side shut-off valve 6 open/close commandDonon-voltage a-contact output
DO3Cooling water side shut-off valve 7 open/close commandDonon-voltage a-contact output
DO4Cooling water side shut-off valve 8 open/close commandDonon-voltage a-contact output
DO5UnusedDo
DO6UnusedDo
DI1UnusedDi

19. APPENDIX – Compatibility List

List of Daikin chillers that can be connected and managed by iCM is as follow:

Product NameProduct CodeControllerCompatibility
AWSEWAD_C MT 3^1 Y (*)
AWS INVEWAD_CZMT 3Y (*)
AWS FCEWAD_CFMT 3Y (**)
TZEWAD_TZMT 3Y (*)
TZBEWAD_TZBMT 3Y (*)
McENERGY HPIEWYD_BZ MT 2^2 N
McENERGY MonoEWAD_EMT 3Y (*)
McENERGY DualEWAD_DMT 3Y (*)
WHS-EEWWD_IMT 3Y (*)
EcoplusEWWD_GMT 3Y (*)
Prox EvoEWWQ_BMT 3Y
WHBEWWD_JMT 3Y (*)
PFSEWWD_HMT 3Y
VZEWWD_VZMT 3Y (*)
WCZ MonoEWWQ_GMT 3Y (*)
WCZ DualEWWQ_LMT 3Y (*)
WCZ HPIEWHQ_GMT 3N
ACZ-C Mulple Scroll COEWAQ_EMT 3Y
ACZ-H Mulple Scroll HPEWYQ_FMT 3N
AGZ-C Mulple Scroll COEWAQ_GMT 3Y (*)
AGZ-H Mulple Scroll HPEWYQ_GMT 3N
WSC – Centrifugal SingleDWSCMT 2Y
WDC – Centrifugal DualDWDCMT 2Y
WMC – Centrifugal MagnecDWMCMT 2Y

Table 58 – Compatibility List
(*): NOTE 1: iCM can manage chillers with Paral Heat Recovery opon, but cannot manage chillers with Total Heat Recovery opon.
(**): NOTE 2: iCM can manage chillers with Free-cooling opon, but the funcon itself is managed by chiller controller (not centralized).

20. APPENDIX – Integrated Modbus Points

The list of Modbus points integrated to iCM is listed below.

20.1. Global chillers

The list of status monitoring points for (formerly) McQuay global chillers are shown below.

RegisterName
AddressBit
40002b0Chiller Enable Output
40008b0Chiller On/Off
40011-Chiller Mode Output
40013-Actual Capacity(3)
40012-Active Setpoint
40028-Warming Alarm Index
40029-Problem Alarm Index
40030-Fault Alarm Index
40031-Warning Alarm Code
40032-Problem Alarm Code
40033-Fault Alarm Code
40016-Evaporator Entering Fluid Temperature (5)
40017-Evaporator Leaving Fluid Temperature (6)
40001b0Chiller Local/Remote

The list of control command points for (formerly) McQuay global chillers are shown below.

RegisterName
AddressBit
40009b0Chiller Enable Setpoint
40034-Chiller Mode Setpoint – Network
40035-Cool Setpoint – Network
40010b0Clear Alarms – Network
40316b0Units

20.2. U.S. Chillers

The list of status monitoring points for (formerly) McQuay U.S. chillers are shown below.

RegisterName
AddressBit
3-Chiller On Off
3-Chiller On/Off
40148-Chiller Mode Output
40011-Actual Capacity
40003-Active Setpoint
40130b1~b9Warnings
40131~40132b0~b15Problems
40133~40144b5~b4Faults
40130b1~b9Warning Alarm Code
40131~40132b0~b15Problem Alarm Code
40133~40144b5~b4Fault Alarm Code
40130b1~b9Warning Alarm Index
40131~40132b0~b15Problem Alarm Index
40133~40144b5~b4Fault Alarm Index
40005-Evaporator Entering Water Temperature
40007-Evaporator Leaving Water Temperature for Unit
6-Chiller Local/Remote

The list of control command points for (formerly) McQuay U.S. chillers are shown below.

RegisterName
AddressBit
2-Chiller Enable
40146-Chiller Mode Setpoint
40002-Cool Setpoint
25-Clear Alarms

NOTE

NOTE

The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A.. Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content, and the products and services presented therein. Specification are subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A..

DAIKIN APPLIED EUROPE S.p.A.

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : DAIKIN

Model : EKDICMPAL

Category : Controller