PF-420 - Wall socket SurgeX - Free user manual and instructions
Find the device manual for free PF-420 SurgeX in PDF.
| Product Type | Wall-mount surge protector with power filtering |
| Model | PF-420 |
| Brand | SurgeX |
| Number of Outlets | 4 grounded outlets |
| Input Voltage | 120 V AC |
| Maximum Current | 15 A |
| Surge Protection Rating | 2000 joules |
| Clamping Voltage | 330 V |
| Response Time | < 1 ns |
| EMI/RFI Filtering | Yes, up to 60 dB attenuation |
| Dimensions (H x W x D) | 4.2 x 2.6 x 1.4 in (10.7 x 6.6 x 3.6 cm) |
| Weight | 0.5 lb (0.23 kg) |
| Mounting | Direct wall mount over standard outlet box |
| Power Cord | Hardwired, no detachable cord |
| Overload Protection | 15 A resettable circuit breaker |
| Operating Temperature | 32°F to 104°F (0°C to 40°C) |
| Safety Certifications | UL 1449 3rd Edition, cUL |
| Warranty | Lifetime limited warranty |
| Maintenance | Wipe with dry cloth, no liquids |
| Replaceable Parts | None, unit is sealed |
| Status Indicator | Green LED for protection active |
Frequently Asked Questions - PF-420 SurgeX
User questions about PF-420 SurgeX
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Wall socket in PDF format for free! Find your manual PF-420 - SurgeX and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. PF-420 by SurgeX.
USER MANUAL PF-420 SurgeX
Installation Instructions
PF-420
Mounting
The SurgeX PF420 is designed to be mounted on a flat, vertical surface. Secure the unit by fastening at the corners with appropriate screws. This product must not be flush mounted or set between wall studs as overheating can occur under such conditions. Use caution when removing knock-outs so that damage does not occur to internal components.
Connection
The SurgeX PF420 provides four identical circuits, each rated at 120 Volts and 20 Amps, providing a total capacity of 80 Amps. This product shall be wired only by qualified Electricians using 12 AWG conductors as specified in Article 310 of the 2005 National Electric Code, as set forth in Table 310.13. Any type of conductor suitable for use in wet or dry locations such as (but not limited to) THHN, THHW, THW, THWN, or TW shall be considered acceptable if local Code permits. Each circuit must be protected by a 20 Amp circuit breaker.
A special terminal is provided for each circuit to carry an Isolated Ground (technical ground) though the unit. These terminals have no connection to the chassis ground or to the unit itself and their sole purpose is to provide a convenient way of joining isolated ground wires.
The four higher terminal blocks are for the Line connections, with the corresponding Load terminal block for that circuit directly below it.
Line Connection
Connect the electrical service from the load side of the circuit breaker to the upper terminal block as follows:
• Live (Black) wire to the terminal labeled “LINE”
- Neutral (White) wire to the terminal labeled “NEUT”
- Ground (Green) wire to the terminal labeled “GRND”
- Isolated Ground wire (if used) to the terminal labeled “ISO GND”
Load Connection
Connect the equipment circuit (load) to the lower terminal block as follows:
• Live (Black) wire to the terminal labeled “LOAD”
- Neutral (White) wire to the terminal labeled “NEUT”
- Ground (Green) wire to the terminal labeled “GRND”
- Isolated Ground wire (if used) to the terminal labeled "ISO GND"
Indicator Light
There are four green indicator lights on the front of the unit, one for each circuit. These green lights are Self-Test indicators that indicate power is applied to the unit and also that the internal surge protection circuitry on each circuit is fully functional.