SAMSUNG AC036TXADKC - Air conditioner

AC036TXADKC - Air conditioner SAMSUNG - Free user manual and instructions

Find the device manual for free AC036TXADKC SAMSUNG in PDF.

📄 30 pages English EN Download 💬 AI Question 11 questions ⚙️ Specs
Notice SAMSUNG AC036TXADKC - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Split Air Conditioner (Cooling Only)
Model Number AC036TXADKC
Cooling Capacity 3.6 kW (12,000 BTU/h)
Energy Efficiency Ratio (EER) 3.2 W/W (Class A)
Power Supply 220-240 V ~ 50 Hz, Single Phase
Refrigerant Type R410A
Indoor Unit Dimensions (W x H x D) 820 x 285 x 210 mm
Outdoor Unit Dimensions (W x H x D) 720 x 548 x 265 mm
Indoor Unit Weight 8.5 kg
Outdoor Unit Weight 27.0 kg
Airflow Rate (Cooling) 420 m³/h
Noise Level (Indoor/Outdoor) Lower than 32 dB(A) / 52 dB(A)
Operating Temperature Range 16°C to 30°C (Cooling)
Remote Control Included (IR wireless)
Functions Cooling, Dehumidification, Fan Only, Timer, Sleep Mode, Auto Restart
Filter Type Washable Anti-Bacterial Filter
Filter Cleaning Interval Every 2 weeks
Safety Features Overheat Protection, Compressor Time Delay, Auto Shut-off
Installation Type Wall Mounted Split System
Spare Parts Availability Commonly available via authorized service centers
Repairability Index High (Modular design)

Frequently Asked Questions - AC036TXADKC SAMSUNG

How do I clean the air filter?
Turn off the unit and unplug it. Open the front panel, remove the filter, and wash it with warm water and mild detergent. Let it dry completely before reinstalling. Clean every 2 weeks for optimal performance.
What should I do if the air conditioner does not cool properly?
Check if the filter is clean, ensure the thermostat is set lower than room temperature, verify the outdoor unit has clearance, and confirm the mode is set to Cool. If problem persists, contact a technician.
Can I use an extension cord?
No. Plug the unit directly into a dedicated wall outlet with the specified voltage. Using an extension cord may cause overheating or fire.
How do I set the timer?
Press the Timer button on the remote control. Use +/- to set the desired time (1-24 hours). Press Set to confirm. The unit will turn on/off automatically.
What does the 'Auto Restart' function do?
After a power failure, the unit automatically resumes operation with the previous settings once power is restored. This feature is enabled by default.
How often should I service the outdoor unit?
It is recommended to have a professional check the outdoor unit annually. Clean the coils and fins from dust and debris, and ensure proper airflow.
What does error code 'E5' mean?
Error code E5 indicates a communication fault between indoor and outdoor units. Check connections and cables. If persists, call a service technician.
Is the refrigerant R410A environmentally friendly?
R410A is a HFC blend that does not deplete the ozone layer, but it has a high Global Warming Potential (GWP). Proper handling and recycling are required.
What is the ideal temperature setting for energy saving?
For cooling, set the thermostat between 24°C and 26°C. This balances comfort and energy consumption. Each degree lower increases power usage by about 8%.
Where can I find the spare parts for my AC?
Contact Samsung authorized service centers or visit the official Samsung parts website. Provide the model number AC036TXADKC for accurate parts.

User questions about AC036TXADKC SAMSUNG

1 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

Your email remains private: it is only used to notify you if someone answers your question.

What are the complete technical specifications of the Samsung AC036TXADKC outdoor unit?
Frequently Asked Questions - 15 d
Response Notice-Facile

Here are the complete technical specifications of the Samsung AC036TXADKC/VN outdoor unit, extracted from the installation manual:

Main Features

  • Brand: Samsung
  • Model: AC036TXADKC
  • Unit Type: Outdoor unit (Condenser)
  • Refrigerant Type: R-410A
  • Cooling Capacity: Not specified in the manual

Outdoor Unit Dimensions

  • Width: 940 mm
  • Height: 630 mm
  • Depth: 220 mm

Refrigerant Lines

  • Maximum Horizontal Length: 30 m
  • Maximum Height Difference: 30 m
  • Connection Diameters (liquid pipe): Ø6.35, Ø9.52, Ø12.70, Ø15.88, Ø19.05, Ø22.23 mm
  • Connection Diameters (gas pipe): Same as liquid pipe diameters

Minimum Installation Clearances (single unit)

  • Top: 150 mm minimum
  • Front: 750 mm minimum
  • Back: 150 mm minimum
  • Left Side: 150 mm minimum
  • Right Side: 150 mm minimum

For multiple installations: A minimum spacing of 300 mm is required between units (horizontally and vertically for stacked installations).

Respond (be the first)

Download the instructions for your Air conditioner in PDF format for free! Find your manual AC036TXADKC - SAMSUNG and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. AC036TXADKC by SAMSUNG.

USER MANUAL AC036TXADKC SAMSUNG

  • Thank you for purchasing this Samsung air conditioner.
  • Before operating this unit, please read this manual carefully and retain it for future reference.

Safety Information 3

Safety Information 3

Installation Procedure 5

Step 1 Choosing the installation location 5

Step 2 Fixing the outdoor unit in place 8

Step 3 Connecting the power cables, communication cable, and controllers 9

Step 4 Optional: Extending the power cable 14

Step 5 Connecting the refrigerant pipe 16

Step 6 Optional: Cutting and flaring the pipes 16

Step 7 Installing oil traps 17

Step 8 Connecting up and removing air in the circuit 18

Step 9 Adding refrigerant (R-410A) 19

Step 10 Performing the gas leak test 20

Step 11: Connecting the drain hose to the outdoor unit

Step 12: Insulating the refrigerant pipes

Step 13: Checking the earthing

Step 14: Performing final check and trial operation

Extra procedures

Pumping down refrigerant

Relocating the indoor and outdoor units

Using the stop valve

Appendix

Troubleshooting

SAMSUNG AC036TXADKC - Appendix - 1

Correct Disposal of This Product

(Waste Electrical & Electronic Equipment)

(Applicable in countries with separate collection systems)

This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g. charger, headset, USB cable) should not be disposed of with other household waste at the end of their working life. To prevent possible harm to the environment or human health from uncontrolled waste disposal, please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources.

Household users should contact either the retailer where they purchased this product, or their local government office, for details of where and how they can take these items for environmentally safe recycling.

Business users should contact their supplier and check the terms and conditions of the purchase contract. This product and its electronic accessories should not be mixed with other commercial wastes for disposal.

SAMSUNG AC036TXADKC - (Applicable in countries with separate collection systems) - 1

WARNING

- Hazards or unsafe practices that may result in severe personal injury or death.

SAMSUNG AC036TXADKC - WARNING - 1

CAUTION

  • Hazards or unsafe practices that may result in minor personal injury or property damage.
  • Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.

SAMSUNG AC036TXADKC - CAUTION - 1

WARNING

  • Always disconnect the air conditioner from the power supply before servicing it or accessing its internal components.
  • Verify that installation and testing operations are performed by qualified personnel.
  • Verify that the air conditioner is not installed in an easily accessible area.

General information

SAMSUNG AC036TXADKC - General information - 1

WARNING

  • Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order to be able to use it as reference after installation.
  • For maximum safety, installers should always carefully read the following warnings.
  • Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air conditioner is sold or transferred.
  • This manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types of units with different control systems may damage the units and invalidate the warranty. The manufacturer shall not be responsible for damages arising from the use of non compliant units.
  • The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper connection of electric and requirements set forth in the "Operating limits" table, included in the manual, shall immediately invalidate the warranty.
  • The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable to be installed in areas used for laundry.
  • Do not use the units if damaged. If problems occur, switch the unit off and disconnect it from the power supply.
  • In order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact SAMSUNG's technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy. • Always remember to inspect the unit, electric connections, refrigerant tubes and protections regularly. These operations should be performed by qualified personnel only.
  • The unit contains moving parts, which should always be kept out of the reach of children.
  • Do not attempt to repair, move, alter or reinstall the unit. If performed by unauthorized personnel, these operations may cause electric shocks or fires.
  • Do not place containers with liquids or other objects on the unit.
  • All the materials used for the manufacture and packaging of the air conditioner are recyclable.
  • The packing material and exhaust batteries of the remote controller(optional) must be disposed of in accordance with current laws.
  • The air conditioner contains a refrigerant that has to be disposed of as special waste. At the end of its life cycle, the air conditioner must be disposed of in authorized centres or returned to the retailer so that it can be disposed of correctly and safely.
  • Wear protective equipment (such as safety gloves, goggles, and headgear) during installation and maintenance works. Installation/repair technicians may be injured if protective equipment is not properly equipped.
  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

- For use in Europe: This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

Installing the unit

SAMSUNG AC036TXADKC - Installing the unit - 1

WARNING

IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines.

  • Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the material from the retailer.)
  • After completing the installation, always carry out a functional test and provide the instructions on how to operate the air conditioner to the user.
  • Do not use the air conditioner in environments with hazardous substances or close to equipment that release free flames to avoid the occurrence of fires, explosions or injuries.
  • Do not install the product in a place where thermohygrostat is needed (such as server room, machinery room, computer room, etc.) Those places do not provide guaranteed operation condition of the product therefore performance can be poor in these places.
  • Do not install the product in a ship or a vehicle (such as a campervan). Salt, vibration or other environmental factor may cause the product malfunction, electric shock or fire.
  • Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from both sides and allow repairs or maintenance operations to be carried out. The unit's components should be accessible and easy to disassemble without endangering people and objects.

- For this reason, when provisions of the installation manual are not complied with, the cost required to access and repair the units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses, ladders, scaffolding or any other elevation system will NOT be considered part of the warranty and will be charged to the end customer.

Power supply line, fuse or circuit breaker

SAMSUNG AC036TXADKC - Power supply line, fuse or circuit breaker - 1

WARNING

  • Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance with current local safety standards.
  • Always verify that a suitable earthing connection is available.
  • Verify that the voltage and frequency of the power supply comply with the specifications and that the installed power is sufficient to ensure the operation of any other domestic appliance connected to the same electric lines.
  • Always verify that the cut-off and protection switches are suitably dimensioned.
  • Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram included in the manual.
  • Always verify that electric connections (cable entry, section of leads, protections...) are compliant with the electric specifications and with the instructions provided in the wiring scheme. Always verify that all connections comply with the standards applicable to the installation of air conditioners. • Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage category.
  • Be sure not to perform power cable modification, extension wiring, and multiple wire connection. – It may cause electric shock or fire due to poor connection, poor insulation, or current limit override.
  • When extension wiring is required due to power line damage, refer to "Step 4 Optional: Extending the power cable" in the installation manual.

Step 1 Choosing the installation location

Installation location requirements

  • Do not place the outdoor unit on its side or upside down. Failing to do so may cause the compressor lubrication oil to run into the cooling circuit and lead to a serious damage to the unit. • Install the unit in a well-ventilated location away from direct sunlight or strong winds. • Install the unit in a location that would not obstruct any passageways or thoroughfares. • Install the unit in a location that would not inconvenience or disturb your neighbors, as they could be affected by the noise or the airflow coming from the unit. • Install the unit in a location where the pipes and the cables can be easily connected to the indoor unit. • Install the unit on a flat, stable surface that can withstand the weight of the unit. Otherwise, the unit can generate noise and vibration during operation. • Install the unit so that the air flow is directed towards the open area.
  • Maintain sufficient clearance around the outdoor unit, especially from a radio, computer, stereo system, etc.

Indoor Unit Control 1 m or more 1 m or more Stereo Computer etc Air Guide Duct (This product is not provided by Samsung) 1.5 m or more 1.5 m or more 300 mm 200 mm Fuse Outdoor Unit

• Install the unit at a height where its base can be firmly fixed in place. • Make sure that the water dripping from the drain hose runs away correctly and safely.

CAUTION

  • You have just purchased a system air conditioner and it has been installed by your installation specialist.
  • This device must be installed according to the national electrical rules.
  • If your outdoor unit exceeds a net weight of 60 kg, do not install it on a suspended wall, but stand it on a floor.

- When installing the outdoor unit at the seaside, make sure that it is not directly exposed to sea breeze. If you cannot find an adequate place free from direct sea breeze, construct a protection wall or a protective fence.

- Install the outdoor unit in a place (such as near buildings etc.) where it can be prevented from sea breeze. Failure to do so may cause damage to the outdoor unit.

Sea breeze Sea Sea Sea breeze Outdoor Unit Outdoor Unit

- If you cannot avoid installing the outdoor unit at the seaside, construct a protection wall around to block the sea breeze.

- Construct a protection wall with a solid material such as concrete to block the sea breeze. Make sure that the height and the width of the wall are 1.5 times larger than the size of the outdoor unit. Also, secure a space larger than 700 mm between the protection wall and the outdoor unit for exhausted air to ventilate.

Sea breeze Sea Outdoor Unit Protection wall

SAMSUNG AC036TXADKC - CAUTION - 3

CAUTION

  • Depending on the condition of power supply, unstable power or voltage may cause malfunction of the parts or control system. (At the ship or places using power supply from electric generator...etc) • Install the unit in a place where water can drain smoothly.
  • If you have any difficulty finding installation location as prescribed above, contact your manufacturer for details.
  • Be sure to clean the sea water and the dust on the heat exchanger of the outdoor unit and apply a corrosion inhibitor on it. (At least once in a year.)
  • Check the condition of the product periodically.
  • Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG (Code: MOK-220SA) or commercial water repellent grease and wax, etc., based on the product condition.
  • When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate measures like covering the product.

- If the product installed within 500 m of seashore, special anti-corrosion treatment is required.

Please contact your local SAMSUNG representative for further details. Special anti-corrosion treatment is required.

Outdoor unit dimensions

(Unit: mm)

Type A AC024TXADKC880 49 310 798 661 338 15

Type B

AC036TXADKC940 977 998 528 537 675 330 620 360 384

Type C

AC048TXADKC940 1185 1210 558 567 675 330° 620 360 384

Minimum clearances for the outdoor unit

When installing 1 outdoor unit

(Unit: mm)

150 or more 500 or more 150 or more 150 or more 1000 or more 1000 or more 500 or more 150 or more 150 or more 1000 or more

When installing more than 1 outdoor unit

(Unit: mm)

1000 or more 2000 or more 2000 or more 3000 or more 150 or more 300 or more 150 or more 1500 or more 1000 or more

300 or more 150 or more 150 or more 200 or more 300 or more 300 or more 500 or more 500 or more

SAMSUNG AC036TXADKC - Minimum clearances for the outdoor unit - 4

CAUTION

- The outdoor unit must be installed according to the specified distances in order to permit accessibility from each side, to guarantee correct operation, maintenance, and repair of the unit.

The components of the outdoor unit must be reachable and removable under safe conditions for people and the unit.

SAMSUNG AC036TXADKC - CAUTION - 1

WARNING

- Should adopt bar type louver. Don't use a type of rain resistance louver.

[Bar type louver] [Rain resistance louver]

- Louver specifications.

  • Angle criteria: less than 20°
  • Opening ratio criteria: greater than 80%

Moving the outdoor unit with wire rope

1 Before carrying the outdoor unit, fasten two wire ropes of 8 m or longer, as shown in the figure. 2 To prevent damages or scratches effectively, insert a piece of cloth between the outdoor unit and the ropes. 3 Move the outdoor unit.

AC036/048TXADKCWire rope Plate protection cloth

AC024TXADKCWire rope Plate protection cloth

Step 2 Fixing the outdoor unit in place

Install the outdoor unit on a rigid and stable base to prevent disturbance from any noise caused by vibration.

When installing the unit at a height or in a location exposed to strong winds, fix the unit securely to a support (i.e., a wall or a ground).

Fix the outdoor unit with anchor bolts. Make sure that the anchor bolts are 20 mm or higher from the base surface.

AC024TXADKC (Unit: mm)Anchor bolt hole 357 338 359 661 880

AC036/048TXADKC (Unit: mm)Anchor bolt hole 330 360 384 620 940

SAMSUNG AC036TXADKC - Step 2 Fixing the outdoor unit in place - 3

CAUTION

• Install a drain outlet at the lowest end around the base for outdoor unit drainage. - When installing the outdoor unit on the roof, waterproof the unit and check the ceiling strength.

Pure technical diagram of a mechanical bracket with hatched areas and a central circular feature (no text or symbols)

Simple 3D diagram showing a cross symbol crossed over a grid of cubes (no text or labels)

  • Make sure that the wall can support the weights of the rack and the outdoor unit. • Install the rack close to the column as much as possible.

Optional: Fixing the outdoor unit to a wall with a rack

Designed to cut off residual vibration from outdoor unit to rack. (not supplied with product) Anchor bolt 20 mm Base surface Soft rubber designed to cut off vibration from rack to wall. (not supplied with product)

• Install a proper grommet in order to reduce noise and residual vibration transferred by the outdoor unit towards the wall.

SAMSUNG AC036TXADKC - Optional: Fixing the outdoor unit to a wall with a rack - 2

CAUTION

- When installing an air guide duct, be sure to check the following:

- The screws do not damage the copper pipe.

- The air guide duct is fixed firmly on the guard fan.

Step 3 Connecting the power cables, communication cable, and controllers

You must connect the following three electrical cables to the outdoor unit:

  • The main power cable between the auxiliary circuit breaker and the outdoor unit.
  • The outdoor-to-indoor power cable between the outdoor unit and the indoor unit.
  • The communication cable between the outdoor unit and the indoor unit.

SAMSUNG AC036TXADKC - Step 3 Connecting the power cables, communication cable, and controllers - 1

CAUTION

  • During installation, make the refrigerant connections first, then the electrical connections. If the unit is being uninstalled, disconnect the electrical cables first, then the refrigerant connections.
  • Connect the air conditioner to the earthing system before making the electrical connections.

SAMSUNG AC036TXADKC - CAUTION - 1

NOTE

Especially, if your outdoor unit is designed for the Russian and European markets, consult the supply authority, if necessary, to estimate and reduce the supply system impedance before installation.

Air conditioning system examples

When using an earth leakage circuit breaker (ELCB) for a single phase

graph LR A["MCCB 1¢"] --> B["ELB"] C["ELCB 1¢"] --> B B --> D["Outdoor Unit Indoor Unit"] D --> E["Earthing"] E --> F["Outdoor-to-indoor power cable"] style A fill:#f9f,stroke:#333 style C fill:#f9f,stroke:#333 style D fill:#ccf,stroke:#333 style E fill:#cfc,stroke:#333 style F fill:#fcc,stroke:#333

SAMSUNG AC036TXADKC - Air conditioning system examples - 2

CAUTION

If the outdoor unit is installed in a location vulnerable to electric leakage or submergence, make sure to install an ELCB.

Connecting the main power cable

When using ELBPower Supply MCCB ELB 1(L)2(N)LN F2 Cable clamp Outdoor to indoor power cable Main Power Cable Cable tie Communication cable

When using ELB for a single phase

Power Supply MCCB ELB Electrical component box The appearance of the unit may be different from the picture depending on the model. Indoor Unit 1-phase 1(L) 2(N) L N Outdoor-to indoor power cable Main power cable Cable tie Communication cable

SAMSUNG AC036TXADKC - Connecting the main power cable - 3

CAUTION

  • You should connect the power cable into the power cable terminal and fasten it with a clamp.
  • The unbalanced power must be maintained within 2% of the supply rating. If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power exceeds 4% of the supply rating, the indoor unit is protected, stopped, and the error mode indicates.
  • To protect the product from water and possible shock, keep the power cable and the connection cord of the indoor and outdoor units within ducts (with appropriate IP rating and material selection for your application).
  • Ensure that the main supply connection is made through a switch that disconnects all poles, with a contact gap of at least 3 mm. Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage category.
  • Keep distances of 50 mm or more between the power cable and the communication cable.

Main power terminal block specifications AC024TXADKC (Unit: mm)1(L) 2(N) L N 13.8 10.3 F1 F2 10.1 11.4

1-phase terminal block specifications

AC036/048TXADKC (Unit: mm)1(L) 2(N) L N 16.5 12 F1 F2 10.1 11.4

Main power cable specifications

The power cable is not supplied with the air conditioner.

  • Select the power supply cable in accordance with relevant local and national regulations.
  • Wire size must comply with the applicable local and national code.
  • Specifications for local wiring power cord and branch wiring are in compliance with local code.
Model Outdoor unitInput current (A) Power supply
Indoor unit Outdoor unit HzVoltage range (V)Outdoor unitIndoor unitTotalMCA (A)MFA (A)
RatedMin.Max.
AC024TN4PKCAC024TXADKC60220198 26420.01.521.521.525.0
AC024TN4DKC20.01.521.521.525.0
AC036TN4PKCAC036TXADKC24.02.026.026.0 30.0
AC036TN4DKC24.02.026.026.0 30.0
AC048TN4PKCAC048TXADKC32.02.034.0 34.040.0
AC048TN4DKC32.02.034.034.040.0

SAMSUNG AC036TXADKC - Main power cable specifications - 1

NOTE

1. Voltage range: Units are suitable for use on electrical systems where the voltage supplied to the unit terminal is not below or above the listed range limits.

- Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.

2 Maximum allowable voltage variation between phases is 2%.

3 Wire size & type must comply with the applicable local and national code.

- Wire size: Based on the value of MCA. - Wire type: 60245 IEC 57(IEC)/H05RN-F(CENELEC) or 60245 IEC 66(IEC/H07RN-F(CENELEC) grade or more.)

4 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).

5 MCA represents maximum input current.

• MFA represents capacity which may accept MCA

• Abbreviations MCA: Min. Circuit Amps. (A) MFA: Max. Fuse Amps. (A)

Silence mode controller wiring diagram • A C 0 2 4 T X A D K COutdoor unit 8.8 8.8 CN001 Non-voltage contact

  • AC036/048TXADKCSAMSUNG AC036TXADKC - NOTE - 2

Connecting the outdoor-to-indoor power cable and the communication cable

1-phaseFor connecting the power and communication cables Indoor Unit Outdoor Unit 1(L) 2(N) L N Cable tie Communication cable Outdoor-to-indoor power cable Main power cable

SAMSUNG AC036TXADKC - Connecting the outdoor-to-indoor power cable and the communication cable - 2

NOTE

- Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely.

- Ground wire for the indoor unit and outdoor unit connection cable must be clamped to a soft copper tin-plated eyelet terminal with M4 screw hole(NOT SUPPLIED WITH UNIT ACCESSORIES).

Outdoor-to-indoor power terminal specifications

  • Connect the cables to the terminal board using the compressed ring terminal.
  • Cover a solderless ring terminal and a connector part of the power cable and then connect it.

Rf d2 Silver solder B F E L d1 D t

Nominal dimensions for cable (mm2)Nominal dimensions for screw (mm)BDd1E
Standard dimension (mm)Allowance (mm)Standard dimension (mm)Allowance (mm)Standard dimension (mm)Allowance (mm)Min. (mm)Min. (mm)Max. (mm)Standard dimension (mm)Allowance (mm)Min. (mm)
4/649.5±0.2 5.6+0.3 -0.23.4 ±0.26.0520+0.2 0.4.3 0.9
815.0928.58.4+0.4 0
10815.0±0.27.1+0.3 -0.24.5±0.27.9930.08.4+0.4 01.15
16816.0±0.29.0+0.3 -0.25.8±0.29.51333.08.4+0.4 01.45
25812.0±0.311.5+0.5 -0.27.7±0.211.01534.08.4+0.4 01.7
816.5138.4
35816.0±0.313.3+0.5 -0.29.4±0.212.51338.0 8.4+0.4 01.8
822.01343.08.4
50822.0±0.313.5+0.5 -0.211.4±0.317.51450.08.4+0.4 01.8
70824.0±0.417.5+0.5 -0.413.3±0.418.52051.08.4+0.4 02.0
  • Connect the rated cables only.
  • Connect using a driver which is able to apply the rated torque to the screws.
  • If the terminal is loose, fire may occur caused by arc. If the terminal is connected too firmly, the terminal may be damaged.
Tightening torque (N·m)
M40.8 to 1.2
M52.0 to 3.0

- 1 N·m = 10 kg·fcm

CAUTION

  • When connecting cables, you can connect the cables to the electrical part or connect them through the holes below depending on the spot.
  • Connect the communication cable between the indoor and outdoor units through a conduit to protect against external forces, and feed the conduit through the wall together with refrigerant piping.
  • Remove all burrs at the edge of the knock-out hole and secure the cable to the outdoor knock-out using lining and bushing with an electrical insulation such as rubber and so on.
  • Must keep the cable in a protection tube.
  • Keep distances of 50mm or more between power cable and communication cable.
  • When the cables are connected through the hole, remove the Plate bottom.

Outdoor-to-indoor power and communication cables specifications

Indoor power supply
Power supply Max/Min (V) Indoorpower cable
1ø, 220 V, 60 Hz ±10% 1.5 mm2↑, 3wires
Communication cable
0.75 to 1.5 mm2, 2 wires
  • Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
  • When installing the indoor unit in a computer room or net work room, use the double shielded (tape aluminium / polyester braid + copper) cable of FROHH2R type.

Cross-sectional diagram of a cable with visible internal bands and insulation (no text or symbols)

Step 4 Optional: Extending the power cable

1 Prepare the following tools.

Tools Spec Shape
Crimping pliers MH-14SAMSUNG AC036TXADKC - Step 4 Optional: Extending the power cable - 1
Connection sleeve (mm)20x∅6.5 (HxOD)SAMSUNG AC036TXADKC - Step 4 Optional: Extending the power cable - 2
Insulation tapeWidth 19 mmSAMSUNG AC036TXADKC - Step 4 Optional: Extending the power cable - 3
Contraction tube (mm)70x∅8.0 (LxOD)SAMSUNG AC036TXADKC - Step 4 Optional: Extending the power cable - 4

2 As shown in the figure, peel off the shields from the rubber and wire of the power cable.

- Peel off 20 mm of cable shields from the pre-installed tube.

Power cable (Unit: mm) 20 20 60 120 180 120 60 20 20 20 Pre-installed tube for the power cable

CAUTION

  • For information about the power cable specifications for indoor and outdoor units, refer to the installation manual. • After peeling off cable wires from the pre-installed tube, insert a contraction tube.

3 Insert both sides of core wire of the power cable into the connection sleeve.

  • Method1: Push the core wire into the sleeve from both sides.
  • Method 2: Twist the wire cores together and push it into the sleeve.

Method 1 Connection sleeve Method 2 Connection sleeve

CAUTION

- If cable wires are connected without using connecting sleeves, their contact area becomes reduced, or corrosion develops on the outer surfaces of the wires (copper wires) over a long time. This may cause an increase of resistance (reduction of passing current) and consequently may result in a fire.

4 Using a crimping tool, compress the two points and flip it over and compress another two points in the same location.

• The compression dimension should be 8.0.

Compression dimension 8

• After compressing it, pull both sides of the wire to make sure it is firmly pressed.

Method1 Method 2 Compress it 4 times. Compress it 4 times.5 mm

5 mm

5 Apply heat to the contraction tube to contract it.

Method 1 Method 2 Contraction tube Contraction tubeSAMSUNG AC036TXADKC - CAUTION - 4

SAMSUNG AC036TXADKC - CAUTION - 5

6 Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape.

Method 1 Method 2 Insulation tape Insulation tape40 mm

SAMSUNG AC036TXADKC - CAUTION - 7

7 After tube contraction work is completed, wrap it with the insulation tape to finish.

Three or more layers of insulation are required.

Method 1 Insulation tape Method 2 Insulation tape

SAMSUNG AC036TXADKC - CAUTION - 9

CAUTION

  • Make sure that the connection parts are not exposed to outside.
  • Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same level of withstand voltage with the power cable. (Comply with the local regulations on extensions.)

SAMSUNG AC036TXADKC - CAUTION - 1

WARNING

- In case of extending the electric wire, please DO NOT use a round-shaped Pressing socket.

– Incomplete wire connections can cause electric shock or a fire.

Pure electrical circuit symbol for a light bulb, no text or labels present

Step 5 Connecting the refrigerant pipe

ItemsOutdoor unit modelsMain pipe (L1)Max. height difference between outdoor and indoor units (h1)
Maximum allowable lengthAC024TXADKC 50 30
AC036TXADKC 50 30
AC048TXADKC 75 30

graph LR A["Outdoor Tank"] --> B["Indoor Unit"] B --> C["Indoor"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333

• Temper grade and minimum thickness of the refrigerant pipe

Outer diameter [mm]Minimum thickness [mm]Temper grade
ø 6.35 0.7C1220T-O
ø 9.52 0.7
ø 12.70 0.8
ø 15.88 1.0
ø 15.88 0.8C1220T-1/2H OR C1220T-H
ø 19.05 0.9
ø 22.23 0.9

SAMSUNG AC036TXADKC - WARNING - 3

CAUTION

- Be sure to use C1220T-1/2H (Semi-hard) pipe for more than ∅19.05 mm. If you use C1220T-O (Soft) pipe for ∅19.05 mm, the pipe may be broken, which can result in an injury.

Make at least one round: It will reduce noise and vibration Block the part.

- The appearance of the unit may differ from the diagram depending on the model.

SAMSUNG AC036TXADKC - CAUTION - 2

CAUTION

Pipe outlet

  • Cut the pipe outlet to the exact pipe size. In addition, remove foreign substances and burrs around the outlet.
  • Perform cutting with only a cutter (e.g., nipper) and never tap with a hammer near the pipe outlet. Otherwise, it may cause product damage such as warping of the cabinet. • After connecting the pipes with the pipe outlet, plug the space around the pipes. • After connecting the pipes, proceed exactly as directed in the guide to prevent interference with the internal parts.
  • Tighten the nuts to the specified torques. If overtightened, the nuts could be broken, causing refrigerant to leak.
  • Protect or enclose refrigerant tubing to avoid mechanical damage.
  • After installing pipes, block the unused knock hole to prevent small animals from entering. However, the radiant heat hole (A) should be able to intake air.

Step 6 Optional: Cutting and flaring the pipes

1. Make sure that you have the required tools available (pipe cutter, reamer, flaring tool, and pipe holder). 2. If you wish to shorten the pipes, cut them with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe. Refer to the illustrations below for examples of edges cut correctly and incorrectly.

Pipe cutter 90° Pipe Oblique Rough Burr

3. To prevent any gas from leaking out, remove all burrs at the cut edge of the pipe using a reamer. 4. Slide a flare nut onto the pipe and modify the flare.

D Pipe Flare 90° ±2° 45° ±2° R 0.4 to 0.8 mm D Flare

Outer diameter (D)Depth (A)Flare dimension (L)
ø 6.35 mm 1.3 mm8.7 to 9.1 mm
ø 9.52 mm 1.8 mm12.8 to 13.2 mm
ø 12.70 mm 2.0 mm16.2 to 16.6 mm
ø 15.88 mm 2.2 mm19.3 to 19.7 mm
ø 19.05 mm 2.2 mm23.6 to 24.0 mm

5. Check that the flaring is correct, referring to the illustrations below for examples of incorrect flaring.

1 2 3 Correct Inclined Damaged Surface Cracked Uneven Thickness

Step 7 Installing oil traps

Check the following list and install an oil trap.

  • Based on cooling operation, install it on the gas side pipe only.
  • Install the oil trap only in between the outdoor unit and the first branch joint and it should be installed at every 10 m.
  • Radius of curvature (R) on the oil trap are as follows;
Pipe diameter (D, mm)12.7015.8819.0522.2325.4028.6031.75
Radius of curvature (R, mm)25 and over32 and over38 and over41 and over51 and over57 and over60 and over

• Height of the oil trap H: 4R ≤ H ≤ 6R - When the indoor unit is installed at a higher place than the outdoor unit

Outdoor Unit Indoor Unit Oil trap (Install it at every 10 m) R H

SAMSUNG AC036TXADKC - Step 7 Installing oil traps - 2

CAUTION

  • If the pipes require brazing ensure that OFN(Oxygen Free Nitrogen) is flowing through the system.
  • Nitrogen blowing pressure range is 0.02 to 0.05 MPa.

Step 8 Connecting up and removing air in the circuit

SAMSUNG AC036TXADKC - Step 8 Connecting up and removing air in the circuit - 1

CAUTION

- When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

The air in the indoor unit and in the pipe must be evacuated. If air remains in the refrigerant pipes, it will affect the compressor either reduce cooling capacity or lead to a malfunction. Refrigerant for air purging is not charged in the outdoor unit. Use Vacuum Pump as shown at the right figure.

1 Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut. 2 Referring to the illustration below, tighten the flare nut on section D first manually and then with a torque wrench, applying the following torque.

Outdoor Unit A (Gas) B (Liquid) C D

Outer Diameter (mm) Torque (N·m)
ø 6.35 14 to 18
ø 9.52 34 to 42
ø 12.70 49 to 61
ø 15.88 68 to 82
ø 19.05 100 to 120

3 Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port as shown at the figure.

SAMSUNG AC036TXADKC - CAUTION - 2

CAUTION

  • The designs and shape are subject to change according to the model. 4 Open the valve of the low pressure side(A) of manifold gauge anticlockwise.

AC024TXADKC Vacuum pump

AC036/048TXADKC Outdoor Unit Vacuum pump A (Gas) B (liquid)

5 Purge the air from the system using vacuum pump for about 10 minutes.

  • Close the valve on the low-pressure side of the manifold gauge by turning it clockwise.
  • Ensure that the pressure gauge reads -0.1 MPa (-76 cmHg) after about 10 minutes. This step is crucial to prevent gas leaks.
  • Turn off the vacuum pump.
  • Disconnect the hose from the low-pressure side of the manifold gauge.

6 Open the stop valves on both the liquid and gas sides.

7 Install the valve stem nuts and the service port cap onto the valve, and tighten them to a torque of 183 kgf·cm using a torque wrench.

8 Check for gas leaks.

- At this point, especially check for gas leaks from the 3-way valve's stem nuts (A port) and the service port cap.

SAMSUNG AC036TXADKC - CAUTION - 3

CAUTION

  • Connect the indoor and outdoor units using pipes with flared connections (not supplied). For the lines, use insulated, unwelded, degreased, and deoxidized copper pipe (Cu DHP type to ISO 1337 or UNI EN 12735-1), suitable for operating pressures of at least 4200 kPa and a burst pressure of at least 20700 kPa. Copper pipe intended for hydro-sanitary applications is completely unsuitable.
  • For sizing and limits (height difference, line length, max. bends, refrigerant charge, etc.), refer to the "Connecting refrigerant pipe section".

Step 9 Adding refrigerant (R-410A)

- The outdoor unit is pre-charged with enough refrigerant for standard piping. Therefore, additional refrigerant must be added if the piping is extended. This operation should only be performed by a qualified refrigeration specialist. To determine the amount of refrigerant to add, see "Calculating the quantity of refrigerant to add" on page 20.

1 Check that the stop valve is fully closed. 2 AC024TXADKC: Charge the refrigerant through the service port of the gas stop valve. AC036/048TXADKC: Charge the refrigerant through the service port of the liquid stop valve.

SAMSUNG AC036TXADKC - Step 9 Adding refrigerant (R-410A) - 1

NOTE

- AC036/048TXADKC: Do not charge the refrigerant through the service port of the gas stop valve.

3 AC024TXADKC: Charge the refrigerant by taking the following steps:

AC036/048TXADKC: If you have any difficulty charging the refrigerant as described in the steps above, take the following steps:

a. Open the liquid stop valve and gas stop valve. b. Operate the air conditioner by pressing the K2 button on the outdoor unit PCB. c. After about 30 minutes, charge the refrigerant through the service port of the gas stop valve.

AC024TXADKC Indoor Unit Balance Ref Vacuum Pump Gas side stop valve (service port) Liquid side stop valve (Non-service port)

AC036/048TXADKC Indoor Unit Liquid side stop valve(service port) Gas side stop valve(service port) Outdoor Unit Balance Ref Vacuum Pump

Calculating the quantity of refrigerant to add

The quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor unit situation before adding refrigerant. This operation can only be performed by a qualified refrigeration specialist.

Single installation outdoor unit

Interconnection pipe length (m)AC024TX ADKCAC036TX ADKCAC048TX ADKC
0~30+10g/m over 5m+50g/m over 30m+50g/m over 30m
30~40
40~50
50~60
60~70
70~75

Step 10: Performing the gas leak test

LEAK TEST WITH NITROGEN (before opening valves)

In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-410A, it is the responsibility of the installer to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 0.2MPa, less than 4MPa (gauge).

LEAK TEST WITH R-410A (after opening valves)

Before opening valves, discharge all the nitrogen into the system and create vacuum. After opening valves check leaks using a leak detector for refrigerant R-410A. Once you have completed all the connections, check for possible leaks using leak detector specifically designed for HFC refrigerants.

- AC024TXADKC

A (Gas) B (liquid)

- AC036/048TXADKC

A (Gas) B (liquid)

- The designs and shape are subject to change according to the model.

Step 11 Connecting the drain hose to the outdoor unit

1. Make space more than 80 mm between the bottom of the outdoor unit and the ground for installation of the drain hose, as shown in the figure. 2. Insert the drain plug into the hole on the underside of the outdoor unit. 3. Connect the drain hose to the drain plug. 4. Ensure that the drained water runs off correctly and safely.

80 mm 13 mm

5. Be sure to plug the rest of the drain holes not connected with drain plugs using drain caps.

AC024TXADKC Drain cap (4 EA) Drain plug (1 EA)

AC036/048TXADKC Drain cap (3 EA) Drain plug (1 EA)

  • When installing the product, make sure that the rack is not placed under the drain hole.
  • If the product is installed in a region of heavy snow, allow enough separation distance between the product and the ground.

Step 12 Insulating the refrigerant pipes

Once you have checked that there are no leaks in the system, you can insulate the piping and hose.

1. To avoid condensation problems, place an insulator around each refrigerant pipe.

No gap NBR

SAMSUNG AC036TXADKC - Step 12 Insulating the refrigerant pipes - 2

NOTE

- When insulating the pipe, be sure to overlap the insulation.

- The insulation has to be produced in full compliance with European regulation reg. EEC/EU 2037/2000, which requires the use of sheath insulation forms without using CFC and HCFC gases for health and the environment.

SAMSUNG AC036TXADKC - NOTE - 1

CAUTION

- When insulating the pipe, use a non-slit insulator.

2. Select the insulation of the refrigerant pipe.

• Insulate the gas side and liquid side pipe, referring to the thickness according to the pipe size. - Less than indoor temperature of 30°C and humidity of 85% is the standard condition. If installing in a high humidity condition, use one grade thicker insulator by referring to the table below. If installing in unfavorable conditions, use a thicker one. - Insulator's heat-resistance temperature should be more than 120°C.

PipePipe size (mm)Insulation Type (Heating/Cooling)Remarks
Standard [Less than 30°C, 85%]High humidity [over 30°C, 85%]
EPDM, NBR (mm)
Liquid pipe∅6.35 ~ ∅9.529 t 9 tInternal temperature is higher than 120°C
∅12.7 ~ ∅19.0513 t 13 t
Gas pipe∅6.35 13 t19 t
∅9.52 ~ ∅19.0519 t 25 t

- When installing insulation in places and conditions below, use the same insulation that is used for high humidity conditions.

– High humidity places such as shoreline, hot spring, near lake or river, and ridge (when the part of the building is covered by earth and sand.)

– Restaurant ceiling, sauna, swimming pool etc. - - The ceiling frequently exposed to moisture and cooling is not covered. – e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently. - The place where the pipe is installed is highly humid due to the lack of ventilation system.

Step 13 Checking the earthing

If the power distribution circuit does not have a earthing or the earthing does not comply with specifications, an earthing electrode must be installed. The corresponding accessories are not supplied with the air conditioner.

1 Select an earthing electrode that complies with the specifications given in the illustration. 2 Connect the flexible hose to the flexible hose port.

  • In damp hard soil rather than loose sandy or gravel soil that has a higher earthing resistance.
  • Away from underground structures or facilities, such as gas pipes, water pipes, telephone lines and underground cables.
  • At least two metres away from a lightening conductor earthing electrode and its cable.

SAMSUNG AC036TXADKC - Step 13 Checking the earthing - 1

NOTE

- The earthing wire for the telephone line cannot be used to ground the air conditioner.

Carbon plastic Steel core Terminal M4 To grounding screw PVC-insulated green/yellow wire 50 cm 30 cm

3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit. 4 Install a green/yellow coloured earthing wire:

  • If the earthing wire is too short, connect an extension lead in a mechanical way and wrap it with insulating tape (do not bury the connection).
  • Secure the earthing wire in position with staples.

SAMSUNG AC036TXADKC - NOTE - 2

NOTE

  • If the earthing electrode is installed in an area with heavy traffic, its wire must be connected securely. 5 Carefully check the installation by measuring the earthing resistance with an earth resistance tester. If the resistance is above the required level, drive the electrode deeper into the ground or increase the number of earthing electrodes. 6 Connect the earthing wire to the electrical component box inside the outdoor unit.

Step 14 Performing final check and trial operation

1 Check the power supply between the outdoor unit and the auxiliary circuit breaker.

• 1 phase power supply : L, N • 3 phase power supply : R, S, T, N

2 Check the indoor unit.

a Check that you have connected the power and communication cables correctly. (If the power cable and communication cables are mixed up or connected incorrectly, the PCB will be damaged.) b Check that the thermistor sensor, drain pump/hose, and display are connected correctly.

3 Press K2 on the outdoor unit PCB to run the test mode and stop.

Key Push type ModeDisplay
SEG 1SEG 2SEG 3SEG 4
K2 Short1st Cooling testF288
2nd Inverter checkF488
3rdPump downF688
4thStop8888
K3 Short1stReset Release Eco mode8888

- AC024TXADKC

8.8.8.0 1 T 1 T 1 T 1 T

- AC036/048TXADKC

8.0 8.0 K1 K2 K3 K4

4 After 12 minutes of operation, check the discharged air temperature of the indoor unit.

- Cooling mode (indoor unit check) → Inlet air temp. - Outlet air temp.: From 10°C to 12°C

5 How to reset the power supply of the outdoor unit and deactivate the eco mode (standby mode):

• Outdoor unit types A, B : Refer to Outdoor unit dimensions on page 6.

- Press K3 button for over 1 second to reset the power supply of the outdoor unit and deactivate the eco mode (standby mode).

※ Eco mode : Standby for minimizing power consumption

6 View mode: When the K4 switch is pressed, you can see information about our system state as below.

K4 short pushDisplay contents SEG1 SEG2 SEG3 SEG4 Unit
1 Order frequency 1 Hundreds digit Tens digitUnits digit Hz
2Current frequency2Hundreds digitTens digitUnits digitHz
3The number of preset indoor units3Hundreds digitTens digitUnits digitEA
4Ambient temperature sensor4+/-Tens digitUnits digit°C
5Compressor discharge sensor5Hundreds digitTens digitUnits digit°C
6Eva-Mid sensor6+/-Tens digitUnits digit°C
7Condensor sensor7+/-Tens digitUnits digit°C
8Current8Tens digitUnits digitThe first place of decimalsA
9Outdoor fan RPM9Thousands digitHundreds digitTens digitrpm
10Target discharge temperatureAHundreds digitTens digitUnits digit°C
11EEVBHundreds digitTens digitUnits digitstep
12The capacity sum of indoor unitsCTens digitUnit digitThe first place of decimalskW
13Protective controlD0: Cooling1: HeatingProtective control0: No Protective control1: Freezing2: Non-stop defrosting3: Over-load4: Discharge5: Total electric currentFrequency status0: Normal1: Hold2: Down3: Up_limit4: Down_limit-
14IPM temperatureEHundreds digitTens digitUnits digit-
15The number of connected indoor unitsFHundreds digitTens digitUnits digitEA
16View mode endBLANKBLANKBLANKBLANK-
Display contentsSEG1SEG2SEG3SEG4
K4 long push-Main micom versionYear (Dec)Month (Hex)Date (Tens digit)Date (Units digit)
After short push 1Inverter micom versionYear (Dec)Month (Hex)Date (Tens digit)Date (Units digit)
After short push 2E2P versionYear (Dec)Month (Hex)Date (Tens digit)Date (Units digit)
After short push 3Page 1 - AUTOPage 2 - (SEG1,2 - Indoor : "A","0") (SEG3,4 - Address : ex)00 )
After short push 4Page 1 - MANUPage 2 - (SEG1,2 - Indoor : "A","0") (SEG3,4 - Address : ex)00 )

- Long push K4 (Main micom ver.) → short push 1 more (Inv. micom ver.) → short push 1 more (E2P.ver.) → short push 1 more (Automatic address) → short push 1 more (Manual address) → short push 1 more (Main micom ver.) → ...... → Long push K4 (View mode end)

7 Setting outdoor unit option switch and address manually

a Setting the option

- Press and hold K2 to enter the option setting. (Only available when the operation is stopped) – If you enter the option setting, display will show the following.

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 3

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 4

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 5

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 6

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 7

  • Seg 1 and Seg 2 will display the number for selected option.
  • Seg 3 and Seg 4 will display the number for set value of the selected option.

- If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change the function for the selected option.

Example)

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 8

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 9

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 10

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 11

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 12

- If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change the function for the selected option.

Example)

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 13

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 14

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 15

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 16

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 17

- After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited value of the option will be saved when entire segments blinks and tracking mode begins.

Option itemInput unitSEG1SEG2SEG3SEG4Function
Channel addressMain 00AUAutomatic setting (Factory default)
00~15Manual setting
Snow accumulation prevention controlMain 0100Disabled (Factory default)
01Enabled
Step for Silence modeMain 0200Disabled (Factory default)
01S
02St ep2
03St ep3
Type of Silence modeMain 0300Automatic Silence mode (Factory default)
01Manual Silence mode

SAMSUNG AC036TXADKC - Step 14 Performing final check and trial operation - 18

CAUTION

  • Edited option will not be saved if you do not end the option setting as explained in above instruction. ※ While you are setting the option, you may press and hold the K1 button to reset the value to previous setting. ※ If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting mode.

- If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored setting is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress, setting will be saved.

Pumping down refrigerant

SAMSUNG AC036TXADKC - Pumping down refrigerant - 1

WARNING

- After installing the product, be sure to perform leak tests on the piping connections. After pumping down refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the connected pipes.

- Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected or incorrectly connected pipe. Failure to do so may cause air to flow into the compressor and too high a pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.

Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit. This operation must be carried out before disconnecting the refrigerant pipe in order to avoid refrigerant loss to the atmosphere.

1 Turn the system on in cooling with fan operating at high velocity and then let the compressor run for more than 5 minutes. (Compressor will immediately start, provided 3 minutes have elapsed since the last stop.) 2 Release the valve caps on High and Low pressure side. 3 Use L-wrench to close the valve on the high pressure side. 4 After approximately 2 minutes, close the valve on the low pressure side. 5 Stop operation of the air conditioner by pressing the (Power) button on the indoor unit or remote control. 6 Disconnect the pipes. - AC024TXADKC

A (Gas) B (liquid)

- AC036/048TXADKC

B (liquid) A (Gas)

Relocating the indoor and outdoor units

1 Pump down refrigerant. See Pumping down refrigerant on page 25. 2 Remove the power cord. 3 Disconnect the assembly cable from the indoor and outdoor units. 4 Remove the flare nuts connecting the indoor units and the pipes. At this time, cover the pipes of the indoor unit and the other pipes using a cap or vinyl plug to avoid foreign material entering. 5 Disconnect the pipes connected to the outdoor units. At this time, cover the valve of the outdoor units and the other pipes using a cap or vinyl plug to avoid foreign material entering.

Note: Make sure you do not bend the connection pipes in the middle and store together with the cables.

6 Move the indoor and outdoor units to a new location. 7 Remove the mounting plate for the indoor unit and move it to a new location.

Using the stop valve

Opening the stop valve

1 Open the cap and turn the stop valve anticlockwise by using a hexagonal wrench. 2 Turn it until the axis is stopped.

Tightening torque for charging port cap (Refer to the table) Charging Core R-22: Thread of the screw - 7/16-20UNF R-410A: Thread of the screw - 1/2-20UNF Spindle Tightening torque for body cap (Refer to the table)

3 Tighten the cap securely.

Outer Diameter (mm)Tightening torque
Body cap (N·m)Charging port cap (N·m)
∅6.3520 to 2510 to 12
∅9.5220 to 25
∅12.7025 to 30
∅15.8830 to 35
Over ∅19.0535 to 40

(1 N·m = 10 kgf·cm)

SAMSUNG AC036TXADKC - Opening the stop valve - 2

NOTE

  • Do not apply excessive force to the stop valve and always use special tools. Otherwise, the valve box can be damaged and the back sheet can leak.
  • If the watertight sheet leaks, turn the axis back by half, tighten the valve box, then check the leakage again. If there is no leakage any more, tighten the axis entirely.

Closing the stop valve

1. Remove the cap. 2. Turn the stop valve clockwise using a hexagonal wrench. 3. Tighten the axis until the valve reaches the sealing point. 4. Tighten the cap securely.

SAMSUNG AC036TXADKC - Closing the stop valve - 1

CAUTION

  • When using the service port, always use a charging hose as well.
  • Check for refrigerant gas leakage after tightening the cap.
  • Always use a spanner and wrench when opening or tightening the stop valve.

Troubleshooting

The table below lists the self-diagnostic routines. For some error codes, you must contact an authorized service center. If an error occurs during operation, it is displayed on the outdoor unit PCB LED, on both the MAIN PCB and the INVERTER PCB.

No.Error CodeMeaning Remarks
1E108Error due to duplicated communication address Check on repeated indoor unit main address
2E 1Error on room temperature sensor of indoor unit (Short or Open)Indoor unit Room Thermistor Open/Short
3E122Error on EVA IN sensor of indoor unit (Short or Open)Indoor unit EVA_IN Thermistor Open/Short
4E 1Error on EVA OUT sensor of indoor unit (Short or Open)Indoor unit EVA_OUT Thermistor Open/Short
5E 15 3 Error on float switch (2nd detection)Indoor unit Float Switch Open/Short Drain Pump operation Check
6E154Fan error Check on indoor unit indoor Fan operation
7E198Error on thermal fuse of indoor unit (Open)Thermal Fuse Open Check of indoor unit Terminal Block
8E 20Communication error between the indoor unit and outdoor unit (Pre-tracking failure or when the actual number of indoor units are different from the indoor unit quantity setting on the outdoor unit)Error due to communication tracking failure after initial power is supplied (The error occurs regardless of the number of units.)Check indoor quantity setting in outdoor
9E202Communication error between indoor unit and outdoor unit (When there is no response from indoor units after tracking is completed)Check electrical connection and setting between indoor unit and outdoor unit
10E203Communication error between the outdoor unit and main micom (For PF #4 to #6 controllers, error will be determined from the time when the compressor is turned on.)Check electrical connection and setting between outdoor unit MAIN PBA - INVERTER PBA
11E221Error on outdoor temperature sensor (Short or Open)Check Outdoor sensor Open / Short
12E231Error on outdoor COND OUT sensor (Short or Open)Check Cond-Out sensor Open / Short
13E251Error on discharge temperature sensor of compressor 1 (Short or Open)Check Discharge sensor Open / Short
14E320Error on OLP sensor (Short or Open)Check OLP sensor Open / Short
15E403Compressor down due to freeze protection controlCheck Outdoor Cond.
16E404System stop due to overload protection controlCheck Comp. when it starts
17E416System stop due to discharge temperature -
18E422Blockage detected on high pressure pipeCheck if the service valve is openCheck for refrigerant leakage (pipe connections, heat exchanger) and charge refrigerant if necessaryCheck if there's any blockage on the refrigerant cycle (indoor unit/outdoor unit)Check if additional refrigerant has been added after pipe extension
19E425Reverse phase or open phaseCheck whether 3 phase is reversed or opened.
20E440Heating operation restricted at outdoor temperature over Theat_high value (default:30°C)Check the range of temperature limited for heating operationCheck the outdoor temperature sensor
21E441Cooling operation restricted at outdoor temperature below Tcool_low value (default:0°C)1. Check the range of temperature limited for cooling operation2. Check the outdoor temperature sensor
22E458Fan speed error FAN1 ERROR
23E461Error due to operation failure of inverter compressor -
24E462System stop due to full current control -
25E463Over current trip / PFC over current error Check OLP sensor
26E464IPM Over Current(O.C)1. Check if the service valve is open2. Check the state of refrigerant3. Check if connecting wire and the pipe are OK4. Check the compressor
27E465Comp. Over load error -
28E466DC-Link voltage under/over error Check AC Power and DC Link Voltage
29E467Error due to abnormal rotation of the compressor or unconnected wire of compressorCheck Comp wire
30E468Error on current sensor (Short or Open)Check Outdoor Inverter PBA.
31E469Error on DC-Link voltage sensor (Short or Open)-
32E470Outdoor unit EEPROM Read/Write error (Option)Check Outdoor EEPROM Data
33E471Outdoor unit EEPROM Read/Write error (H/W)Check Outdoor EEPROM PBA
34E474Error on IPM Heat Sink sensor of inverter 1 (Short or Open)Check Outdoor Inverter PBA.
35E475Error on inverter fan 2FAN2 ERROR
36E483Overvoltage of H/W detect DC linkCheck AC Power
37E484PFC Overload (Over current) ErrorCheck Outdoor Inverter PBA.
38E485Error on input current sensor of inverter1 (Short or Open)Check Outdoor EEPROM PBA
39E488Inverter input voltage sensor errorCheck Outdoor Inverter PBA
40E500IPM over heat error on inverter 1Check Outdoor Inverter PBA.
41E508Smart install is not installed -
42E554Gas leak detectedCheck the refrigerant
43E556Error due to mismatching capacity of indoor and outdoor unitCheck the indoor and outdoor unit capacity
44E557DPM remote controller option errorCheck the indoor option code
45E563Error due to mismatching indoor and outdoor unitCheck the outdoor EEPROM data and indoor option code
46E590Inverter EEPROM Checksum error-
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : SAMSUNG

Model : AC036TXADKC

Category : Air conditioner