ADR-D 230 D63 - Energy consumption meter Vemer - Free user manual and instructions
Find the device manual for free ADR-D 230 D63 Vemer in PDF.
| Product Type | Energy Consumption Meter |
| Brand | Vemer |
| Model | ADR-D 230 D63 |
| Mounting | DIN Rail (4 modules) |
| Dimensions (W x H x D) | 70 mm x 90 mm x 65 mm |
| Weight | Approx. 200 g |
| Rated Voltage | 230 V AC, 50 Hz |
| Rated Current | 63 A (max) |
| Measurement Type | Single-phase active energy (kWh) |
| Accuracy Class | Class B (per EN 50470) |
| Display | LCD, 6+1 digits |
| Pulse Output | Yes (S0, 1000 imp/kWh) |
| Operating Temperature | -25°C to +55°C |
| Storage Temperature | -35°C to +70°C |
| Humidity Range | Up to 95% non-condensing |
| Protection Class | IP20 (front), IP50 (terminal block) |
| Main Functions | Measures active energy, instantaneous power, total consumption, partial consumption |
| Maintenance | Dry cloth cleaning; no user-serviceable parts |
| Safety Standards | IEC 61010, IEC 62053-21 |
| Spare Parts / Reparability | Contact Vemer for replacement; device is not user-repairable |
Frequently Asked Questions - ADR-D 230 D63 Vemer
User questions about ADR-D 230 D63 Vemer
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Energy consumption meter in PDF format for free! Find your manual ADR-D 230 D63 - Vemer and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ADR-D 230 D63 by Vemer.
USER MANUAL ADR-D 230 D63 Vemer
Read all instructions carefully
■ Single-phase system analyser for TRMS (True Root Mean Squared) values. Pulse output for direct connection of a current lead with I_MAX = 63A . Connection is effected by directly inserting the power lead vertically into the housing.
SAFETY INSTRUCTIONS
To guarantee correct installation, observe the following instructions: 1) The instrument must be installed by a qualified person 2) The instrument must be installed in an electrical panel which, after installation.
3) The instrument must be installed in an electrical panel unit, after installation, leaves terminals inaccessible 3) The building in which the instrument is installed must have an electrical system including a switch or a circuit breaker this must be near the device and in a position that can be easily reached by operators 4) A protection device against over-currents must be installed in the electrical system upstream of the instrument
5) Connect the instrument as shown in the diagrams of this manual
6) Before making contact with terminals, ensure that leads to be connected to the instrument are not live
7) Do not power or connect the instrument if any part of it is damaged
Note: The network analysers in the ADR-D 230 D63 series are aimed for use in places with overvoltage category III and pollution degree 2 to EN 61010-1.
Code Model Description
VE035200 ADR-D 230 D63 Single-phase network analyser
TECHNICAL SPECIFICATIONS
- Power supply/Input voltage: 230V AC (-15%/+10%) 50/60Hz - Input Current: I s = 10A; I max = 63A by direct connection - Galvanic insulation between voltage and current inputs - Maximum cross-section of the current lead: 25 mm ^3 - Maximum diameter of the perforation for the current lead: 12.5 mm - Maximum consumption (device only): voltage circuit <2.5 VA power circuit <2.5 VA power supply < A VA
• Quantities measured: Voltage (Page 1)
Current (Page 2)
Active power (Page 3)
Power factor (Page 4)
Frequency (Page 5)
• Operating temperature: -10 ÷ +45^
- Operating temperature: -10 ± +45 °C - Relative humidity: 10% ÷ 90% non-condensing
- Storage temperature: -20 ÷ +60^ C
• Signalling leds: green = power on
red = flashing at frequency 10Wh
- Optoinsulated pulse output: pulse duration = 100 ms ± 15%
pulse voltage = 9 ± 24 V DC (± 10%) maximum output current = 20 mA
• Display: LCD display, 7 + 5-digits
• Enclosure: 3 DIN, RAL 7035 gray
• Protection rating: IP20/IP51 on the front
RESOLUTION AND ACCURACY
• Alternating voltage: Maximum reading: 265.0V
Resolution: 0,1
Accuracy: ± IV ± 1 digit
• Alternating current: Maximum reading: 67.00A
Minimum reading: 0.10A
Resolution: 0,01A
Accuracy: ± 0,5% full scale ± 1 digit (full scale: 63A)
• Active power: Resolution: 0.01kW
Accuracy: +1% full scale + 1 digit (full scale: 100kW)
• Power factor: Resolution: 0.01
Accuracy: ± 1% ± 1 digit
• Frequency: Resolution: 0,1Hz
Accuracy: ± 0,1Hz (from 45Hz to 65Hz)
• Total active energy: Resolution: 0,1kWh (full scale: 999999,9 kWh)
Resolution: 1kWh (full scale: 999) Accuracy class 1 to EN 62053-21
- Partial active energy: Resolution: 0,01kWh (full scale: 999,99 kWh)
Resolution: 0,1kWh (full scale: 9999,9 kWh)
Accuracy: class 1 to EN 62053-21
DEVICE DESCRIPTION
① Backlit LCD display to read the values measured
② Open collector pulse output: 1 pulse every 0,1kWh count
③ Perforation for direct connection of current leads
④ Green LED: ON when the instrument is powered
⑤ Red LED: every flash corresponds to an energy count of 10Wh ⑥ Page scroll button, zeroing of partial meter, parameter set-up
OPERATION
The values measured are read over 6 pages to be scrolled using the SEL button.
| Page 1 | 1076843^km | Total active energy meter |
| 2302^v | Alternating voltage value | |
| Page 2 | 1076843^km | Total active energy meter |
| 805^A | Alternating current value |
| 1076843 ^mWh | Total active energy meter |
| 245 ^mm | Active power value |
| 1076843 kWh | ← Total active energy meter |
| 087 PF | ← Power factor value |
| Page 5 | FrE9500 | ← Frequency value |
| 1076843 kWh | ← Total active energy meter |
| 16392 kWh | ← Partial active energy meter |
To access the 2 pages reading only active energy counts, press the SEL button again.
| Page 7 | 1076843 ^thm | ← Non-zeroable total active energy meter |
| Page 8 | 16392 ^thm | ← Zeroable partial active energy meter |
The partial meter is automatically zeroed when the scale range is overrun. To set the meter to
zero manually, hold the "SEL" key down for more than 3 seconds
To view the first page again, press the SEL key once more.
BACKLIGHTING
The device's display backlights when the SEL key is pressed. it stays on for 30 seconds after the
last key is pressed.
To change this betting go to page 1 and hold down the BUB key for at least 6 seconds

Backlighting status (ON / OFF)
OPERATING MESSAGES
PHASE ERROR
On startup the device checks the connection of voltage terminals and the direction of the current lead. In case of error the phase error page will be displayed for 3 minutes. The triangular LED on the left will flash and the red signaling LED will be ON.
To resume correct operation, turn the device off, invert voltage connections or current lead direction and turn it back on.
Error conditions occurring during normal operation are indicated by the flashing of the triangu

← Error reading on start-up
lar LED on the left and the lighting up of the red signaling LED. Voltage, current and frequency values are nonetheless read correctly. As far the remaining nodes, average counts will not increase, the power factor will be found not to
As for the remaining pages, energy counts will not increase, the power factor will be force-set to

← Voltage value with Phase error LED
1 and the active power value to 0.
OVERFLOW ERROR
When the voltage or current reading range is overrun, the relevant field will flash dots and the total energy count will be read.
Voltage or current overflow error is indicated on the other pages too. in this case the values

Voltage page for V > 265V
measured will flash.
REFERENCE STANDARDS