SIEMENS 3RW5234-6AC15 - Circuit breaker

3RW5234-6AC15 - Circuit breaker SIEMENS - Free user manual and instructions

Find the device manual for free 3RW5234-6AC15 SIEMENS in PDF.

📄 11 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice SIEMENS 3RW5234-6AC15 - page 2
Pick your language and provide your email: we'll send you a specifically translated version.
Product TypeSoft Starter (SIRIUS 3RW52 series)
Dimensions (H x W x D)306 mm x 185 mm x 203 mm
Weight (without packaging)6.6 kg
Control Supply Voltage110-250 V AC, 50/60 Hz
Rated Operating Current (at 40°C)113 A (direct), 196 A (inside-delta)
Rated Operating Voltage200-600 V AC
Adjustable Motor Current Range53-113 A (direct), 91.8-196 A (inside-delta)
Start-Up Ramp Time0-20 s
Stop Voltage50% (fixed)
Current Limiting Value130-700% adjustable
Protection ClassIP00
Ambient Temperature (operation)-25°C to +60°C (derating above 40°C)
Mounting PositionVertical surface, +/-90° rotatable, +/-22.5° tiltable
Required Spacing (side-by-side)10 mm forward, 0 mm backward, 100 mm upward, 75 mm downward, 5 mm side
Main Circuit ConnectionBusbar connection; conductor up to 2x (25-120 mm² fine stranded)
Control Circuit ConnectionScrew terminals; solid 1x (0.5-4.0 mm²) or fine stranded 1x (0.5-2.5 mm²)
Digital Inputs / Outputs1 digital input, 3 digital outputs (2 NO, 1 changeover), 1 analog output (4-20 mA / 0-10 V)
Overvoltage ProtectionVaristor
Short-Circuit Protection (control circuit)4 A gG fuse or 6 A quick-acting fuse (not supplied)
Integrated BypassYes
Motor Overload ProtectionElectronic, CLASS 10A/10E/20E
Communication Modules SupportedPROFINET, EtherNet/IP, Modbus TCP/RTU, PROFIBUS (optional)
CertificationsCE, UL, CSA, CCC, RCM, Marine (ABS, LRS, PRS)
MaintenanceRefer to user manual for cleaning and inspection intervals; no user-serviceable parts inside.
Spare Parts / AccessoriesCommunication modules, HMI modules, circuit breakers, fuses (see catalog)

Frequently Asked Questions - 3RW5234-6AC15 SIEMENS

What is the operating current rating of the 3RW5234-6AC15?
The rated operating current is 113 A at 40°C (direct connection) and 196 A at 40°C (inside-delta circuit). It derates at higher temperatures.
What control supply voltage does the soft starter require?
It requires 110-250 V AC at 50/60 Hz. The tolerance is -15% to +10%.
Can the soft starter be used with an inside-delta motor connection?
Yes, the 3RW5234-6AC15 supports inside-delta circuit operation. The current settings and power ratings differ for this configuration.
What communication options are available?
Optional communication modules for PROFINET, EtherNet/IP, Modbus TCP, Modbus RTU, and PROFIBUS can be installed.
How do I adjust the motor current?
Use the rotary encoding switch on the device. It has 16 positions corresponding to current values from 53 A to 113 A (direct) or 91.8 A to 196 A (inside-delta).
What is the ambient temperature range for operation?
The device can operate from -25°C to +60°C. However, derating (reduction in current capacity) is required above 40°C.
Does the soft starter provide motor overload protection?
Yes, it includes electronic motor overload protection with trip classes CLASS 10A (default), 10E, and 20E according to IEC 60947-4-2.
What are the mounting requirements?
Mount vertically on a flat surface. Minimum spacing: 10 mm forward, 0 mm backward, 100 mm upward, 75 mm downward, and 5 mm on sides for airflow.
How can I reset the device after a fault?
The device supports automatic reset (auto-reset) and manual reset. Remote reset is possible by cycling the control supply voltage off and on.
Where can I find the user manual or technical support?
Manuals and detailed information are available at Siemens Industry Online Support: https://support.industry.siemens.com/cs/ww/en/ps/3RW5234-6AC15

User questions about 3RW5234-6AC15 SIEMENS

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Circuit breaker in PDF format for free! Find your manual 3RW5234-6AC15 - SIEMENS and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. 3RW5234-6AC15 by SIEMENS.

USER MANUAL 3RW5234-6AC15 SIEMENS

SIRIUS soft starter 200-600 V 113 A, 110-250 V AC Screw terminals Analog output

SIEMENS 3RW5234-6AC15 - 1

natural_image Industrial control unit with buttons and ventilation grilles (no visible text or symbols)
Product brand name SIRIUS
Product category Hybrid switching devices
Product designation Soft starter
Product type designation 3RW52
Manufacturer's article number
• of HMI module usable3RW5980-0HS00
• of HMI-Modul high-feature usable3RW5980-0HF00
• of communication module PROFINET standard usable3RW5980-0CS00
• of communication module PROFIBUS usable3RW5980-0CP00
• of communication module Modbus TCP usable3RW5980-0CT00
• of communication module Modbus RTU usable3RW5980-0CR00
• of communication module Ethernet/IP3RW5980-0CE00
• of circuit breaker usable at 400 V3VA2216-7MN32-0AA0; Type of coordination 1, lq = 65 kA, CLASS 10
• of circuit breaker usable at 400 V at inside-delta circuit3VA2220-7MN32-0AA0; Type of coordination 1, lq = 65 kA, CLASS 10
• of the gG fuse usable up to 690 V3NA3244-6; Type of coordination 1, lq = 65 kA
• of the gG fuse usable at inside-delta circuit up to 500 V3NA3244-6; Type of coordination 1, lq = 65 kA
  • of full range R fuse link for semiconductor protection usable up to 690 V
  • of back-up R fuse link for semiconductor protection usable up to 690 V

3NE1225-0; Type of coordination 2, Iq = 65 kA

3NE3332-0B; Type of coordination 2, Iq = 65 kA

General technical data
Starting voltage [%] 30 ... 100 %
Stopping voltage [%] 50 ... 50 %
Start-up ramp time of soft starter 0 ... 20 s
Current limiting value [%] adjustable 130 ... 700 %
Certificate of suitability
CE markingYes
UL approvalYes
CSA-approvalYes
Product component
is supported HMI-StandardYes
is supported HMI-High FeatureYes
Product feature integrated bypass contact system Yes
Number of controlled phases 3
Trip class CLASS 10A (default) / 10E / 20E; acc. to IEC60947-4-2
Insulation voltage
rated value600 V
Degree of pollution 3, acc. to IEC 60947-4-2
Impulse voltage rated value 6 kV
Blocking voltage of the thyristor maximum 1 800 V
Service factor 1
Surge voltage resistance rated value 6 kV
maximum permissible voltage for safe isolation
between main and auxiliary circuit600 V
Protection class IP IP00
Usage category acc. to IEC 60947-4-2 AC 53a
Shock resistance 15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
Vibration resistance 15 mm to 6 Hz; 2g to 500 Hz
Reference code acc. to DIN EN 81346-2Q
Product function
ramp-up (soft starting)Yes
ramp-down (soft stop)Yes
Soft TorqueYes
Adjustable current limitationYes
pump ramp downYes
Intrinsic device protectionYes
motor overload protectionYes; Electronic motor overload protection
Evaluation of thermistor motor protectionNo
• Inside-delta circuitYes
• Auto-resetYes
• Manual RESETYes
• remote resetYes; By turning off the control supply voltage
• communication functionYes
• Operating measured value displayYes
• error logbookYes
• via software parameterizableNo
• via software configurableYes
• PROFenergyYes; in connection with the PROFINET Standard communication module
• firmware updateYes
• removable terminal for control circuitYes
• torque controlNo
• analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)

Power Electronics

Operating current
• at 40 °C rated value113 A
• at 50 °C rated value101 A
• at 60 °C rated value89 A
Operating current at inside-delta circuit
• at 40 °C rated value196 A
• at 50 °C rated value175 A
• at 60 °C rated value154 A
Operating voltage
• rated value200 ... 600 V
• at inside-delta circuit rated value200 ... 600 V
Relative negative tolerance of the operating voltage -15 %
Relative positive tolerance of the operating voltage 10 %
Relative negative tolerance of the operating voltage at inside-delta circuit-15 %
Relative positive tolerance of the operating voltage at inside-delta circuit10 %
Operating power for three-phase motors
• at 230 V at 40 °C rated value30 kW
• at 230 V at inside-delta circuit at 40 °C rated value55 kW
• at 400 V at 40 °C rated value55 kW
• at 400 V at inside-delta circuit at 40 °C rated value110 kW
• at 500 V at 40 °C rated value75 kW
• at 500 V at inside-delta circuit at 40 °C rated value132 kW
Operating frequency 1 rated value 50 Hz
Operating frequency 2 rated value 60 Hz
Relative negative tolerance of the operating frequency-10 %
Relative positive tolerance of the operating frequency 10 %
Adjustable motor current
• at rotary encoding switch on switch position 153 A
• at rotary encoding switch on switch position 361 A
• at rotary encoding switch on switch position 465 A
• at rotary encoding switch on switch position 569 A
• at rotary encoding switch on switch position 673 A
• at rotary encoding switch on switch position 777 A
• at rotary encoding switch on switch position 881 A
• at rotary encoding switch on switch position 985 A
• at rotary encoding switch on switch position 1089 A
• at rotary encoding switch on switch position 1193 A
• at rotary encoding switch on switch position 1297 A
• at rotary encoding switch on switch position 13101 A
• at rotary encoding switch on switch position 14105 A
• at rotary encoding switch on switch position 15109 A
• at rotary encoding switch on switch position 16113 A
• minimum53 A
• at inside-delta circuit minimum91.8 A
Adjustable motor current for inside-delta circuit
• at rotary encoding switch on switch position 191.8 A
• at rotary encoding switch on switch position 298.7 A
• at rotary encoding switch on switch position 3106 A
• at rotary encoding switch on switch position 4113 A
• at rotary encoding switch on switch position 5120 A
• at rotary encoding switch on switch position 6126 A
• at rotary encoding switch on switch position 7133 A
• at rotary encoding switch on switch position 8140 A
• at rotary encoding switch on switch position 9147 A
• at rotary encoding switch on switch position 10154 A
• at rotary encoding switch on switch position 11161 A
• at rotary encoding switch on switch position 12168 A
• at rotary encoding switch on switch position 13175 A
• at rotary encoding switch on switch position 14182 A
• at rotary encoding switch on switch position 15189 A
• at rotary encoding switch on switch position 16196 A
Minimum load [%] 15 %; Relative to smallest settable le
Power loss [W] for rated value of the current at AC
• at 40 °C to power-up46 W
• at 50 °C to power-up42 W
• at 60 °C to power-up39 W
Power loss [W] at AC at AC
• at 60 °C during startup1 086 W
• at 50 °C during startup1 291 W
Control circuit/ Control
Type of voltage of the control supply voltage AC
Control supply voltage at AC
• at 50 Hz110 ... 250 V
• at 60 Hz110 ... 250 V
Relative negative tolerance of the control supply voltage at AC at 50 Hz-15 %
Relative positive tolerance of the control supply voltage at AC at 50 Hz10 %
Relative negative tolerance of the control supply voltage at AC at 60 Hz-15 %
Relative positive tolerance of the control supply voltage at AC at 60 Hz10 %
Control supply voltage frequency 50 ... 60 Hz
Relative negative tolerance of the control supply voltage frequency-10 %
Relative positive tolerance of the control supply voltage frequency10 %
Control supply current in standby mode rated value 30 mA
Holding current in the by-pass mode operating rated value75 mA
Starting current at close of by-pass contact maximum 2.5 A
Inrush current peak at connect of control supply voltage maximum12.2 A
Duration of inrush current peak at connect of control supply voltage2.2 ms
Design of the overvoltage protection Varistor
Design of short-circuit protection for control circuit4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply
Inputs/ Outputs
Number of digital inputs 1
Number of inputs for thermistor connection 0
Number of digital outputs 3
• not parameterizable2
Digital output version 2 normally-open contacts (NO) / 1changeover contact (CO)
Number of analog outputs 1
Switching capacity current of the relay outputs
• at AC-15 at 250 V rated value3 A
• at DC-13 at 24 V rated value1 A

Installation/ mounting/ dimensions

Mounting position with vertical mounting surface +/-90°rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Mounting type screw fixing
Height 306 mm
Width 185 mm
Depth 203 mm
Required spacing with side-by-side mounting
• forwards10 mm
• Backwards0 mm
• upwards100 mm
• downwards75 mm
• at the side5 mm
Installation altitude at height above sea level maximum5 000 m; Derating as of 1000 m, see catalog
Weight without packaging 6.6 kg

Connections/ Terminals

Type of electrical connection
• for main current circuitbusbar connection
• for control circuitscrew-type terminals
Width of connection bar maximum 25 mm
Type of connectable conductor cross-sections
• for DIN cable lug for main contacts stranded2x (16 ... 95 mm^2 )
• for DIN cable lug for main contacts finely stranded2x (25 ... 120 mm^2 )
Type of connectable conductor cross-sections
• for control circuit solid1x (0.5 ... 4.0 mm^2 ), 2x (0.5 ... 2.5 mm^2 )
• for control circuit finely stranded with core end processing1x (0.5 ... 2.5 mm^2 ), 2x (0.5 ... 1.5 mm^2 )
• at AWG conductors for control circuit solid1x (20 ... 12), 2x (20 ... 14)
Wire length
• between soft starter and motor maximum800 m
• at the digital inputs at AC maximum100 m

Ambient conditions

Ambient temperature
• during operation-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
• during storage and transport-40 ... +80 °C

Environmental category

• during operation acc. to IEC 60721
• during storage acc. to IEC 60721
• during transport acc. to IEC 60721

3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

EMC emitted interference acc. to IEC 60947-4-2: Class A

Communication/ Protocol
Communication module is supported

• PROFINET standard
• EtherNet/IP
• Modbus RTU
• Modbus TCP
• PROFIBUS
Yes
Yes
Yes
Yes
Yes

UL/CSA ratings
Manufacturer's article number
- of circuit breaker

— usable for Standard Faults at 460/480 V according to UL
— usable for High Faults at 460/480 V according to UL
— usable for Standard Faults at 460/480 V at inside-delta circuit according to UL
— usable for High Faults at 460/480 V at inside-delta circuit according to UL
— usable for Standard Faults at 575/600 V according to UL
— usable for Standard Faults at 575/600 V at inside-delta circuit according to UL
Iq = 10 kA
Iq max = 65 kA
Iq = 10 kA
Iq max = 65 kA
Iq = 10 kA
Iq = 10 kA
  • of the fuse
— usable for Standard Faults up to 575/600 V according to UL
— usable for High Faults up to 575/600 V according to UL
— usable for Standard Faults at inside-delta circuit up to 575/600 V according to UL
— usable for High Faults at inside-delta circuit up to 575/600 V according to UL
Type: Class RK5 / K5, max. 350 A; Iq = 10 kA
Type: Class J / L, max. 350 A; Iq = 100 kA
Type: Class RK5 / K5, max. 350 A; Iq = 10 kA
Type: Class J / L, max. 350 A; Iq = 100 kA

Operating power [hp] for three-phase motors

• at 200/208 V at 50 °C rated value
• at 220/230 V at 50 °C rated value
• at 460/480 V at 50 °C rated value
• at 575/600 V at 50 °C rated value
30 hp
30 hp
75 hp
100 hp
  • at 200/208 V at inside-delta circuit at 50 °C rated value
  • at 220/230 V at inside-delta circuit at 50 °C rated value
  • at 460/480 V at inside-delta circuit at 50 °C rated value
  • at 575/600 V at inside-delta circuit at 50 °C rated value

50 hp

60 hp

125 hp

150 hp

Contact rating of auxiliary contacts according to UL R300-B300

Electromagnetic compatibility in accordance with IEC 60947-4-2

Certificates/ approvals

General Product Approval EMC Declaration ofConformity
SIEMENS 3RW5234-6AC15 - Environmental category - 1SIEMENS 3RW5234-6AC15 - Environmental category - 2SIEMENS 3RW5234-6AC15 - Environmental category - 3SIEMENS 3RW5234-6AC15 - Environmental category - 4SIEMENS 3RW5234-6AC15 - Environmental category - 5SIEMENS 3RW5234-6AC15 - Environmental category - 6
CCCCSAULRCMEG-Konf.

CCC
CSA
UL
RCM
EG-Konf.

Declaration of ConformityTest CertificatesMarine / Shipping other
Miscellaneous Type Test Certificates/Test ReportABSLRSPRSConfirmation

Further information

Information- and Downloadcenter (Catalogs, Brochures,...)

www.siemens.com/sirius/catalogs

Industry Mall (Online ordering system)

https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RW5234-6AC15

Cax online generator

http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RW5234-6AC15

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)

https://support.industry.siemens.com/cs/ww/en/ps/3RW5234-6AC15

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)

http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RW5234-6AC15&lang=en

Characteristic: Tripping characteristics, I²t, Let-through current

https://support.industry.siemens.com/cs/ww/en/ps/3RW5234-6AC15/char

Characteristic: Installation altitude

http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RW5234-6AC15&objecttype=14&gridview=view1

1/ L1 3 / L2 5 / L3 SIRIUS 2 / T1 4 / T2 6 / T3 136 135 GD 17 Ø7 206.8 206.6 226 SIRIUS

203 110 10 115

1/L12/T1 3/L2 5/L3 4/T2 6/T3 A2 A1 IN 14/24 ON/RUN BYPASSSED 95 13 NO 23 NO 98 NO 96 NC AQ I+ AQ U+ AQ-