3RW5234-6AC15 - Circuit breaker SIEMENS - Free user manual and instructions
Find the device manual for free 3RW5234-6AC15 SIEMENS in PDF.
| Product Type | Soft Starter (SIRIUS 3RW52 series) |
| Dimensions (H x W x D) | 306 mm x 185 mm x 203 mm |
| Weight (without packaging) | 6.6 kg |
| Control Supply Voltage | 110-250 V AC, 50/60 Hz |
| Rated Operating Current (at 40°C) | 113 A (direct), 196 A (inside-delta) |
| Rated Operating Voltage | 200-600 V AC |
| Adjustable Motor Current Range | 53-113 A (direct), 91.8-196 A (inside-delta) |
| Start-Up Ramp Time | 0-20 s |
| Stop Voltage | 50% (fixed) |
| Current Limiting Value | 130-700% adjustable |
| Protection Class | IP00 |
| Ambient Temperature (operation) | -25°C to +60°C (derating above 40°C) |
| Mounting Position | Vertical surface, +/-90° rotatable, +/-22.5° tiltable |
| Required Spacing (side-by-side) | 10 mm forward, 0 mm backward, 100 mm upward, 75 mm downward, 5 mm side |
| Main Circuit Connection | Busbar connection; conductor up to 2x (25-120 mm² fine stranded) |
| Control Circuit Connection | Screw terminals; solid 1x (0.5-4.0 mm²) or fine stranded 1x (0.5-2.5 mm²) |
| Digital Inputs / Outputs | 1 digital input, 3 digital outputs (2 NO, 1 changeover), 1 analog output (4-20 mA / 0-10 V) |
| Overvoltage Protection | Varistor |
| Short-Circuit Protection (control circuit) | 4 A gG fuse or 6 A quick-acting fuse (not supplied) |
| Integrated Bypass | Yes |
| Motor Overload Protection | Electronic, CLASS 10A/10E/20E |
| Communication Modules Supported | PROFINET, EtherNet/IP, Modbus TCP/RTU, PROFIBUS (optional) |
| Certifications | CE, UL, CSA, CCC, RCM, Marine (ABS, LRS, PRS) |
| Maintenance | Refer to user manual for cleaning and inspection intervals; no user-serviceable parts inside. |
| Spare Parts / Accessories | Communication modules, HMI modules, circuit breakers, fuses (see catalog) |
Frequently Asked Questions - 3RW5234-6AC15 SIEMENS
User questions about 3RW5234-6AC15 SIEMENS
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Circuit breaker in PDF format for free! Find your manual 3RW5234-6AC15 - SIEMENS and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. 3RW5234-6AC15 by SIEMENS.
USER MANUAL 3RW5234-6AC15 SIEMENS
SIRIUS soft starter 200-600 V 113 A, 110-250 V AC Screw terminals Analog output

natural_image
Industrial control unit with buttons and ventilation grilles (no visible text or symbols)| Product brand name SIRIUS | |
| Product category Hybrid switching devices | |
| Product designation Soft starter | |
| Product type designation 3RW52 | |
| Manufacturer's article number | |
| • of HMI module usable | 3RW5980-0HS00 |
| • of HMI-Modul high-feature usable | 3RW5980-0HF00 |
| • of communication module PROFINET standard usable | 3RW5980-0CS00 |
| • of communication module PROFIBUS usable | 3RW5980-0CP00 |
| • of communication module Modbus TCP usable | 3RW5980-0CT00 |
| • of communication module Modbus RTU usable | 3RW5980-0CR00 |
| • of communication module Ethernet/IP | 3RW5980-0CE00 |
| • of circuit breaker usable at 400 V | 3VA2216-7MN32-0AA0; Type of coordination 1, lq = 65 kA, CLASS 10 |
| • of circuit breaker usable at 400 V at inside-delta circuit | 3VA2220-7MN32-0AA0; Type of coordination 1, lq = 65 kA, CLASS 10 |
| • of the gG fuse usable up to 690 V | 3NA3244-6; Type of coordination 1, lq = 65 kA |
| • of the gG fuse usable at inside-delta circuit up to 500 V | 3NA3244-6; Type of coordination 1, lq = 65 kA |
- of full range R fuse link for semiconductor protection usable up to 690 V
- of back-up R fuse link for semiconductor protection usable up to 690 V
3NE1225-0; Type of coordination 2, Iq = 65 kA
3NE3332-0B; Type of coordination 2, Iq = 65 kA
| General technical data | |
| Starting voltage [%] 30 ... 100 % | |
| Stopping voltage [%] 50 ... 50 % | |
| Start-up ramp time of soft starter 0 ... 20 s | |
| Current limiting value [%] adjustable 130 ... 700 % | |
| Certificate of suitability | |
| CE marking | Yes |
| UL approval | Yes |
| CSA-approval | Yes |
| Product component | |
| is supported HMI-Standard | Yes |
| is supported HMI-High Feature | Yes |
| Product feature integrated bypass contact system Yes | |
| Number of controlled phases 3 | |
| Trip class CLASS 10A (default) / 10E / 20E; acc. to IEC | 60947-4-2 |
| Insulation voltage | |
| rated value | 600 V |
| Degree of pollution 3, acc. to IEC 60947-4-2 | |
| Impulse voltage rated value 6 kV | |
| Blocking voltage of the thyristor maximum 1 800 V | |
| Service factor 1 | |
| Surge voltage resistance rated value 6 kV | |
| maximum permissible voltage for safe isolation | |
| between main and auxiliary circuit | 600 V |
| Protection class IP IP00 | |
| Usage category acc. to IEC 60947-4-2 AC 53a | |
| Shock resistance 15 g / 11 ms, from 12 g / 11 ms with potential contact lifting | |
| Vibration resistance 15 mm to 6 Hz; 2g to 500 Hz | |
| Reference code acc. to DIN EN 81346-2 | Q |
| Product function | |
| ramp-up (soft starting) | Yes |
| ramp-down (soft stop) | Yes |
| Soft Torque | Yes |
| Adjustable current limitation | Yes |
| pump ramp down | Yes |
| Intrinsic device protection | Yes |
| motor overload protection | Yes; Electronic motor overload protection |
| Evaluation of thermistor motor protection | No |
| • Inside-delta circuit | Yes |
| • Auto-reset | Yes |
| • Manual RESET | Yes |
| • remote reset | Yes; By turning off the control supply voltage |
| • communication function | Yes |
| • Operating measured value display | Yes |
| • error logbook | Yes |
| • via software parameterizable | No |
| • via software configurable | Yes |
| • PROFenergy | Yes; in connection with the PROFINET Standard communication module |
| • firmware update | Yes |
| • removable terminal for control circuit | Yes |
| • torque control | No |
| • analog output | Yes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI) |
Power Electronics
| Operating current | |
| • at 40 °C rated value | 113 A |
| • at 50 °C rated value | 101 A |
| • at 60 °C rated value | 89 A |
| Operating current at inside-delta circuit | |
| • at 40 °C rated value | 196 A |
| • at 50 °C rated value | 175 A |
| • at 60 °C rated value | 154 A |
| Operating voltage | |
| • rated value | 200 ... 600 V |
| • at inside-delta circuit rated value | 200 ... 600 V |
| Relative negative tolerance of the operating voltage -15 % | |
| Relative positive tolerance of the operating voltage 10 % | |
| Relative negative tolerance of the operating voltage at inside-delta circuit | -15 % |
| Relative positive tolerance of the operating voltage at inside-delta circuit | 10 % |
| Operating power for three-phase motors | |
| • at 230 V at 40 °C rated value | 30 kW |
| • at 230 V at inside-delta circuit at 40 °C rated value | 55 kW |
| • at 400 V at 40 °C rated value | 55 kW |
| • at 400 V at inside-delta circuit at 40 °C rated value | 110 kW |
| • at 500 V at 40 °C rated value | 75 kW |
| • at 500 V at inside-delta circuit at 40 °C rated value | 132 kW |
| Operating frequency 1 rated value 50 Hz | |
| Operating frequency 2 rated value 60 Hz | |
| Relative negative tolerance of the operating frequency | -10 % |
| Relative positive tolerance of the operating frequency 10 % | |
| Adjustable motor current | |
| • at rotary encoding switch on switch position 1 | 53 A |
| • at rotary encoding switch on switch position 3 | 61 A |
| • at rotary encoding switch on switch position 4 | 65 A |
| • at rotary encoding switch on switch position 5 | 69 A |
| • at rotary encoding switch on switch position 6 | 73 A |
| • at rotary encoding switch on switch position 7 | 77 A |
| • at rotary encoding switch on switch position 8 | 81 A |
| • at rotary encoding switch on switch position 9 | 85 A |
| • at rotary encoding switch on switch position 10 | 89 A |
| • at rotary encoding switch on switch position 11 | 93 A |
| • at rotary encoding switch on switch position 12 | 97 A |
| • at rotary encoding switch on switch position 13 | 101 A |
| • at rotary encoding switch on switch position 14 | 105 A |
| • at rotary encoding switch on switch position 15 | 109 A |
| • at rotary encoding switch on switch position 16 | 113 A |
| • minimum | 53 A |
| • at inside-delta circuit minimum | 91.8 A |
| Adjustable motor current for inside-delta circuit | |
| • at rotary encoding switch on switch position 1 | 91.8 A |
| • at rotary encoding switch on switch position 2 | 98.7 A |
| • at rotary encoding switch on switch position 3 | 106 A |
| • at rotary encoding switch on switch position 4 | 113 A |
| • at rotary encoding switch on switch position 5 | 120 A |
| • at rotary encoding switch on switch position 6 | 126 A |
| • at rotary encoding switch on switch position 7 | 133 A |
| • at rotary encoding switch on switch position 8 | 140 A |
| • at rotary encoding switch on switch position 9 | 147 A |
| • at rotary encoding switch on switch position 10 | 154 A |
| • at rotary encoding switch on switch position 11 | 161 A |
| • at rotary encoding switch on switch position 12 | 168 A |
| • at rotary encoding switch on switch position 13 | 175 A |
| • at rotary encoding switch on switch position 14 | 182 A |
| • at rotary encoding switch on switch position 15 | 189 A |
| • at rotary encoding switch on switch position 16 | 196 A |
| Minimum load [%] 15 %; Relative to smallest settable le | |
| Power loss [W] for rated value of the current at AC | |
| • at 40 °C to power-up | 46 W |
| • at 50 °C to power-up | 42 W |
| • at 60 °C to power-up | 39 W |
| Power loss [W] at AC at AC | |
| • at 60 °C during startup | 1 086 W |
| • at 50 °C during startup | 1 291 W |
| Control circuit/ Control | |
| Type of voltage of the control supply voltage AC | |
| Control supply voltage at AC | |
| • at 50 Hz | 110 ... 250 V |
| • at 60 Hz | 110 ... 250 V |
| Relative negative tolerance of the control supply voltage at AC at 50 Hz | -15 % |
| Relative positive tolerance of the control supply voltage at AC at 50 Hz | 10 % |
| Relative negative tolerance of the control supply voltage at AC at 60 Hz | -15 % |
| Relative positive tolerance of the control supply voltage at AC at 60 Hz | 10 % |
| Control supply voltage frequency 50 ... 60 Hz | |
| Relative negative tolerance of the control supply voltage frequency | -10 % |
| Relative positive tolerance of the control supply voltage frequency | 10 % |
| Control supply current in standby mode rated value 30 mA | |
| Holding current in the by-pass mode operating rated value | 75 mA |
| Starting current at close of by-pass contact maximum 2.5 A | |
| Inrush current peak at connect of control supply voltage maximum | 12.2 A |
| Duration of inrush current peak at connect of control supply voltage | 2.2 ms |
| Design of the overvoltage protection Varistor | |
| Design of short-circuit protection for control circuit | 4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply |
| Inputs/ Outputs | |
| Number of digital inputs 1 | |
| Number of inputs for thermistor connection 0 | |
| Number of digital outputs 3 | |
| • not parameterizable | 2 |
| Digital output version 2 normally-open contacts (NO) / 1 | changeover contact (CO) |
| Number of analog outputs 1 | |
| Switching capacity current of the relay outputs | |
| • at AC-15 at 250 V rated value | 3 A |
| • at DC-13 at 24 V rated value | 1 A |
Installation/ mounting/ dimensions
| Mounting position with vertical mounting surface +/-90° | rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back |
| Mounting type screw fixing | |
| Height 306 mm | |
| Width 185 mm | |
| Depth 203 mm | |
| Required spacing with side-by-side mounting | |
| • forwards | 10 mm |
| • Backwards | 0 mm |
| • upwards | 100 mm |
| • downwards | 75 mm |
| • at the side | 5 mm |
| Installation altitude at height above sea level maximum | 5 000 m; Derating as of 1000 m, see catalog |
| Weight without packaging 6.6 kg |
Connections/ Terminals
| Type of electrical connection | |
| • for main current circuit | busbar connection |
| • for control circuit | screw-type terminals |
| Width of connection bar maximum 25 mm | |
| Type of connectable conductor cross-sections | |
| • for DIN cable lug for main contacts stranded | 2x (16 ... 95 mm^2 ) |
| • for DIN cable lug for main contacts finely stranded | 2x (25 ... 120 mm^2 ) |
| Type of connectable conductor cross-sections | |
| • for control circuit solid | 1x (0.5 ... 4.0 mm^2 ), 2x (0.5 ... 2.5 mm^2 ) |
| • for control circuit finely stranded with core end processing | 1x (0.5 ... 2.5 mm^2 ), 2x (0.5 ... 1.5 mm^2 ) |
| • at AWG conductors for control circuit solid | 1x (20 ... 12), 2x (20 ... 14) |
| Wire length | |
| • between soft starter and motor maximum | 800 m |
| • at the digital inputs at AC maximum | 100 m |
Ambient conditions
| Ambient temperature | |
| • during operation | -25 ... +60 °C; Please observe derating at temperatures of 40 °C or above |
| • during storage and transport | -40 ... +80 °C |
Environmental category
• during operation acc. to IEC 60721
• during storage acc. to IEC 60721
• during transport acc. to IEC 60721
3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
EMC emitted interference acc. to IEC 60947-4-2: Class A
Communication/ Protocol
Communication module is supported
| • PROFINET standard |
| • EtherNet/IP |
| • Modbus RTU |
| • Modbus TCP |
| • PROFIBUS |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
UL/CSA ratings
Manufacturer's article number
- of circuit breaker
| — usable for Standard Faults at 460/480 V according to UL |
| — usable for High Faults at 460/480 V according to UL |
| — usable for Standard Faults at 460/480 V at inside-delta circuit according to UL |
| — usable for High Faults at 460/480 V at inside-delta circuit according to UL |
| — usable for Standard Faults at 575/600 V according to UL |
| — usable for Standard Faults at 575/600 V at inside-delta circuit according to UL |
| Iq = 10 kA |
| Iq max = 65 kA |
| Iq = 10 kA |
| Iq max = 65 kA |
| Iq = 10 kA |
| Iq = 10 kA |
- of the fuse
| — usable for Standard Faults up to 575/600 V according to UL |
| — usable for High Faults up to 575/600 V according to UL |
| — usable for Standard Faults at inside-delta circuit up to 575/600 V according to UL |
| — usable for High Faults at inside-delta circuit up to 575/600 V according to UL |
| Type: Class RK5 / K5, max. 350 A; Iq = 10 kA |
| Type: Class J / L, max. 350 A; Iq = 100 kA |
| Type: Class RK5 / K5, max. 350 A; Iq = 10 kA |
| Type: Class J / L, max. 350 A; Iq = 100 kA |
Operating power [hp] for three-phase motors
| • at 200/208 V at 50 °C rated value |
| • at 220/230 V at 50 °C rated value |
| • at 460/480 V at 50 °C rated value |
| • at 575/600 V at 50 °C rated value |
| 30 hp |
| 30 hp |
| 75 hp |
| 100 hp |
- at 200/208 V at inside-delta circuit at 50 °C rated value
- at 220/230 V at inside-delta circuit at 50 °C rated value
- at 460/480 V at inside-delta circuit at 50 °C rated value
- at 575/600 V at inside-delta circuit at 50 °C rated value
50 hp
60 hp
125 hp
150 hp
Contact rating of auxiliary contacts according to UL R300-B300
Electromagnetic compatibility in accordance with IEC 60947-4-2
Certificates/ approvals
| General Product Approval EMC Declaration of | Conformity | ||||
![]() | ![]() | ![]() | ![]() | ![]() | ![]() |
| CCC | CSA | UL | RCM | EG-Konf. | |
CCC
CSA
UL
RCM
EG-Konf.
| Declaration of Conformity | Test Certificates | Marine / Shipping other | |||
| Miscellaneous Type Test Certificates/Test Report | ABS | LRS | PRS | Confirmation | |
Further information
Information- and Downloadcenter (Catalogs, Brochures,...)
www.siemens.com/sirius/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RW5234-6AC15
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RW5234-6AC15
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RW5234-6AC15
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RW5234-6AC15&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RW5234-6AC15/char
Characteristic: Installation altitude
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RW5234-6AC15&objecttype=14&gridview=view1



last modified:
09/18/2019