ATEMNO - Thermostat Hoffman - Free user manual and instructions
Find the device manual for free ATEMNO Hoffman in PDF.
| Product Type | Temperature Thermostat |
| Brand | Hoffman |
| Model | ATEMNO |
| Mounting | Clip-mounting on 35 mm DIN rail (EN50022) |
| Operating Temperature Range | -45°C to 80°C (-49°F to 176°F) |
| Hysteresis (Switching Difference) | 7 K ±4 K (Kelvin) |
| Contact Types | Normally closed (a), Normally open (b), Combination (c) |
| Applications | Regulate heating, cooling, filter fans, heat exchangers, low or high temperature alarms |
| Installation | Must be installed by qualified technician in accordance with national electrical codes |
| Safety | Do not exceed voltage and current specified on product label |
| Ventilation | Do not cover ventilation openings |
| Set Point Adjustment | Via adjustment knob; account for hysteresis when setting |
| Placement for Heating | Install in upper area of enclosure, away from heaters |
| Placement for Cooling | Install at bottom of enclosure, away from cooling device |
| Standard Compliance | Designed for enclosure temperature measurement |
Frequently Asked Questions - ATEMNO Hoffman
User questions about ATEMNO Hoffman
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Thermostat in PDF format for free! Find your manual ATEMNO - Hoffman and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ATEMNO by Hoffman.
USER MANUAL ATEMNO Hoffman
natural_image
Two black electronic components with red and blue indicator lights, labeled a) and b), (no text or symbols on the devices themselves)
natural_image
Front view of a white industrial power supply unit with control knobs and buttons (no visible text or labels)Temperature Controls
• The temperature control should only be installed by qualified technicians in accordance with the respective national electrical codes.
- The safety and protection against incidental contact is to be ensured through proper installation.
• The technical specifications (voltage and current) as stated on the product must not be exceeded!
a. Normally closed contact (switching contact opens at rising temperature)
b. Normally open contact (switching contact closes at rising temperature)
c. Combination (combination of a) and b))
Applications:
The temperature controls are used to regulate heating equipment, cooling equipment, filter fans and heat exchangers. In addition, they can also be used as switching contacts for signal devices used as low—or high temperature alarms.
Installation guidelines:
The temperature controls are designed to measure the temperature in enclosures. When used in heating applications, they should be installed in the upper area of the enclosure as far away as possible from heaters or other heat-generating components. When used in cooling applications, they should be installed at the bottom of the enclosure as far away as possible from the cooling device.
Clip–mounting onto 35 mm DIN rails according to EN50022 is standard.
The ventilation openings of the temperature control should not be covered at any time.
Operating temperature range: -45 °C to 80 °C (-49 °F to 176 °F)
Important: as operating conditions vary widely, safe operation of the temperature control is to be checked in the final application.
Setting recommendations:
The hysteresis (switching difference) of the temperature control should be taken into account:
a), b) and c): 7 K± 4 K (Kelvin)
In order to determine the actual set point of the normally closed contact, the maximum rated hysteresis should be added to the required minimum operating temperature:
Example for a):
required minimum temperature in enclosure: 5 C (41 F)
Hysteresis of temperature control: +11 K (= 7 K ± 4 K)
Set point on adjustment knob: 16 C (61 F)