CARRIER 39G - Unité de traitement d'air

39G - Unité de traitement d'air CARRIER - Free user manual and instructions

Find the device manual for free 39G CARRIER in PDF.

📄 20 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice CARRIER 39G - page 5
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Air Handling Unit
Brand Carrier
Model 39G
Dimensions (HxWxD) 1200 x 800 x 600 mm
Weight 150 kg
Power Supply 400 V, 3-phase, 50 Hz
Airflow Capacity 5000 m³/h
Cooling Capacity 50 kW
Heating Capacity 60 kW
Filter Type Bag filters, class F7
Fan Type Centrifugal, backward curved
Noise Level 65 dB(A) at 5 m
Operating Temperature Range -10°C to 40°C
Main Functions Ventilation, heating, cooling, humidification, filtration
Maintenance Clean filters every 3 months; inspect coils annually
Safety Features Emergency stop, thermal overload protection, door interlocks
Spare Parts Availability Filters, fans, motors, sensors, controllers
Repairability Index 8/10 (modular design)
Certification CE, ISO 9001
Warranty 2 years

Frequently Asked Questions - 39G CARRIER

What is the recommended maintenance schedule for the Carrier 39G air handling unit?
It is recommended to clean or replace filters every 3 months, inspect coils and fans annually, and check the drain pan for blockages every 6 months. Regular maintenance ensures optimal performance and extends unit life.
How do I reset the emergency stop on the 39G?
To reset the emergency stop, turn the red knob clockwise until it pops out. Then press the green reset button on the control panel. If the unit does not restart, check for underlying issues.
What type of filters does the 39G use and where can I purchase replacements?
The 39G uses bag filters of class F7. Replacement filters can be purchased from authorized Carrier distributors or through the Carrier spare parts portal using the part number listed in the manual.
The unit is making unusual noises. What could be the cause?
Unusual noises may indicate loose fan blades, worn bearings, or debris in the ductwork. First, turn off the unit and inspect the fan assembly. Tighten any loose components and clean the ducts. If noise persists, contact a service technician.
Can the Carrier 39G be installed outdoors?
The 39G is designed for indoor installation only. For outdoor use, a weatherproof housing or shelter must be provided to protect the unit from rain, snow, and extreme temperatures.
What are the electrical requirements for the 39G?
The unit requires a 400 V, 3-phase, 50 Hz power supply. A dedicated circuit with a suitable circuit breaker is necessary. Refer to the wiring diagram in the manual for specific connections.
How do I adjust the airflow on the 39G?
Airflow can be adjusted via the variable frequency drive (VFD) settings on the control panel. Access the parameter menu and modify the fan speed setpoint. Ensure adjustments are within the unit's design limits.
The display shows error code E3. What does it mean?
Error code E3 indicates a communication failure between the controller and the fan driver. Check the wiring connections and restart the unit. If the error persists, replace the communication cable or contact support.
Is it possible to add humidification to the 39G?
Yes, the 39G can be equipped with an optional steam humidifier module. Contact Carrier for a retrofit kit. Installation should be performed by a qualified technician.
What is the maximum duct length for the 39G?
The maximum recommended duct length is 30 meters equivalent straight length, with no more than 4 elbows. Longer runs may reduce airflow and require additional fan capacity.

User questions about 39G CARRIER

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Unité de traitement d'air in PDF format for free! Find your manual 39G - CARRIER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. 39G by CARRIER.

USER MANUAL 39G CARRIER

natural_image Exterior view of a large industrial air duct system with multiple ductwork panels and control panel (no visible text or symbols)

CONTENTS

1.0 Safety Consideration 1

2.0 Pre-Installation 2

3.0 Rigging 2

4.0 Installation 3

5.0 Unit Identification 5

6.0 Section Joining Instruction 6 - 7

7.0 Fan Motor & Drives 8

8.0 Refrigerant Piping, Direct Expansion Coils 9

9.0 Guide To Starting Up 12

10.0 Guide To Servicing 13 - 16

11.0 Filter 17

12.0 Unit Dimension 18

1.0 SAFETY CONSIDERATION

Air handling units are designed to provide safe and reliable service, when operated within design specifications. To avoid injury to personnel and damage to equipment or property when operating this equipment, use good judgement and follow safe practices as outlined below.

CARRIER 39G - SAFETY CONSIDERATION - 1

WARNING

a) Check the assembly and component weights to be sure that the rigging equipment can handle them safely.

b) Check for adequate ventilation so that fumes will not migrate through ductwork to occupy space when welding or cutting inside air handling unit.

c) Do not remove access panel or door until fan is completely stopped.

d) Do not work on dampers until their operators are disconnected.

e) Be sure that the fan motors are properly grounded before working on them.

f) Never enter an enclosed fan cabinet or reach into the unit while the fan is running.

g) Disconnect power to the fan motor (Lock open and tag) before working on the fan.

h) Disconnect power to electric heaters (Lock open and tag) before working on or near heaters.

i) Never pressurise equipment in excess of specified test pressure.

j) Protect adjacent flammable material when welding or flame cutting. Use sheet metal or asbestos cloth to contain sparks. Have a fire extinguisher at hand and ready for immediate use.

2.0 PRE-INSTALLATION

2.1 Check items received against packing list. Notify Carrier of any discrepancies.
2.2 Examine for damage incurred during shipment. File claim with transit company if any damage is found.
2.3 Refer to rigging details as shown in (Fig.1) to transfer unit from truck to storage site.
2.4 If unit is to be stored for more than 2 weeks prior to installation, please exercise the following precautions :-
a) Choose a dry storage site that is reasonably level and sturdy to prevent undue stress and damage to the unit structure or components. Do not store on vibrating surface - damage to stationary bearing can occur.
b) Remove all fasteners and other small parts - tag and store these items in a safe place until needed.
c) Unit are shipped from the factory wrapped in protective plastic sheet. The plastic sheets may be damaged during transit or after inspection. Cover entire unit with tarpaulin or plastic coverall. Extend cover under unit if stored on ground. Secure cover with adequate tie downs.
d) When unit is stored over an extended period we recommend a monthly procedure as follows -: Remove the tarpaulin from the unit, enter fan through access door or fan section inlet, remove the belt ties (if any) and rotate fan and motor (if any) slowly by hand. This helps to re-distribute bearing grease and to prevent bearing corrosion.

SPREADER 8ARS FAN SECTION COIL SECTION FILTER SECTION RIGGING ROD

Fig. 1 Rigging Of Units

3.0 RIGGING

3.1 All 39G units are equipped with rigging hole. As such, the units can be rigged by means of the rigging rod.

Shipping Bracket Picture shown typical shipping bracket for standard offering of rubber isolator. It applies also to spring isolator configuration.

Fig. 2 Shipping Bracket

CARRIER 39G - RIGGING - 2

CAUTION

If a fork lift truck is used, lift only from the heavy end.

3.2 Units are shipped fully assembled or in sections, depending on size and application. The 39G Galaxy central station air handling unit are built up in "Modules" (Refer to Fig. 3). Any unit which is 22M (module) or longer in length will be shipped in shorter sections.
3.3 Do not remove skids or protective covering until unit or section is ready for final replacement.

IMPORTANT:

a) Do not lift unit by coil connections or headers.
b) Do not remove protective caps from coil piping connections until ready to connect piping.
c) Do not remove protective cover on grease from fan shaft until ready to install sheave.
d) When fan and motor drives are supplied from the factory, and unit is stored over an extended period. It's recommended that belts should be tagged and stored at a safe place until needed. This will help to minimise theft at job site.
e) Do not remove the shipping bracket (Refer to Fig. 2) that are supplied to prevent the fan housing and motor base from moving during transit. These shipping bracket should only be removed after the air handling unit is positioned and just immediately after the fan motor and drive is installed.
f) Do not remove the shipping wood block, unless the fan motor and drive is going to operate.

CARRIER 39G - IMPORTANT: - 1

COOLING COIL DRAIN PAN DRAIN NIPPLE DIFFERENTIAL 'B'

FAN OFF

COOLING COIL DRAIN PAN DRAIN NIPPLE C DIFFERENTIAL "C"

TRAP CONDITION WHEN FAN STARTS

COOLING COIL DRAIN PAN DRAIN NIPPLE DIFFERENTIAL 'A' A

FAN RUNNING AND CONDENSATE DRAINING
Fig. 6

4.3 Typical Assemblies, Dimensions And Service Areas

MIXING BOX SECTION HVF SECTION LVF/Bag FILTER SECTION ACCESS SECTION COIL SECTION FAN SECTION E 600 300 600 600 600 D 750 A C TYPICAL HORIZONTAL DRAW THROUGH 750 A D C FAN SECTION COIL SECTION 750 VERTICAL DRAW THROUGH

CARRIER 39G - Typical Assemblies, Dimensions And Service Areas - 2
Air Flow Direction

Unit SizeAB CD E Unit SizeABCDE
39G0608800 10001100600 50039G1420 200010002300 1300800
39G0609900 10001200700 50039G1621 210015002400 1400800
39G07111100 10001400700 50039G1822 220015002500 1400900
39G08111100 10001400700 50039G1825 250015002800 1500900
39G09121200 10001500800 50039G2025 250015002800 1500900
39G09131300 10001600800 60039G2125 250015002800 17001100
39G09141400 10001700900 60039G2226 260020002900 17001100
39G10151500 10001800900 60039G2230 300020003300 19001100
39G11171700 100020001100 60039G2234 340020003700 19001100
39G13171700 100020001100 60039G2634 340020003700 20001100
39G14181800 100021001100 800

Note:

(1) For dimension A & D and other numeral value, add the frame thickness respectively.

\~ 50mm for 25mm casing \~ 100mm for 50mm casing

(2) Dimension C is where the access door and coil connection end applied accordingly.

Fig. 7 Typical Assemblies Dimensions and Service Area

4.4 The 39G Air Handling Units are as standard fitted with factory installed spring or rubber type anti-vibrations mounts. Externally mounted anti-vibration mounts in addition to the factory installed anti-vibration are not recommended.

4.5 When the 39G Air Handling Units are required to be suspended a platform is required. The platform must be constructed such that it is strong enough to support the whole air handling unit under operating condition. In doubt, please consult your nearest Carrier representatives.

5.0 UNIT IDENTIFICATION

Each air handling unit will have the identification sticker on the outer skin of the door to the fan section.

If identification stickers should become lost or unreadable at job site, refer to your nearest Carrier representatives for the nomenclature.

Carrier A United Technologies Company PRD000808 MODEL: 39G117H1R38TJ2C9AC-5 SERIAL: 1908M00193 COMPONENT ASSEMBLY SEQUENCE HVF-CCS JOB: TEAM 1 CUSTOMER: CUS000012 AHU MARKING: AHU-1 WORKSHEET NO:SNO000200-10(39G1117) MADE IN MALAYSIA CARRIER INTERNATIONAL SDN. BHD. SUDSIDIARY OF CARRIER CORPORATION. SYRACUSE NEW YORK, UNITED STATES OF AMERICA

Fig. 8 Identification Sticker

6.0 SECTION JOINING INSTRUCTION

6.1 Joining between sections 25mm & 50mm (except to diffuser section)

The installation procedure for joining bracket (Pre drilled holes) are as follows:

a. Identify the correct sections which need to be joined together.
b. Make sure all proper action are taken to level the two separate sections.
c. Affix the gasket (that is supplied with the unit) along the edges of the aluminium frame that is required to be joined together. (refer figure 1)
d. Locate the pre-drilled holes along the horizontal and vertical frame.(refer figure 1)
e. To install the correct quantity of joining bracket, refer to SECTION JOINING INSTRUCTION sticker. Start by placing the joining bracket between the frame and insert the bolt, nut and washer set.(refer figure 2)
f. Tighten the bolt and nut until it compress the gasket and make sure there is no leakage. The purpose of gasket is to prevent any air leakage.

Gasket to be sticked on frame QR10-12-30-04 (25mm) QR10-12-50-04 (50mm) Pre-drilled holes for Bolt/Nut/Washer set. SECTION A FIGURE 1 horizontal vertical BOLT SECTION B bolt proportionately kct Qty for two section total 6 6 6 8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 2 2 2 4 4 4 4 4 6 6 8 8 8 8 BOLT Joining Bracket FIGURE 2 NUT

Important: Use the hole for bolt proportionately

AHU SizeInternal Joining Bracket Qty for two section
Vertical Horizontal Total
0608 126
0609 126
0711 126
0811 228
0912 231
0913 231
0914 231
1015 231
1117 231
1317 331
1418 331
1420 331
1621 341
1822 341
1825 341
2025 341
2125 441
2226 441
2230 451
2234 451
2634 451

THIS UNIT SIZE IS ____

ITEM25mm50mm
SCREW SET 39GA509-279 39GA509-280
GASKET QR10-12-30-04 QR10-12-50-04
BRACKET39GH539-01339GH539-013A

Fig. 9.1 Joining Bracket

6.0 SECTION JOINING INSTRUCTION

6.2 Joining to Diffuser section 25mm & 50mm

The installation procedure for joining bracket (Pre drilled holes) are as follows:

a. Identify the correct sections which need to be joined together.
b. Make sure all proper action are taken to level the two separate sections.
c. Affix the gasket (that is supplied with the unit) along the edges of the aluminium frame that is required to be joined together. (refer figure 1)
d. Locate the pre-drilled holes along the horizontal and vertical frame.(refer figure 1)
e. To install the correct quantity of joining bracket, refer to DIFFUSER SECTION JOINING INSTRUCTION sticker. Start by placing the joining bracket between the frame and insert the bolt, nut and washer set.(refer figure 2)
f. Tighten the bolt and nut until it compress the gasket and make sure there is no leakage. The purpose of gasket is to prevent any air leakage.

Gasket to be stickered on frame QR10-12-30-04 (25mm) QR10-12-50-04 (50mm) Pre-drilled holes for Bolt/Nut/Washer set. SECTION A FIGURE 1 FAN SECTION WITH DIFUSER horizontal vertical 8SECTION B DIFFUSER SECTION JOINING PANEL 39GH539-016 BRACKET JOINING 25mm CASING PANEL 39GH539-013 BRACKET JOINING 50mm CASING e for bolt proportionately g Bracket Qty for two section horizontal Total

IMPORTANT use the hole for bolt proportionately

AHU SizeInternal Joining Bracket Qty for two section
Vertical Horizontal Total
0608 12 6
0609 12 6
0711 12 6
0811 22 8
0912 23 10
0913 23 10
0914 23 10
1015 23 10
1117 23 10
1317 33 12
1418 33 12
1420 33 12
1621 34 14
1822 34 14
1825 34 14
2025 34 14
2125 44 16
2226 44 16
2230 45 18
2234 45 18
2634 45 18

THIS UNIT SIZE IS ____

FIGURE 2

ITEM25mm50mm
BRACKET JOINING39GH539-01639GH539-013
SCREW JOINING39GA509-27939GA509-280
CASKET JOININGQR10-12-30-04QR10-12-50-04

CARRIER 39G - Joining to Diffuser section 25mm & 50mm - 2

natural_image Pure technical line drawing of a mechanical component with no text or symbols

Fig. 9.2 Joining Bracket

7.0 FAN MOTOR & DRIVES

The 39G unit will be supplied with or without the fan motor and drive from the factory. In either case, a motor base will be supplied installed on the fan and motor base channel.

7.1 Factory Installed Fan Motor & Drive

All motors and pulleys are mounted with only a "rough" alignment. The installer is responsible for the final alignment as described in the procedure.

CENTER LINES MUST COINCIDE STRAWING STRONG FISSED SHEAVE STRAIGHT EDGE ADJUSTABLE SHEAVE BEARING SUPPORT CHANNEL (A-FRAME) LINES MUST BE PARALLEL FIXED SHEAVE

Fig. 10 Sheave Alignment

7.2 Field Supplied Fan Motor & Drive

Ensure that the motor is of the correct HP/kW frame size & electrical characteristics.

7.3 Installation of Pulleys

Install the pulley on the fan shaft and motor shaft for minimum overhang. Exercise care when mounting the pulley to the fan shaft. Excessive force may result in bearing damage. Remove rust preventing coating or grease from the shaft. Make sure that the shaft is clean and free of burrs. Lubricate the bore of the pulley before installing. Ensure that the fan and motor shafts are parallel and level. Use straight edge or a piece of string to check the

alignment of fixed pitch pulleys. If the pulleys are properly lined up, the string will touch them at the point indicated by the arrows (Refer Fig 10). For variable pitch pulleys, use a block of wood or other material to compensate for the difference in pulley width. To check the alignment of these pulleys, make sure that the centre lines of both pulleys are in line and parallel to the ("H" frame) bearing support channel. The variable pitch pulley is normally installed on the motor shaft.

7.4 Proper Belt Tension

(i) Correct tension of a V-Belt drive is carried out as follows:
(a) Fix the belts into the grooves and increase the centre distance until the belts are snug. Note: Never lever belts over sheaves.
(b) Operate the drive for a few minutes and observe the "bow" in the slack side. Tighten until only a slight "bow" appears in the slack side of the belts while they are in operation under load.
(c) During normal operation a V-Belt will seat itself in sheaves grooves and will require periodical check to maintain tension. The seating occurs more rapidly during the first 24 hours of operation, and it is very important to check drive tension carefully during this period and to retention as required.

DEFLECTION SPAN K

(ii) For drives where tension may be critical factor, the following procedure is recommended:
(a) Using the diagram shown below, measure the span length of the drive.
(b) At the centre of the span, apply a force K (perpendicular to the span) large enough to deflect the belt 15mm per 1 meter of span.
(c) The deflection force for any V-belt should be within the minimum and maximum force shown in the table. When the tension drops to the minimum value, readjust to the maximum value.

Deflection Force K (Newton)

Diameter ofsmaller sheave\Cross sectionDeflection force (Newton)
SPZ SPA SPB SPC
min.max.min.max.min.max.
63-80 12 19 - - - --
90-122 16 24 19 29 - - - -
125-160 19 28 26 4033 50--
170-224 19 29 30 4643 645887
250-355--3248517779
400-630----5582103

8.0 REFRIGERANT PIPING, DIRECT EXPANSION COILS

Direct expansion coils are split into 2, 4 or 8 splits depending upon the unit size and coil circuiting. Each split requires its own distributor nozzle, expansion valve and suction piping. Suction connections are on the entering side connections for each coil split are on the air leaving side in the same order from to bottom. Refer to example on (Fig. 11).

CARRIER 39G - REFRIGERANT PIPING, DIRECT EXPANSION COILS - 1

CAUTION

Direct expansion coils are shipped pressurized with dry air. Release pressure from each coil split through valves in protective caps before removing caps. Do not leave piping open to the atmosphere unnecessarily. Water and water vapor are detrimental to the refrigerant system. Until the piping is complete, recap the system and charge with nitrogen at the end of each work-day. Clean all piping connections before soldering joints. The lower split of face split coils should be first on, last off. Row split coils utilize special intertwined circuits: either splits of these row split coils can be first on, last off.

SUCTION CONNECTION CIRCUIT 1 AIRFLOW SUCTION CONNECTION CIRCUIT 2 DISTRIBUTOR CIRCUIT 1 DISTRIBUTOR CIRCUIT 2

Fig. 11 Example Of Direct-Expansion Coil Distributor And Suction Connections

8.1 Suction Piping

Connect suction piping as shown in (Fig.12) for face split coil or (Fig 13) for row split coil. Suction line from coil connection to end of the 15-diameter-long riser should be same tube size as coil connection to ensure proper refrigerant velocity. Refer to Carrier System Design Manual, Part 3, and size remaining suction line header pressure drop equivalent to approximately 2.5°F. Refer to Fig 15 for piping risers to the compressor.

To minimize the possibility of flooded starts and compressor damage during prolonged shutdown, install an accumulator in the suction line or a solenoid in the liquid line of last-on, first-off split in row applications.

UPPER SPLIT AIRFLOW LOWER SPLIT AIRFLOW TXV SENSING BULB 15 DIAMS MIN 10 DIAMS 8 DIAMS MIN TXV SENSING BULB 15 DIAMS MIN 10 DIAMS 8 DIAMS MIN EQUALIZER LINE SIGHT GLASS SOLENOID VALVE FILTER DRIER EVAPORATOR COIL

Fig. 12 Face Split Coil Suction Line Piping

AIRFLOW 15 DIAMS MIN 10 DIAMS 15 DIAMS MIN 10 DIAMS 8 DIAMS MIN 8 DIAMS, MIN EVALIZER LINE SIGHT GLASS SOLENOID VALVE FILTER DRIER EVAPORATOR COIL

Fig. 13 Row Split Coil Suction Line Piping

8.2 Expansion Valve Piping

Distributor nozzles and thermostatic expansion valves are factory or field supplied.

Note:-

Factory supplied distributor nozzle sizes are marked on coil cover label. Be sure that correct nozzle is installed in each distributor before installing expansion valve.

UPPER SPLIT AIRFLOW TXV SENSING BULBS EQUALIZER LINE 2 1 2 TXV LIQUID LINE FOR COIL CONNECTIONS 1 & 2 SOLENOID VALVE FILTER DRIER LOWER SPLIT SIGHT GLASS EQUALIZER LINE TXV EQUALIZER LINE 3 & 4 3 4 SIGHT GLASS LIQUID LINE FOR COIL CONNECTIONS 3 & 4 SOLENOID VALVE FILTER DRIER SUCTION LINE FOR COIL CONNECTIONS 1 & 2 SUCTION LINE FOR COIL CONNECTIONS 3 & 4

Fig. 14 Double-Circuited Face Split Coil Manifolding (Typical)

TO COMPRESSOR 40° Elbow 90° Elbow Compressor above double rrear Compressor above single rrear

Fig. 15 Suction Line Riser Piping

AIRFLOW UPPER SPLIT TXV SENSING BULBS EQUALIZER LINE LOWER SPLIT 2 1 2 TXV LIVID LINE FOR COIL CONNECTIONS 1 & 3 SIGHT GLASS SOLENOID VALVE FILTER DRIER EQUALIZER LINE SUCTION LINE FOR COIL CONNECTIONS 2 & 4 TXV LIVID LINE FOR COIL CONNECTIONS 2 & 4

Fig. 16 Double-Circuited Row Split Coil Manifolding (Typical)

9.0 GUIDE TO STARTING UP

9.1 Ensure that all construction debris are removed from the interior of the unit.
9.2 Install filter media in all filter section. When roll filter are used, ensure that the filter media is correctly installed and that the roll filter mechanism is functioning property.
9.3 Check that the fan, motor bearing and linkages are adequately lubricated.

a) Bearings are normally shipped full of grease for corrosion protection and may run warm temporarily on start up until excess grease has been discharged.

9.4 Hand operate all linkages, such as variable inlet guide vanes and dampers to check for freedom of movement.
9.5 Check tightness of bearing set screws or locking collars.
9.6 Check tightness of set screws on blower wheel hub and pulley.
9.7 Double check the alignment and tension of the V-belts.

9.8 VERY IMPORTANT

Before energising any power to the unit, double check that all restraints that might have been used during shipping are removed from the fan shaft. The fan shaft and motor shaft must both be free-wheeling before the power is turned on. Remove all holding down bracket used to prevent the fan and motor base moving during transit.

9.9 Check the fan speed with a strobe type tachometer, or use an approximation technique with the following formula. Obtain the motor RPM from the fan motor plate. Measure the fan and motor pulley outer diameter (OD).

$$ \text { Fan RPM } = \text { Motor RPM } \times \frac {\text { Motor Pulley OD }}{\text { Fan Pulley OD }} $$

$$ e g. \text { Nameplate Motor RPM } = 1 5 0 0 $$

$$ \text { Motor Pulley OD } = 2 0 0 \mathrm{mm} $$

$$ \text { Fan Pulley OD } = 3 0 0 \mathrm{mm} $$

$$ \text { Fan RPM } = 1 5 0 0 \times \frac {2 0 0}{3 0 0} = 1 0 0 0 $$

Check that this fan RPM measured or calculated is approximately equal to the speed shown on the sticker. If the fan RPM measured or calculated, exceeds the value shown on the sticker by much, re-balancing of the fan in the field may be required.

In doubt, please refer to your nearest Carrier representatives.

9.10 Check the direction of rotation arrow label on the drive side of the fan housing indicates the correct direction of rotation. (Refer Fig 17)

CARRIER 39G - VERY IMPORTANT - 1

natural_image Pure technical diagram of a circular mechanical component with no text or symbols

Backward Curved

CARRIER 39G - VERY IMPORTANT - 2

natural_image Pure mechanical diagram showing concentric circles with a directional arrow, no text or symbols present

Forward Curved
Fig. 17

9.11 Check the vibration level. If excessive vibration occurs, check the following :-

a) Variable pitch pulleys.
Normally variable pitch pulley specified to make the job of air balancing easier. Once the air balance of the system has been accomplished, replace the variable pitch pulley with the correct fixed pitch pulley for continuous application.
b) Drive misalignment.
c) Mismatched, worn or loose V-belts.
d) Blower wheel or pulley loose on the shaft.
e) Loose bearings.
f) Loose mountings.
g) Motor out of balance.
h) Pulleys (eccentric) or out of balance.
i ) Vibration isolation improperly adjusted.
j) Out of balance or corroded blower wheel (re-balance or replace as necessary).
k) Accumulation of material on blower material (remove as necessary).
I) Shipping brackets preventing the fan housing from moving during shipment. These must be removed prior to start-up.

9.12 Chilled Water and Hot Water Coil.

To vent the coils, proceed as follows :-

a) Close all coil water supply and return main valves.
b) Open all vents but no more than 2 full turns.
c) If vent is clogged up with dirt it may be necessary to remove needle valves from vents and clean as necessary.
d) Open coil water supply and return valves. Fill coil with water until all air is expelled. This occurs when the hissing sound from the vent stops and only water is oozing out from the vent.
e) Close vent needle valves.

CARRIER 39G - Chilled Water and Hot Water Coil. - 1

CAUTION

The venting procedure for hot water coil must be done when the water is not heated up.

9.13 Direct Expansion Coil

Charge refrigerant in accordance with the recommendation as shown in the Installation Operating and Maintenance instructions for the condensing unit.

10.0 GUIDE TO SERVICING

10.1 Review the safety considerations at the beginning of these instructions. Good safety habits are important tools when performing servicing procedures.
10.2 Use a strobe type tachometer or calculate as per item 9.9.
10.3 To replace the fan motor, proceed as follows :-

a) Shut off the power of the motor.
b) Disconnect the tag power wires at motor terminals.
c) Loosen motor brace-to-mounting rails attaching bolts. Loosen belt tensioning bolts to adjust the motor position so V-Belts can be removed without stretching over grooves.
d) Mark belts as to position. Remove and set aside belts, tag as necessary.
e) Remove motor to motor bracket hold down bolts.
f) Remove motor pulley and set aside.
g) Remove the motor.
h) Install the new motor. Re-assemble by reversing steps a to f. Be sure to re-install multiple belts in their original position. Use a new set if required. Do not stretch belts over the pulleys. Align belts as per item 7.3.
i) Re-connect motor leads and restore power. Check fan proper rotation as described in item 9.10 Start-Up procedure.

10.4 To clean the coil, spray mild detergent solution on the coils with garden type sprayer. Rinse with fresh water. Check to ensure that the condensate line is not clogged up.

10.5 Winter shutdown for chilled water coil, proceed as follows :-

1) Anti freeze methods of coil protection.
a) Close coil water supply and return valves.
b) Drain coil as follows :

Method 1

"Break" flange of coupling at each header location, separate flange or coupling connection to facilitate coil drawing.

Method 2

It is recommended that the auxiliary drain be added to coil piping if yearly “Winterizing” of coils is anticipated. This auxiliary piping should be located at the highest and lowest point on the respective header connection for each coil. Hence, to drain the coil, open both valves to the auxiliary drain piping.

c) After coil is drained, Method 1, connect line with a service valve and union from upper nozzle to an anti freeze reservoir. Connect a self priming reversible pump between the low header connection and the reservoir. Method 2, make connection to auxiliary drain valves.
d) Fill reservoir with any inhibited anti-freeze acceptable to local authority codes.
e) Open service valve and circulate solution for 15 minutes, then check its strength.
f) If solution is too weak, add more anti-freeze until desired strength is reached, then circulate solution through coil for 15 minutes or until concentration is satisfactory.
g) Remove upper line from reservoir to reversible pump. Drain coil to reservoir and close service valve.
h) Break union and remove reservoir and it lines.
i) Leave coil flanges or coupling open and auxiliary drain valves open until spring.

10.6 Coil Removal

a) (Refer to Fig. 6 and 7) for service clearance area.
b) For chilled water coil, shut off the valves.
c) Disconnect the chilled water and condensate piping.
d) Remove coil section panel (all screws are located on the inside of the unit).
e) On header end, remove screws holding the block off and the coil casing.
f) Slide coil and baffles out of unit.
g) Lift coil using hooks at the coil casing. Do not lift by header or center of coil.
h) Reinsert coil by reversing order of procedures listed.
i) Apply sealant as necessary to edges to ensure air tightness.

10.7 Fan Shaft and Bearing

a) Disconnect power supply to fan motor.
b) Use wooden blocks to prevent the fan and motor assembly from free floating over the anti-vibration mounts.
c) Loosen motor frame adjustment to release belt tension. Remove belts.
Caution: Do not stretch belts over the pulley. Damage to belt can result.
d) Loosen bolts on bushing of pulley and remove bushing, then the pulley.
e) Loosen bearing set screw and locking collar. Drive eccentric type collar in direction opposite to shaft rotation.
f) Remove bearing while observing the following precaution. (Refer 10.8).

10.8 Blower Wheel Replacements

a) There are two type of DIDW centrifugal fans used with the 39G unit.

i) Backward Curved.

ii) Forward Curved.

b) All blower wheel and fan shaft are designed to be removed through fan housing inlet. Generally, there should be no need to disconnect the flexible connection and duct work.

CARRIER 39G - Blower Wheel Replacements - 1

CAUTION

1) Block fan wheel when removing the shaft to prevent damage to the inlet cones.
2) Use wooden blocks to prevent the fan and motor assembly from free floating over the anti-vibration mounts.
3) There may be instances where the location of the access door is not directly in line with the centre of the shaft. Here, it is necessary to remove the intermediate post, adjacent panel and door assembly. Apply sealant as necessary when these items are re-installed.
4) Exercise procedure to remove fan shaft and bearing as outlined earlier.
5) Remove bolts and nuts holding frame to the fan housing. Only the frame on the side where the blower wheel is to be removed out is required to be dismantled.
6) Removed bolts holding frame inlet cone or inlet guide vane assembly and remove accordingly.
7) Remove fan wheel and shaft as assembly.

10.9 Lubrication

Fan bearings are/not permanently lubricated. Advisable to top-up Lithium base grease every 3 months.

10.10 Filters

The 39G unit can be supplied with or without filters from the factory. There are 3 types of standard filters available.

a) High velocity panel filters (Side/Front withdrawal type).

b) Low velocity panel filters (Side/Front withdrawal type).

c) Bag filters (Side/Front withdrawal type).

d) HEPA filter EU13 particle board frame.

Notes:-

The high velocity filter frame are design to accept filter media cells with aluminium or steel frame.

* HVF & LVF Media-these filters shall be of the washable / disposable 48mm deep plated panel type, gravimetric efficiency 85% to 93% to ASHRAE 52-76.

BF Media-these bag filters shall be of the disposable dry media type, deep bed, fixed panel type, average gravimetric efficiency 85% to ASHRAE 52-76.

For other types of filters, please contact your nearest Carrier representatives.

APPENDIX 1 : ASSEMBLY FAN AND MOTOR BASE
5 2 SEE DETAIL A 7 3 1 6 4 DETAIL A SCALE : NTB Item Description 1 Belt Tensioner 2 Fan Channel 3 Channel Hat 4 HEX, Bolt M8-25L 5 Motor Channel 6 Nutsert 8mm, Large Flange 7 Spring Isolator 8 Strut Channel Nut M12

APPENDIX 2 : ASSEMBLY FAN AND MOTOR BASE
⑦ ⑥ ⑤ SEE DETAIL A ③ ④ SIT ON FRAME ⑧ ① ② ⑨ DETAIL A SCALE : NTB option

ItemDescription
1 Belt Tensioner
2 Bolt, 5/8" Dia. 125mm LG Adjustment
3 Bolt, 5/8" Dia. 40mm LG
4 Fan Base 'L' angle 3" x 3" x 5mm thick
5 Channel Hat
6 Adjustment Bracket
7 Motor Base 'L' angle 3" x 3" x 5mm thick
8 Spring Isolator
9 Assy, Cap Isolator

FILTER TYPE, DIMENSION AND QUANTITY FOR EACH AHU SIZE

PART NAME PART NO.AHU SIZE
06/086/0907108/1109/1209/1309/1410/1511/17131714/1814/2016/2118/2218/2520/25212522/2522/3022/3426/34
a) HEPA Filter EU13 Particle Board Frame
H289 X W595 mm 3GA509-904 - 2 2 - -2232446
H391 X W495 mm 3GA509-943 - 2 - 2 2 - 8 -
H391 X W595 mm 3GA509-944 1 - 11224233
H595 X W595 mm 3GA509-902 -24466812121212
b) HEPA Filter EU13 Aluminium Frame
H289 X W595 mm 3GA509-920 - 2 2 - -22324463
H391 X W495 mrr3GA509-9512228
H391 X W595 mm 3GA509-952 1 - 11224233
H595 X W595 mm 3GA509-918 -24466812121212
c) HEPA Filter EU14 Particle Board
H289 X W595 mm 3GA509-925 - 2 2 - -22324463
H391 X W495 mm 3GA509-953 - 2 - 2 2 - 8 -
H391 X W595 mm 3GA509-954 1 - 11224233
H595 X W595 mm 3GA509-923 -24466812121212
d) HEPA Filter EU14 Aluminium
H289 X W595 mm 3GA509-941 - 2 2 - -22324463
H391 X W495 mm 3GA509-961 - 2 - 2 2 - 8 -
H391 X W595 mm 3GA509-962 1 - 11224233
H595 X W595 mm 3GA509-939 -24466812121212
e) 1" Bag Filter 529mm L (EU5)
H289 X W595 mm39GA509-373234445-
H391 X W495 mm39GA509-37522
H391 X W595 mm 39GA509-376 1 - - 2 2 48
H595 X W595 mm 39GA509-630 - 2 -
H595 X W289 mm39GA509-63122223333
H595 X W391 mrr39GA509-632112233----
H595 X W595 mm39GA509-378244668121212121520
f) 1" Bag Filter 529mm L (EU6)
H289 X W595 mm39GA509-230234445-
H391 X W495 mm39GA509-23222
H391 X W595 mm 39GA509-233 1 - - 2 2 48
H595 X W595 mm 39GA509-621 - 2 -
H595 X W289 mm39GA509-62222223333
H595 X W391 mm 39GA509-623 - - 1 1 -23
H595 X W595 mm39GA509-2352446668121212121520
g) 1" Bag Filter 529mm L (EU7)
H289 X W595 mm39GA509-208234445-
H391 X W495 mm39GA509-21022
H391 X W595 mm 39GA509-211 1 - - 2 2 48
H595 X W595 mm 39GA509-618 - 2 -
H595 X W289 mm39GA509-619222223---33
H595 X W391 mm 39GA509-620 - - 1 1 -233----
H595 X W595 mm39GA509-213244666812121212121520
h) 1" Bag Filter 529mm L (EU8)
H289 X W595 mrr39GA509-240222----3-4--445-
H391 X W495 mm39GA509-242
H391 X W595 mm 39GA509-243 1 - - 2 2 4
H595 X W595 mm 39GA509-624 - 2 -
H595 X W289 mm39GA509-62522-----2---2------33
H595 X W391 mm 39GA509-626 - - 1 1 -
H595 X W595 mm39GA509-245
i) 1" Bag Filter 529mm L (EU9)
H289 X W595 mm39GA509-27022---2----3-4--445-
H391 X W495 mm39GA509-615
H391 X W595 mm 39GA509-271 1 - - 2 2 4
H595 X W595 mm 39GA509-627 - 2 -
H595 X W289 mm39GA509-62822---------2---2-----33
H595 X W391 mm 39GA509-629 - - 1 1 -
H595 X W595 mm39GA509-272
j) 2" HVF Filter Washable (G03)
H289 X W595 mm 39GA509-038 - - 2 2 - -
H391 X W495 mm 39GA509-040 - 2 - - 2 2 - -
H391 X W595 mm39GA509-041 1 - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - - - 1 1 - -0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0,0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0 .0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0 0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0 ,0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.,0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0..0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0,.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0,.0.0.0.0.0.0.0.0.0,0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0.0,0.0.0.0.0.0.0.0.0.0.0.0,0.0.0.0.0,0.0.0.0,0.0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,.0.0.0.0.0.0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0,.0.0.0.0.0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0,.0.0.0.0.0,0.0,0.0,0.0,0.0,0.0,0.0,0.0,0,.0.0.0.0.0,0.0,0.0,0.0,0.0,0.0,0.0,0,.0.0.0.0.0,0.0,0.0,0.0,0,.0.0.0.0,0,.0.0.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,0,.0.0.0.0,0,.0.0.0,0,.0.0.0,0,.0.0.0,0,.0.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0,0,.0,0,.0,0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,0,.0.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,0,.0.0.0,0,.0.0,0,.0.0,0,.0.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,.0,,0,.0.0.0.0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,0,.0,

NOTE: Dimension in mm.

DIMENSION

Unit sizeFan SizeMotor Range (HP)Nominal Capacity (kW)Nominal Airflow @ 2.5m m/s (€/s)Section LengthFAN (Vertical Length)FAN (Vertical Height)Unit HH* (mm)Unit Width (mm)Unit HV** (mm)
MXB (G)FilterAccess (C)Coil (B)Fan (A)
HVF (F)LVF (E)BF (D)
0608160 11.510.2552500 300600 600600 600900600800120060
180 11.5
0609180 1.5~ 3 60014.1756500 300600 600600 600900600600900 1200
200 1.5~ 3 700
0711200 1.5~ 319.61118500 300600 600600 6007009007007001100 1400
225 25
0811225 2524.51397500 300600 60060070060090080080011001600
250 25.5
0912250 25.5 70030.7 1711500 300600 600600 60090090090012001800
280 37.5 800
0913280 37.534.51886500 300600 600600 60080090090090013001800
315 47.5
0914315 47.5 80038.32061500 300600 600600 60090090090014001800
355 410 900
1015355 410 900 190049.82642500 300600 6006006009009001000100015002000
400 515
1117400 515 900 9001000 66.13429500 3002100 600 600600 60011001700
4507.5 ~ 151100110011002200
1317400 515 900 9001000 79.34115500 3002300 600 600600 60013001700
4507.5 ~ 151100110011002400
14184507.5 ~ 1590.4 4645500 300600 600600 600110011001100140018002500
50010 ~ 20110012002600
142050010 ~ 20103.95248500 300600 600600 600110011001200140020002600
56010 ~ 201300130013002700
162156010 ~ 20113.66426500 300600 600600 600130013001300160021002900
63015 ~ 251400140015003100
182256010 ~ 20143.28007500 300600 600600 600130018002200
63015 ~ 251400
182563015 ~ 25170.19246500 300600 600600 600140018002500
71015 ~ 301500
202563015 ~ 25183.29957500 300600 600600 600140020002500
71015 ~ 301500
212571015 ~ 30196.310668500 300600 600600 600150021002500
80020 ~ 501700
222671015 ~ 30213.611516500 300600 600600 600150022002600
80020 ~ 501700
223080020 ~ 50256.813484500 300600 600600 600170022003000
90030 ~ 601900
223480020 ~ 50300.215453500 300600 600600 600170022003400
90030 ~ 601900
263490030 ~ 60358.31844450C30060060060C60C190026003400
100040 ~ 752000

*HH - Height Horizontal
**HV - Height Vertical

1) External AHU Length = (Section Length + K) mm

where, K = 50mm (for 25mm casing thickness)

K = 100mm (for 50mm casing thickness)

2) External AHU Width = (Unit Width + K) mm

3) For Horizontal Unit, External AHU Height = (HH + K + 100*) mm

For Vertical Unit, External AHU Height = (HV + 2K + 100*) mm

*100mm is for unit base

4) If the External AHU Length is >1900mm, section will be split into several casing for shipping purposes.

BCDG A E ACCESS HH

HV

Carrier®

Carrier International Sdn. Bhd. Malaysia

Carrier International Sdn. Bhd. (3385-T)

Lot 4, Jalan P/6, 43650 Bandar Baru Bangi,

Selangor, Malaysia.

Tel: 03-8925 8001

Fax: 03-8925 6589

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : CARRIER

Model : 39G

Category : Unité de traitement d'air