CyberPower CPSPI3700EVF380 - Solar panel

CPSPI3700EVF380 - Solar panel CyberPower - Free user manual and instructions

Find the device manual for free CPSPI3700EVF380 CyberPower in PDF.

📄 94 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice CyberPower CPSPI3700EVF380 - page 4
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Solar Pump Controller (AC Drive)
Brand CyberPower
Model CPSPI3700EVF380
Rated Power 3.7 kW
Input Voltage (PV) Up to 750 Vdc
Output Voltage 3-phase, 380-460 Vac
Frequency Range 0.0 - 400.0 Hz
Control Method V/F, Vector, MPPT for solar
Dimensions (W x H x D) 130 x 250 x 175 mm
Enclosure Rating IP20
Operating Temperature -10°C to +60°C
Cooling Forced air (built-in fan)
Display LED keypad with remote option
Communication RS-485, Modbus, optional CANopen
Protection Features Overvoltage, undervoltage, overcurrent, overheat, short-circuit
MPPT Efficiency High efficiency with built-in MPPT algorithm
Warranty Standard manufacturer warranty (check local distributor)
Maintenance Keep clean, ensure adequate ventilation, periodic fan inspection
Safety Standards EN 61800-5-1, CE, UL (check local)

Frequently Asked Questions - CPSPI3700EVF380 CyberPower

What is the maximum PV input voltage for the CPSPI3700EVF380?
The maximum PV input voltage is 750 Vdc. Exceeding this may damage the controller.
Can this controller run a single-phase pump?
No, this controller is designed for 3-phase loads only. Using it with single-phase equipment is dangerous and not supported.
How do I reset the controller after a fault?
Press the RESET key on the keypad, or cycle the power supply after clearing the fault cause. Refer to Chapter 6 of the manual for specific fault codes.
What is the recommended cable size for the main circuit?
For the 3.7 kW model, use cables rated for at least 10 AWG (6 mm²) and tighten terminals to 1.4 Nm as shown in Table 4.2.2.
How to set the controller for solar pumping (MPPT)?
Set parameter A1-03 to 2838 (2-wire initialization), S9-00 to 1 to enable MPPT, and configure PV input parameters in group S9. See section 5.2.1.
What does the 'oH' alarm indicate?
'oH' indicates heatsink overheat. Check ambient temperature, ensure cooling fan is working, and improve ventilation. Reduce load or carrier frequency if necessary.
Can I use a remote keypad?
Yes, the keypad can be removed and mounted remotely using an extension cable (ordered separately). See section 3.5 for details.
How to set PID control for constant pressure?
Enable PID in parameter b5-00, set target and feedback signals in group b5, and assign analog inputs accordingly. Default PID values are suitable for many applications.
What is the default acceleration time?
The default acceleration time (C1-00) is 10.0 seconds from 0 to maximum frequency. Adjust as needed for your pump.
Why does the controller display 'Uv' after power up?
'Uv' means undervoltage. Check that the input voltage matches the controller rating (380-460V) and that all phases are present. Loose connections can also cause this.

User questions about CPSPI3700EVF380 CyberPower

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Solar panel in PDF format for free! Find your manual CPSPI3700EVF380 - CyberPower and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. CPSPI3700EVF380 by CyberPower.

USER MANUAL CPSPI3700EVF380 CyberPower

Reliability. Quality. Value.

5

5

5

Solar5Controller5

CP<PI3700EVF380

CP<PI5500EVF380

User's5Manual5

5

5

5

5

Table of Contents

Chapter 1 | Safety....3

1.1 General Safety ....3

1.1.1 Usage....3
1.1.2 Receiving ....3
1.1.3 Installation .... 3
1.1.4 Wiring....4
1.1.5 Operation 4
1.1.9 Maintenance ....5

1.2 Warning Label....5

Chapter 2 | Product....7

2.1 Product Part....7
2.2 Receiving Checklist......8
2.3 Product Dimensions....9

Chapter 3 | Controller Installation....10

3.1 Installation Environment....10

3.2 Installation Direction and Spacing ....11

3.2.1 Direction....11
3.2.2 <pacing....11
3.2.3 <ide-by-<ide Installation....12

3.3 Keypad and Terminal Cover Installation....12

3.4 Wiring Protection....13

3.4.1 Controller and Input Cable....13
3.4.2 Output Cable Protection for <hort-Circuit <ituations 14

3.5 Keypad Remote Usage ....14

3.5.1 Remote Operation....15
3.5.2 External/Face-Mount 19

Chapter 4 | Wiring....17

4.1 Wiring Safety 17

4.2 Main Circuit....18

4.2.1 Main Circuit >terminal....18
4.2.2 Main Circuit Wiring 18
4.2.3 Main Circuit Cable ightening >orque 20

4.3 Control Circuit....20

4.3.1 Control Circuit >erminals....21
4.3.2 Control Circuit Wiring 23
4.3.3 Control Circuit Cable ightening >orque 29

4.3.4 Ferrule->ype >terminals....26

4.4 I/O Connections....27

4.4.1 NPN and PNP Mode 4.4.2 >terminal A2 Voltage/Current Input 4.4.3 >terminal AM Voltage/Current Output <election.... 28
4.4.4 R<-485 Communication >ermination ON / OFF <witch 29

4.6 Wiring Checklist....31

Chapter 5 | Keypad and Parameters....32

5.1 Keypad ....32

5.1.1 %eys and Displays....32
5.1.2 %eypad Display 34
5.1.3 %eypad Programming....36

5.2 Parameter List....37

5.2.1 Parameters setting for <olar Controller 37
5.2.2 Parameters setting for the other applications 38

Chapter 6 | Troubleshooting....88

6.1 Alarm and Fault Displays 88

Chapter 1 | Safety

1.1 General Safety

<afety Information:

Warning: Indicates highly dangerous consequences such as fire, serious injury and death when failing to comply with the instructions.

Caution: Indicates dangerous consequences such as moderate injury and equipment damage when failing to comply with the instructions.

1.1.1 Usage

Danger5
>he controller is used to control the speed of 3 phase synchronous and asynchronous loads, which must not be used for single phase or other purposes. Failure to comply could cause controller damage or serious injury by fire.
>he controller must not be used in any medical equipment in which human life may involve.
>he controller is manufactured according to strict quality control standard. However, bypass the safety protection in case the controller failure causes death or serious injury.

1.1.2 Receiving

Warning5
Do not install damaged controller or any controller without complete components inside. Failure to comply could result in accident.

1.1.3 Installation

Warning5
Carry the controller by the bottom as carrying by the front cover may cause injury and damage from the main body of the controller falling.Attach the controller to metal or other nonflammable materials. %eep away from heat and flammable items.A control panel must have cooling fans, air vents and room for ventilation when the controller is installed inside.

1.1.4 Wiring

Danger5
Allow only qualified electrical engineers to install the controller. Failure to comply could cause electrical shocks to personnel or damage to the controller.Ensure the power supply is off when connecting. Failure to comply could cause electrical shocks.Ensure the ground terminal PE is properly wired. Failure to comply could cause electrical shocks from the controller cover. >herefore ground the controller and for personnel safety.Do not touch the main circuit terminal. %eep the main circuit off controller cover to avoid electrical shocks.>he terminal for braking resistor is B1 and B2. Do not connect it to any other terminals. Failure to comply could cause a fire.
Warning5
Do not connect three-phase power supply to terminals U, V and W. Failure to comply could damage the controller.An output reactor is recommended when the cable connecting between the controller and is over 100 meters. Failure to comply could result in controller damage with overcurrent caused by over-distributed capacitance.Never connect the output terminals to capacitors or unapproved LC/RC filters. Failure to comply could damage the controller components.<eparate the controller main circuit cables and control circuit cables. Failure to comply could cause interference to the control signalsEnsure the phase of power supply and rated voltage match the label on the controller. Failure to comply could controller damage.

1.1.5 Operation

Danger5
Connect the power after completion of wiring and closing the front cover. Opening the front cover when the power is on could cause an electrical shock.%eep other personnel off the equipment when setting the controller fault restart and momentary power loss restart functions. Failure to comply could cause damage to the personnel and equipment.Once the controller is powered, the terminals are live even when controller is not in operation. >ouching the terminals could cause electrical shocks.Cancel run command before resetting the alarm and fault. Failure to comply could cause physical injury.
Warning5
Do not start or stop the controller by connection or disconnection the power supply. Failure to comply could cause controller damage.
Ensure the and equipment are in proper use before operation. Failure to; comply could damage the equipment.
>he temperature of the braking resistor and heatsink could be very high during operation. Do not touch it or it could result in scald.
For lift applications, please install mechanical brakes.
Adjust a few parameters only if necessary as the defaults are optimum settings for most of applications.
Editing parameters indiscriminately could cause equipment abnormal operation.
Interlock the electricity supply with AC controller supply when both are available to a load.

1.1.6 Maintenance

Danger5
Do not touch the main circuit of the controller when power is on. Failure to comply could cause electrical shocks.Disconnect the power supply before opening the front cover of the controller.Maintain the controller only when the CHARGE indicator light is off or 5 minutes after turning off power supply, so as to avoid charged capacitors causing physical injury.Allow only qualified electric engineers and electrician to maintain, repair and replace the AC controller modules.
Warning5
>he release of breaker on the AC controller primary side could be caused by incorrect wiring, short circuit and damaged controller components. Investigate and remove the problem before reconnecting the breaker.Do not use a megger (insulation resistor) to test the controller control circuit. Failure to comply could cause controller damage.

Notice:

All the instruction photographs and diagrams of opened controller in this manual are only for illustration. Do not attempt to operate any AC controllers with the cover opened.

1.2 Warning Label

he warning label is on the front of the controller. Please read it carefully and follow the instructions.

  • Read the user manual before operation.
    Risk of electrical shock. <hut off main power and wait for 5 minutes before servicing.
    ■ Hot surface. Risk of burn.

OK CC OR ON FN MEN FNZ FWD REV LO RE RESET ENTER RUN STOP WARNING - Read the user manual before operation - Run of remote drive. Short/long power and switch 3 seconds before mounting - Run off bus. Warning Label

Chapter 2 | Product

2.1 Product Part

Exploded view diagram of an electronic device with labeled components from A to L

A - Heatsink

B - Cooling fan

F->terminal cover screw

G - Front cover

H - U < B port

I ->erminal cover

+ - Front cover screw

% ->terminal cover screw

L-%eypad

2.2 Receiving Checklist

Check the following when receiving the controller:

1. Is the packaging box in good condition? Any damage or damp ?If so, contact the distributor or local CyberPower representative.
2. Is the model label on the box same as what you purchased?If not, contact the distributor or local CyberPower representative.
3. After opening the box, is there any damp mark inside the box? Any damage or crack on the controller enclosure?If so, contact the distributor or local CyberPower representative.
4. Does the controller nameplate show the same model number as the carton label?If not, contact the distributor or local CyberPower representative.
5. Are the manual and keypad in the carton?If not, contact the distributor or local CyberPower representative.

2.3 Product Dimensions

CyberPower CPSPI3700EVF380 - Product Dimensions - 1

W W1H W11 DD1 <HΦΦ1 Φ21D1
130[5.12]118[4.65]250[9.84]235[9.25]175[6.88]64[2.51]5.2[0.20]5.5[0.22]22[0.86]28[1.1]

Unit: mm/inch

Chapter 3 | Controller Installation

3.1 Installation Environment

0 ensure the optimum controller performance, install the AC controller in a proper environment specified below.

EnvironmentConditions
Area of Use Indoors
-10°C to +60°C (IP20 enclosure)Do not install the controller in environments with wide temperature fluctuations so as to ensure the controller reliability.When the controller is installed in an enclosure cabinet, make sure the cooling works properly to keep the temperature within the specified levels.Do not allow the controller to freeze.When controllers are installed side-by-side in a cabinet, follow the instruction illustrated in Figure 3.2 to ensure the air flow.
HumidityUnder 90% RHFree of condensation
>temperature-20°C to +60°C
<urrounding AreaFree from water, oil, metal shavings or other foreign materials.Free from flammable materials (e.g., wood)Free from harmful gases and liquidsFree from direct sunlightFree from oil mist, corrosive gas, flammable gas or dust.Free from radioactive materialGreen Class 2 or above
AltitudeUp to 1000 m without derating. Up to 2000 meters with 1% rated current derated for every 100 m counted from 1000 m.
Vibration10 to 20 Hz at 9.8 m/s220 to 55 Hz at 5.9 m/s2
EnclosureIP20

3.2 Installation Direction and Spacing

3.2.1 Direction

Install the AC controller upright for better cooling.

OK
Line drawing of a mechanical device with control panel and ventilation slots (no text or symbols)

a. Upright installation

NG
Line drawing of a portable electronic device with control panel and buttons (no text or symbols)

b. Horizontal installation

NG
Line drawing of a portable electronic device with control panel and buttons (no text or symbols)

c. Transverse installation

3.2.2 Spacing

<ingle Controller Installation

Install the AC controller as illustrated below to ensure the required space for airflow and wiring.

A B A B A A

A - Minimum 50 mm; B - Minimum 30 mm

C C

C – Minimum 150 mm
Illustration of a server rack with blue upward arrows indicating data flow or operation (no text or symbols present)

3.2.3 Side-by-Side Installation

Install the AC controllers as illustrated below to ensure the required space for airflow and wiring.

A C B A B A

A - Minimum 50 mm
B - Minimum 30 mm
C - Minimum 10 mm

Technical line drawing of a mechanical device with internal channels and dimension labels (D), no readable text or symbols present.

D - Minimum 150 mm

3.3 Keypad and Terminal Cover Installation

It is not necessary to remove the keypad before wiring. You just need to loosen the terminal cover screw and remove the terminal cover.

his model enclosure is non-metal. Loosen terminal cover screw and remove terminal cover for wiring. After wiring, affix the terminal cover back in position and tighten the screw. For wiring instructions and screw tightening torque please refer to Chapter 4.

Line drawing of an industrial control unit with buttons and a rotary knob (no text or symbols)

Step 1: Loosen the Screw

Illustration of a hand holding an industrial control device with buttons and ports, showing a left-hand rule for change (no text or symbols present)

Step 2: Remove the Terminal Cover

Illustration of a hand inserting a device into a rack, showing internal components and a directional arrow (no text or symbols)

Step 3: Affix the Terminal Cover After Wiring

Technical line drawing of an industrial control unit with labeled buttons and a rotary dial indicator

Step 4: Tighten the Screw

3.4 Wiring Protection

3.4.1 Controller and Input Cable

Please refer to the following figure for the proper wiring, DC switch is recommended to be installed in PV input side

Note: Ensure the PV input voltage doesn't over 750Vdc at any condition, otherwise may damage the controller.

PV String DC Switch Load

3.4.2 Output Cable Protection for Short-Circuit Situations

If the output cables are properly selected according to the controller rated current, the controller itself is fully capable of protecting the load and output cables in case of short-circuit situations.

Note: If a single controller runs more than 1 load, a separate thermal overload switch or a circuit breaker is required.5

3.5 Keypad Remote Usage

%eypad mounted on the controller can be removed and connected to the controller using an extension cable to facilitate operation when the controller is installed in a location where it cannot be easily accessed. It can also be permanently mounted remote locations such as panel doors using an extension cable and an installation support set.

3.5.1 Remote Operation

3.5.1.1 Remote Operation

Drive Cable Connector Keypad USB WARNING A. A.

3.5.2.2 Panel Cut-Out Dimensions

21.6 2.7 93.0(2X) 35.9 36.0(2X)

Chapter 4 | Wiring

4.1 Wiring Safety

Danger5
■ >urn off all the power to the equipment before wiring. Wiring during power on could ca electrical shocks to personnel.
■ Allow only qualified personnel for installation, wiring, repairing and parts replacement.
■ Capacitors in the controller may still be charged for a short time after shutting off the power. Wait for the amount of time specified on the controller before any maintenance.
■ Never touch input or output power cables. Do not connect any circuit to controller enclosure.
Warning5
■ Properly connect the loadground terminal. Contacts between the loadground terminal and loadenclosure could cause electrical shocks or a fire.
■ Ensure terminal screws are all tightened. Loose connection to the main circuit could cause overheat or a fire.
■ Verify if the rated voltage of the controller matches the voltage of the incoming power supply before applying power.
■ Perform all wiring as specified in the wiring diagrams provided when installing braking options. Failure to comply could result in controller, braking components damage or a fire.
■ Do not disconnect the loadfrom the controller while the controller is outputting voltage.
■ Do not use unshielded cable for control circuit wiring. Failure to comply could cause abnormal operation of controller.
■ Use shielded twisted-pair cables and connect the shield to ground terminal of the controller.
■ Do not modify the controller circuits. Failure to comply could cause controller damage.
■ Ensure all connections are correct after connecting the controller with other controllers.
■ Rubber grommets located on conduit box shall be removed and replaced with conduit hubs in the end use installation.
■ Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and a additional local codes", or the equivalent

4.2 Main Circuit

4.2.1 Main Circuit Terminal

R/L 1 (PV+) S/L 2 (PV-) U/T 1 V/T 2 W/T 3 Load E

Table54.2.15Main5Circuit5Terminals5

Terminal5Name55Terminal5Description5
R/L1 (PV+),</L2 (PV-)PV string input terminal
U/>1, V/>2, W/>3 3Ph power output terminal
B1, B2, +1, +2 Do not use in solar controller application
E Ground terminal

4.2.2 Main Circuit Wiring

4.2.2.1 PV Input Terminal

  • Install a DC switch between PV string output and PV+/PV-terminal on controller. <urge protector controller is also suggested to install.
    ■ Connect PV input wires from string PV+/PV- to DC switch; DC switch to PV+/PV- terminal of controller.
    ■ Ensure the max. voltage of PV will not over 750V at any condition, or may damage the controller.

4.2.2.2 Power Output Terminal

■ Connect AC controller output terminals U/>1, V/>2 and W/>3 to loadinput terminals U, V and W respectively. Ensure the loadand controller terminals are in same phase sequence or the loadwill rotate reversely.

■ Do not connect power cable to output terminals of the controller. Failure to comply could cause controller damage and a fire.

4.2.2.4 Ground Terminal

■ Use grounding cables of dimensions regulated by electrical equipment standard. Do not use share the same grounding cable with welding machines or any controller requiring large current. Failure to comply could cause controller or equipment malfunction.
Do not wind the grounding cable when multiple controllers are installed. Failure to comply could cause controller or equipment malfunction.
■ Ensure the neutral of the input side and controller terminal "±" are grounded according to the local electrician regulations. >N and >> system are suggested for the controller primary side.

4.2.2.5 Jumper

his controller complies with the European LVD standard EN 61800-5-1 (2007) reducing the current leakage to below 10mA DC under testing condition regulated by IEC 60990 (1999).
■ Follow the instructions below to remove the jumper if an even lower current leakage to a even lower level.
■ Removing the jumper may increase the signal interference.

Technical diagram of an electronic device rear panel with labeled ports and a red arrow indicating a component or connection.

4.2.3 Main Circuit Cable Size and Tightening Torque

able 4.2.2.

  1. he recommended cables are 600 V vinyl-sheathed cables which have continuous temperature tolerance up to 75°C with ambient temperature tolerance up to 40 °C, wiring distance up to 100 meters and conditions suitable for on Normal Duty mode.

  2. terminal +1, +2, B1 and B2 are only for connecting DC reactor and braking resistor options. Do not connect it to other controllers.

  3. Consider the amount of voltage drop when selecting cable sizes. Increase the cable size when the voltage drop exceeds 2% of the Load Rated voltage. >he amount of voltage drop can be calculated using the following formula:

Line drop voltage (V) = 3 × cable resistance (Ω/km) × cable length (m) × current (A) × 10 -3

Table54.2.25 Cable5Size5and5Tightening5Torque58Three-phase54005V)5

Controller Rating>terminalAsia UApplicableApplicable>terminal>ightening CableApplicableCableApplicableCable>orque Nm (lb.in.)>terminal>orque Nm (lb.in.)
ApplicableCableApplicableCableApplicable>threadApplicableCableApplicableCable>orque Nm (lb.in.)ApplicableCableApplicableCable>orque Nm (lb.in.)ApplicableCableApplicableCable>orque Nm (lb.in.)ApplicableCableApplicableCable>orque Nm (lb.in.)ApplicableCable>orque Nm (lb.in.)
3.7kWR, <, U, V, W, PE5.35.3 to 8.410 10to 85.35.3 to 8.4M41.57(13.9)

4.3 Control Circuit

■ Multi-function analog input <1 to <8 can be switched between <ink (NPN) mode and he default setting is NPN mode.
■ +V and -V are for analog auxiliary power. Do not connect +V with -V.
■ Analog output is used to connect a frequency meter, current meter, voltage meter and power meter.

4.3.1 Control Circuit Terminals

V-SC S1 S2 S3 S4 S5 S6 S7 S8 PC P1 P2 +V A1 A2 AC FM AM AC MT RP AC MP AC PE R1A R1B R1C R2A R2C

4.3.1.1 Input Terminals

Table54.6.1.15Control5Circuit5Input5Terminal555

>terminal >ype>terminal Code>terminal Name >terminal Description
Multi-Function Digital Inputs<1 Digital input terminal 1 (forward/stop)Photocoupler, 24 V, 8 mA.Use NPN/PNP switch to select multi-function digital input type.>he default is NPN mode.
<2 Digital input terminal 2 (reverse/stop)
<3 Digital input terminal 3 (external fault 1)
<4 Digital input terminal 4 (fault reset)
<5Digital input terminal 5 (multi- step speed 1)
<9Digital input terminal 9 (multi- step speed 2)
<7 Digital input terminal 7 (+og command)
<8Digital input terminal 8 (baseblock (normal open))
<CDigital input common terminal for NPN/PNP mode switch.
Multi-Function Analog Inputs+V Auxiliary power terminal +10V Analog input power+10V
-V Auxiliary power terminal -10V Analog input power-10V
A1Analog input terminal 1(main frequency command)Voltage input0 to 10V / -10V to +10V
A2Analog input terminal 2(auxiliary frequency command)Voltage or current input(0 or 4 to 20mA, 0 to 10V, 0 to 5V
PE Ground terminal>he ground terminal for contro signals to avoid interference.Use shielded cables only.
AC Common terminal for analog signals
M> Loadtemperature signal terminalConnects the temperature sensor of AC loadfor the controller to know the loadtemperature and trigger necessary protections.
Pulse >rain InputsRPPulse train input(frequency command)Input frequency up to 32KHz
PC Common terminal for pulse train signals

4.3.1.2 Output Terminals

Table54.6.1.25Control5Circuit5Output5Terminals555

>terminal >ype>terminal Code>terminal Name>terminal Description
Multi-Function Relay OutputR1ARelay 1 normal openRelay outputDC 30 V, 3 AAC 250 V, 5 A
R1BRelay 1 normal closed
R1CRelay 1 common
R2ARelay 2 normal open
R2CRelay 2 normal closed
Multi-Function Photocoupler OutputD1Photocoupler Output terminal 1 (zero speed)Photocoupler Output48 V, 2 to 50 mA
D2Photocoupler Output terminal 2 (speed agree)
DC Photocoupler Output terminal
Multi-Function Analog OutputFMProgrammable analog output terminal (output frequency)Voltage Output0 to 10V, -10 to +10V
AMMulti-function analog output terminal (output current )Voltage or current output (Selectable) 0 or 4 to 20mA, 0 to 10V
AC Analog common terminal
Multi-Function Pulse Train OutputMPMulti-function pulse train output ( output frequency)32KHz Max
PC Pulse train common terminal

<1> Do not assign frequent switching functions such as ON/OFF to terminals R1 and R2, which may shorten the relay terminal life.

4.3.2 Control Circuit Wiring

The applicable functions in parameter Group E can be assigned to multi-function digital inputs (S1 to S8), multi-function relay outputs (R1, R2), multi-function digital outputs (D1, D2), multi-function analog input (A1, A2) and multi-function analog output (FM, AM). The default settings are listed in Figure 4.3.1.1 and Figure 4.3.1.2.

For safety, always check the emergency stop operation after wiring. Emergency stop circuit is necessary to stop the controller immediately in a safe manner to prevent any injuries.
■ Do not remove the controller covers or touch the circuit boards when the power is on. Failure to comply could cause electrical shocks to personnel.
Separate control circuit wiring from main circuit wiring and other power lines. Failure to comply could cause controller malfunction.
■ Insulate shielded cable with tape to avoid contact with equipment and other signal lines. Improper insulation could cause controller or equipment malfunction.
■ Always use shielded twisted-pair cables to prevent controller and equipment malfunction cause by electrical interference.
■ Ground the shield to the ground terminal of controller. Failure to comply could cause erroneous operation or damage to the controller and equipment. Wire ground terminal and main circuit terminals before wiring control circuit terminals.

4.3.2.1 Digi Input Connection for PLC

graph TD A["Digi Input Connecting 1"] --> B["PLC (High Active/Source/PNP)"] A --> C["External Power Supply"] B --> D["LOAD"] C --> D D --> E["SC (24V)"] F["Source(PNP)"] --> G["NPN/PNPS Switch"] H["Sink(NPN)"] --> I["SC (24V)"] J["Y0-Y7"] --> K["COM0/V0-Y5-Y6-Y7"] L["DC24V-DC0V"] --> M["Load"] style…

graph TD A["Digi Input Connecting 2"] --> B["Source(PNP)"] B --> C["NPN/PNPS Switch"] C --> D["SC(0V)"] D --> E["EVO8000"] F["External Power Supply"] --> G["LOAD"] G --> H["PLC (Low Active/Sink/NPN)"] H --> I["DC24V"] H --> J["DC0V"] K["Y0"] --> L["S1"] M["Y1"] --> N["S2"] O["Y2"] --> P["S3"] Q["Y3"…

4.3.2.2 Digi Input Connection for Water Tower and/or Well

When user wants to use float switch in water tower and/or well to control on/off, please connect the digi inputs to switches and set the parameters as below.

Note: >he switch type for tower and well application is A type (NO) and B type (NC) respectively.

Parameter5Value55Application58with5tower5and5well)5
b1-01 4CyberPower CPSPI3700EVF380 - Digi Input Connection for Water Tower and/or Well - 1 CyberPower CPSPI3700EVF380 - Digi Input Connection for Water Tower and/or Well - 2
E1-00 197
E1-01 198
E1-02 194
E1-03~07 20
Parameter5Value55Application58with5either5tower5or5well)5
b1-01 4CyberPower CPSPI3700EVF380 - Digi Input Connection for Water Tower and/or Well - 3
E1-00 197
E1-01 198
E1-02 194
E1-03~07 20

4.3.3 Control Circuit Cable Size and Tightening Torque

able 4.3.3.1. Use crimp ferrules on the cable ends for simpler and more reliable wiring.

Table54.6.6.15 Cable5Size5and5Tightening5Torque5

>terminal>ightening >orque Nm (lb.in.)Bare Cable Ferrule->ype>terminalCable >ype
ApplicableApplicableApplicableApplicableApplicableCable >ype
<1, <2, <3, <4, <5, <6, <7, <8,, RP, PE, DC, D1,D2M20.23(2.0)0.13 to 1.31(26 to 16)0.13(26)0.13 to 0.33(26 to 22)0.13(26)
R1A, R1B, R1C, R2A, R2CM2.60.59(5.2)0.13 to 2.08(26 to 14)0.13(26)0.13 to 0.33(26 to 22)0.13(26)

4.3.4 Ferrule-Type Terminals

Always use ferrule-type terminals with insulated sleeves. Refer to >able 4.3.3.2. for dimensions. In addition, crimping tool CRIMPFOX ZA-3 manufactured by Phoenix Contact is recommended.

φd1 6 mm L φd2

Table54.6.6.25Ferrule-Type5Terminal5Models5and5Sizes5

Cable <ize mm2 ( AWG)>ypeL ( mm)d1 ( mm)d2 ( mm)Manufacturer
0.25 ( 24) AI 0.25-6YE 10.5 0.82 Phoenix Contact
0.34 ( 22) AI 0.34-6>= 10.5 0.82 Phoenix Contact
0.5 ( 20)AI 0.56-WH141.12.5Phoenix Contact

4.4 I/O Connections

4.4.1 NPN and PNP Mode Selection

Use <ink/<source DIP switch on the control board to set NPN/PNP mode for multi-function digital inputs <1 to <8. (Default: NPN mode)

Source Sink

Figure 4.4.1 Sink/Source DIP Switch

4.4.2 Terminal A2 Voltage/Current Input Selection

<elect voltage or current input at terminal A2

  • o select current as the input type, set DIP switch A2 to I and set parameter E3-09 to 0 (0 to 20 mA) or 1 (4 to 20 mA).

  • o select voltage as the input type, set DIP switch A2 to V and set parameter E3-09 to 2 (0 to 10 V) or 3 (0 to 5 V).

Technical diagram of a device rear panel with labeled components and an inset layout showing two labeled sections V and I.

Figure 4.4.2 DIP Switch A2

Table 4.4.1 DIP Switch A2 Settings 8Terminal A2)

V Voltage input (0 to 10 V or 0 to 5 V)
I Current input (4 to 20 mA or 0 to 20 mA) (default)

Table 4.4.2 Parameter E3-06

No.Parameter Name DescriptionDefault
E3-09>terminal A2 <signal Level<election<elects the signal level for terminal A2.0: 0~20 mA1: 4~20 mA2: 0~10 V3: 0~5 V0, 1, 2, 3 1

4.4.3 Terminal AM Voltage/Current Output Selection

<elect voltage or current output type for terminal AM

  • o select voltage as the output type, set DIP switch AM to V and set parameter E4-04 to 0 (0 to 10 V).

  • o select current as the output type, set DIP switch AM to I and set parameter E4-04 to 1 (0 to 20 mA) or 2 (4 to 20 mA).

Technical diagram of an electrical panel layout with labeled components and a magnified inset showing internal layout.

Figure 4.4.3 DIP Switch AM

Table344436BD1B56WchtoA5AM5Setting58Terminal5AM)555

V Voltage output (0 to 10 V)
I Current output (4 to 20 mA or 0 to 20 mA)(default)

5

Table54.4.45Parameter54-045

No Parameter Name DescriptionDefault
E4-04>terminal AM <signal Level<election0, 1, 2 2

4.4.4 RS-485 Communication Termination ON / OFF Switch

he default of termination resistor for R<-485 communication is OFF. <witch it to ON when the controller is the last in a series of slave controllers. <et this termination resistor on DIP switch R<485 illustrated in Figure 4.4.4.

OFF ON

Figure 4.4.4 DIP Switch RS-485 Termination Resistor

4.6 Wiring Checklist

Table 4.6 Wiring Checklist

No.ItemPage
Power Supply Voltage and Output Voltage
1Power supply voltage is within the voltage range of specified controller input.
2>he loadvoltage matches the controller output specifications.
3>he controller rating matches the loadrating.
Main Circuit Wiring
4An MCCB of proper specifications is connected between the controller and load.
5Power cables are correctly connected to controller input terminals R/L1,,/L3.
6Loadterminals and controller terminals U/>1, V/>2 and W/>3 are in same phase sequence. (Otherwise the loadwill rotate reversely)
7Power supply and loadpower cable complies with electrician regulations.
8>he controller is properly grounded.
9Controller terminal screws of the main circuit and ground are tightened.
10An MC is installed for each loadif a single controller runs more than one loadCyberPower CPSPI3700EVF380 - Wiring Checklist - 1Note:
11When using a braking resistor or braking unit, an MC is installed on the controller input side and able to shut off the power to controller when overloaded.
Control Circuit Wiring
12>wisted-pair cables are used for all controller control circuit wiring.
13
14Options (if any) are properly installed.
15No wiring mistakes.
16Do not use a buzzer to check wiring.
17>he control circuit terminal screws are tightened.
18No cable clippings or screws are left inside the controller enclosure.
19Control circuit wiring and main circuit wiring are separated.

Chapter 5 | Keypad and Parameters

5.1 Keypad

Use the keypad to enter RUN and <>OP commands, display data, fault, alarm and set parameters. >he keypad of EVO 8000 series can be removed and connected to the controller using an extension cable. >he remote keypad can be mounted on control panels with screws thread M4 X P0.7 and the screw length longer than the thickness of panel door.

5.1.1 Keys and Displays

19 18 17 16 15 REV EXT BMR RUN PAJT 8.8.8.8.8 14 13 1 FN1 MENU FN2 10 2 FND REV LU RE 12 3 RESET ENTER 8 11 RUN STOP 4 5 6 7

Figure 5.1.1 Keypad

Table 5.1.1 Keypad Keys and Displays

NoDisplayNameFunction
1CyberPower CPSPI3700EVF380 - Keys and Displays - 2FN1 KeyUser-defined function key for Quick Setting Mode
2CyberPower CPSPI3700EVF380 - Keys and Displays - 3FWD/REV KeyForward/reverse selection
3CyberPower CPSPI3700EVF380 - Keys and Displays - 4RESET KeyMoves the cursor to the right Resets the controller to clear a fault situation
4CyberPower CPSPI3700EVF380 - Keys and Displays - 5RUN KeyRuns the controller
5CyberPower CPSPI3700EVF380 - Keys and Displays - 6MENU KeyEnters or exits the parameter group Switches the displayed menu
6CyberPower CPSPI3700EVF380 - Keys and Displays - 7CyberPower CPSPI3700EVF380 - Keys and Displays - 8UP/DOWN KeySelects parameter numbers, increments and decrements setting value and frequency
7CyberPower CPSPI3700EVF380 - Keys and Displays - 9STOP KeyStops the controller
8CyberPower CPSPI3700EVF380 - Keys and Displays - 10ENTER KeyEnters parameter value, parameter and setting Enters parameter setting menu.
9CyberPower CPSPI3700EVF380 - Keys and Displays - 11LO/RE Selection KeySwitches controller control between the keypad (LOCAL) and an external source (REMOTE)
10CyberPower CPSPI3700EVF380 - Keys and Displays - 12FN2 KeyRetain
11CyberPower CPSPI3700EVF380 - Keys and Displays - 13RUN LightRefer to Table 5.1.2.2
12CyberPower CPSPI3700EVF380 - Keys and Displays - 14LO/RE LightRefer to Table 5.1.2.2
13CyberPower CPSPI3700EVF380 - Keys and Displays - 15RPM LightRefer to Table 5.1.2.2
14CyberPower CPSPI3700EVF380 - Keys and Displays - 16Hz LightRefer to Table 5.1.2.2
15CyberPower CPSPI3700EVF380 - Keys and Displays - 17Fault LightRefer to Table 5.1.2.2
16CyberPower CPSPI3700EVF380 - Keys and Displays - 18Modbus RUN Light Refer to >able 5.1.2.2
17CyberPower CPSPI3700EVF380 - Keys and Displays - 19Modbus ERR Light Refer to >able 5.1.2.2
18CyberPower CPSPI3700EVF380 - Keys and Displays - 20EX> Light Refer to >able 5.1.2.2
19CyberPower CPSPI3700EVF380 - Keys and Displays - 21REV Light Refer to >able 5.1.2.2

5.1.2 Keypad Display

5.1.2.1 LED Display

Table 5.1.2.1 LED Display

Number /LetterLED DisplayNumber /LetterLED DisplayNumber /LetterLED DisplayNumber /LetterLED Display
0CyberPower CPSPI3700EVF380 - LED Display - 19CyberPower CPSPI3700EVF380 - LED Display - 2irCyberPower CPSPI3700EVF380 - LED Display - 3
1ACyberPower CPSPI3700EVF380 - LED Display - 4+CyberPower CPSPI3700EVF380 - LED Display - 5<CyberPower CPSPI3700EVF380 - LED Display - 6
2CyberPower CPSPI3700EVF380 - LED Display - 7bCyberPower CPSPI3700EVF380 - LED Display - 8%t
3CyberPower CPSPI3700EVF380 - LED Display - 9cCyberPower CPSPI3700EVF380 - LED Display - 10LCyberPower CPSPI3700EVF380 - LED Display - 11UCyberPower CPSPI3700EVF380 - LED Display - 12
4dCyberPower CPSPI3700EVF380 - LED Display - 13Mv
5CyberPower CPSPI3700EVF380 - LED Display - 14EnWNil
6FoXNil
7CyberPower CPSPI3700EVF380 - LED Display - 15GCyberPower CPSPI3700EVF380 - LED Display - 16PCyberPower CPSPI3700EVF380 - LED Display - 17yNil
8CyberPower CPSPI3700EVF380 - LED Display - 18HCyberPower CPSPI3700EVF380 - LED Display - 19qNilZNil

5.1.2.2 LED Indication

Table 5.1.2.2 LED Indication

Indicator LightLit Blinking Off
CyberPower CPSPI3700EVF380 - LED Indication - 1Controller in operationController in decelerationOutput frequency below the minimum frequencyController not in operation
CyberPower CPSPI3700EVF380 - LED Indication - 2Control from Local NilControl from Remote
CyberPower CPSPI3700EVF380 - LED Indication - 3Displaying output speedNil Nil
CyberPower CPSPI3700EVF380 - LED Indication - 4Displaying output frequencyNil Nil
CyberPower CPSPI3700EVF380 - LED Indication - 5During fault Nil Normal operation
CyberPower CPSPI3700EVF380 - LED Indication - 6Communication connectedNil Nil
CyberPower CPSPI3700EVF380 - LED Indication - 7Communication error Nil Nil
CyberPower CPSPI3700EVF380 - LED Indication - 8Allows Run commands only from a remote sourceNilAllows Run commands only from keypad
CyberPower CPSPI3700EVF380 - LED Indication - 9Rotating reversely NilNil

5.1.3 Keypad Programming

%eypad Display Menu <tructure

ER, MENU, UP, DOWN and RE to monitor and edit settings.

graph TD A["060.00"] -->|MENU| B["R1"] B -->|ENTER| C["R1-00"] C -->|ENTER| D["00000"] D -->|ENTER| E["End"] B -->|MENU| F["R1-01"] F -->|UP/DOWN/RESET| G["b1"] G -->|UP/DOWN/RESET| H["R1-01"] H -->|UP/DOWN/RESET| I["00001"] I -->|UP/DOWN/RESET| J["(1sec)"]

=quick setting mode: User must assign the function to the FN1 key in advance so as to quickly set the parameter by pressing FN1 key.

graph TD A["06000"] -->|FN1| B["b"] B -->|FN1| C["0"] B -->|ENTER| D["00000"] D -->|ENTER| E["End"] E -->|(1 sec)| B B -->|MENU| F["00001"] F -->|UP/DOWN/RESET| G["0606"] G -->|UP/DOWN/RESET| H["00001"]

=quick monitor mode: Press FN2 key to quickly monitor part of the parameters and press UP and Down key to switch the parameter.

graph TD A["060.00"] --> B["FN2"] B --> C["800.32"] C --> D["U1-03 (Output Current)"] D --> E["FN2"] E --> F["800.0"] F --> G["U1-06 (Main Circuit DC Voltage)"] G --> H["FN2"] H --> I["800.0"] I --> J["U1-05 (Output Voltage)"] J --> K["FN2"] K --> L["444.0"] L --> M["U1-04 (Motor Speed)"] M --> N["F…

During-operation setting mode: Controller frequency is adjustable during operation in Local mode

0.6000 UP/DOWN/RESET 0.5500

5.2 Parameter List

5.2.1 Parameters setting for Solar Controller

ParameterName DescriptionOption Default
A1-03 Initialization 2838: 2-Wire
<9-00 M PP> Mode Enable 1:EEnable/ 0: Disable 1
<9-01Controller Min.Operating VoltageController starts when input voltage(DC) higher than this value.350
<9-02 <tarting Frequency <tart to operate from this frequency 20
<9-04 M PP> Voltage <tep Delta output voltage per MPP> step 4
<9-05Min. Operating FrequencyController min. operating frequency, shutdown if operating frequency is lower this this vale15
<9-09 M>>he regular duration between MPP> commandsUnit: 20ms30 (0.9s)
b1-00Frequency Command source0: %eypad1: Control Circuit >erminal (Analog Input)2: >erminal Up/Down3: Modbus Communication4: Pulse >rain Input (Including PWM signal5: MPP>5
b1-01Operating Command4: >erminal5: Auto5
b1-02Stopping Method Selection0: Ramp to Stop1: Coast toimer1
C1-00 Acceleration >ime Controller acceleration >ime. Unit: s 3
C1-01 Deceleration >ime Controller deceleration >ime. Unit: s 0.1
P2-03 UV protection Under voltage protection level. Unit: s 300
E1-00 >terminal <1 FunctionDigi input <1,197: Controller stop when water gage(sensor) open197
E1-01 >terminal <2 FunctionDigi input <2, default is disable (no function) 20
E1-02 >terminal < Function 3Digi input <3, Digi input <3,194: Operation pause when terminal close194
E1-03~07>terminal <4~<8 FunctionDigi input <4~<8 default is disable (no function)20

5.2.2 Parameters setting for the other applications

ParameterNameDescriptionSetting Range
Group A, Initialization
A1: Basic Settings
A1-01<4>Access LevelSelectionSelects access level (edit /view)0: View OnlyAccess to only parameter A1-011: User-Defined Parameter AccessAccess to only parameter A1-01 and A2-00 to A2-312: All Parameter AccessAll parameters can be edited and viewedDefault: 2Range: 0, 1, 2
A1-02Control Method Selection0: Open-Loop V/F Control1: Closed-Loop V/F Control2: Open-Loop Vector Control3: Closed-Loop Vector Control4: PM Open-Loop Vector Control5: PM Closed-Loop Vector Control6: Closed-Loop Torque Control7: Position ControlDefault: 0Min.: 0Max.: 7
A1-03ResetResets parameter settings to defaults. After resetting parameters, the value will become 0.2538: Resets 2-Wire Sequence/ 50Hz / 380V2541: Resets 2-Wire Sequence / 50Hz / 415V2544: Resets 2-Wire Sequence / 50Hz / 440V2546: Resets 2-Wire Sequence / 50Hz / 460V2638: Resets 2-Wire Sequence / 60Hz / 380V2641: Resets 2-Wire Sequence / 60Hz / 415V2644: Resets 2-Wire Sequence / 60Hz / 440V2646: Resets 2-Wire Sequence / 60Hz / 460V3538: Resets 3-Wire Sequence / 50Hz / 380V3541: Resets 3-Wire Sequence / 50Hz / 415V3544: Resets 3-Wire Sequence / 50Hz / 440V3546: Resets 3-Wire Sequence / 50Hz / 460V3638: Resets 3-Wire Sequence / 60Hz / 380V3641: Resets 3-Wire Sequence / 60Hz / 415V3644: Resets 3-Wire Sequence / 60Hz / 440V3646: Resets 3-Wire Sequence / 60Hz / 460VDefault: 0Range: 0 to 3646
A1-04PasswordSet password to parameter A1-05 and enter the password to parameter A1-04 to unlock it.Parameters A1-01 to A1-03, A1-06, A2-01 to A2-32 cannot be edited until correct password is entered to A1-04Default: 0000Min.: 0000Max.: 9999
A1-05Password Setting
A1-06ND/HD Selection0: Heavy Duty (HD)1: Normal Duty (ND)Default: 0Range: 0, 1
A2: User-Defined Parameters
A2-00 to A2-31User-Defined Parameters 1 to 32Selects up to 32 parameters and assigns them to parameter A2-00 to A2-31. Saved parametersRange: A1-00 to F1-18
can be viewed in User-Defined Parameter Access. To assign specific parameters to A2-00 to A2-31, set parameter A1-01 to 2. The saved parameters A2-00 to A2-31 can only be viewed if A1-01 is set to 1
Parameter DefaultNameParameterDefaultName
A2-00 b1-00Frequency Command SelectionA2-16E3-07Terminal A2 Function Selection
A2-01 b1-01Run Command SelectionA2-17
A2-02 C1-00Acceleration TimesA2-18
A2-03 C1-01Deceleration TimesA2-19
A2-04 C3-00Torque Compensation GainA2-20
A2-05 d1-02Maximum Output FrequencyA2-21
A2-06 d1-03Maximum VoltageA2-22
A2-07 d1-04Base FrequencyA2-23
A2-08 d1-05Base VoltageA2-24
A2-09 a2-06Operation Direction at Power Up when Using KeypadA2-25
A2-10 b1-10Run Command at Power upA2-26
A2-11 E2-00Relay 1 Function SelectionA2-27
A2-12 E2-01Relay 2 Function SelectionA2-28
A2-13 E3-00Terminal A1 Signal Level SelectionA2-29
A2-14 E3-01Terminal A1 Function SelectionA2-30
A2-15 E3-06Terminal A2 Signal Level SelectionA2-31
A2-32User-Defined Parameter Automatic SaveSaves the most recently edited parameters. 0: Do not save list of recently edited parameters 1: Save list of recently edited parametersDefault: 1Range: 0, 1
Group b, Application
b1: Operation Mode Selection
b1-00Frequency Command Selection 10: Keypad1: Control Circuit Terminal (Analog Input)2: Terminal Up/Down3: Modbus Communication4: Pulse Train Input (Including PWM signalDefault: 1Min.: 0Max.: 5
input)5: Option Card
b1-01Run Command Selection 10: Keypad1: Control Circuit Terminal (Sequence Control Input)2: Modbus Communication3: Option CardDefault: 1Range: 0, 1, 2, 3
b1-02Stopping Method Selection0: Ramp to Stop1: Coast to Stop2: DC Braking to Stop3: Coast to Stop with TimerDefault: 0Min.: 0Max.: 3
b1-03Reverse Rotation Selection0: Reverse Rotation EnabledController accepts a run command of both forward and reverse directions1: Reverse Rotation disabledController can accept only run command of forward directionDefault: 0Range: 0, 1
b1-04<9>Zero-speed mode functionWhen the frequency command lower than the set value of the d1-08, and the operation command also exists when the load deceleration and lower than d1-08 setting value, the zero-speed operationDefault: 0Range: 0, 1
b1-05Run Command Action after Switch0: Ignore Active Run Command at the New SourceIf a Run command at the new source is active, the controller will not start or the controller will stop operation if it was running when switching from the old source to the new source. The controller can start only when the Run command is removed and given again.1: Accept Active Run Command at the New SourceIf a run command at the new source is active, the controller will accept it and run the load immediately right after switching from the old source to the new source.Default: 0Range: 0, 1
b1-06Run Command Selection during Programming0: Run command disabled during Programming1: Run command enabled during Programming2: Prohibit programming during runThe programming mode cannot be displayed during run except for monitoringparameter Group U.Default: 0Range: 0, 1, 2
b1-07FrequencyCommandSelection 2Enabled while E1-00 to E1-07 is set to 4 and the DIP switch is set to OFF0: Keypad1: Control Circuit Terminal (Analog Input)2: Terminal Up/Down3: Modbus Communication4: Pulse Train Input (Including PWM signal input)5: Option cardDefault: 0Min.: 0Max.: 5
b1-08Run CommandSelection 2Enabled while E1-00 to E1-07 is set to 4 and the DIP switch is set to OFF0: Keypad1: Control Circuit Terminal (Sequence Control Input)2: Modbus Communication3: Option cardDefault: 0Range: 0, 1, 2, 3
b1-09<7>FrequencysuperpositionSelection0: Disabled1: EnabledDefault: 0Range: 0, 1
b1-10Run Command atPower upDetermines to accept or ignore an active Run command from Remote during power up.0: IgnoreController ignores an active run command during power up1: AcceptController accepts an active run command at power up and runs the load immediately.Default: 0Range: 0, 1
b1-12<7>Local/ Remoteswitching Enableduring Operating0 :Disabled1 :EnabledDefault: 0Range: 0, 1
b2: DC Braking
b2-00Zero SpeedHolding (DCBraking) Start LevelSets the start frequency for Zero Speed Holding (DC braking). Enabled when b1-02 (Stopping Method Selection) is set to 0 (Ramp to Stop)Default: 0.5HzMin.: 0.0 HzMax.: 10.0 Hz
b2-01DC Braking CurrentSets the DC braking current as a percentage of the controller rated currentDefault: 30%Min.: 0%Max.: 100%
b2-02DC Braking Time atStartSets the DC braking time at start to stop a coasting load before restarting it or to applybraking torque at start when high starting torque is needed. Disabled when set to 0.00.Default: 0.00 sMin.: 0.00 sMax.: 99.99 s
b2-03DC Braking Time at StopSets the DC braking time at stop to stop a load rotating with high inertia. Disabled when set to 0.00.Default: 0.50s Min.: 0.00s Max.: 99.99s
b3: Speed Search
b3-00Speed Search Setting0 :Disabled1 :Enabled and searched from the highest frequency2 : Enabled and searched from the frequency command3 :Retain4 :RetainDefault: 0 Range: 0, 1, 2
b3-01Speed Search Operating CurrentSets the current level as a percentage of the controller rated current below which Speed Search is deactivated.Default: 80% Min.: 0 % Max.: 100%
b3-02 <9>Voltage Rocevery TimeSets the search speed in the output voltage restoring to the time set v / f voltage curve requiredDefault: 0.6s Min.: 0.3s Max.: 5.0s
b3-03Retain
b3-04 <9>Speed search deceleration timeSets the search speed in the deceleration time (The maximum output frequency to the minimum output frequency deceleration time)Default: 2.0s Min.: 0.1s Max.: 10.0s
b3-05 <9>Search speed in V / fIn order to reduce the speed of search output current by the V / f curve calculated by multiplying the voltage set value b3-05 by adjusting the setting, the speed can be suppressed search output current.Default: 100% Min.: 10 % Max.: 100%
b4: Timer Function
b4-00Timer Function On-Delay TimeSets the on-delay and off-delay time to switch on/off the timer output.Default: 0.1 s Min.: 0.1 s Max.: 3000.0 s
b4-01Timer Function Off-Delay TimeDefault: 0.0 s Min.: 0.0 s Max.: 3000.0 s
b5: PID Control
b5-00PID Control Setting0 : PID Control Disabled1 : PID Control Enabled (D Control for DeviationSignal U4-01)2 : PID Control Enabled (D Control for Feedback Signal U4-05)3 : PID Control Enabled (Frequency Command + PID Output from D Controlled Deviation)4 : PID Control Enabled (Frequency Command + PID Output from D Controlled Feedback)5 : PID Control Disabled · but b5-14/b5-15 (PID Sleep) and b5-29/b5-30(PID Wake-up)EnabledDefault: 0 Min.: 0Max.: 5
b5-01<4>Proportional Gain Setting (P)Sets the P gain for PID input.Default: 1.00Min.: 0.00Max.: 25.00
b5-02<4>Integral Time Setting (I)Deviation appears between PID target value and feedback value when using only proportional control. To reduce the deviation, set integral time (I).Default: 1.0 sMin.: 0.0 sMax.: 360.0 s
b5-03<4>Integral Time (I)Limit SettingSets the maximum output from the I (integral) control as a percentage of the maximum frequency (d1-02)Default: 100.0%Min.: 0.0%Max.: 100.0%
b5-04<4>Derivative Time (D)Sets derivative time for D control.Default: 0.00 sMin.: 0.00 sMax.: 10.00 s
b5-05<4>PID Output LimitSets the maximum output from PID control as a percentage of the maximum frequency.Default: 100.0%Min.: 0.0%Max.: 100.0%
b5-06<4>PID Bias Voltage AdjustmentSets the PID bias voltage adjustment as a percentage of the maximum frequency to add to the PID control output.Default: 0.0%Min.: -100.0%Max.: 100.0%
b5-07<4>PID Primary Delay TimeSets the delay time for the PID output filter.Default: 0.00 sMin.: 0.00 sMax.: 10.00 s
b5-08PID Output Selection0 : Normal PID Output1 : Reverse PID OutputReverses the +/- sign of the PID outputDefault: 0Range: 0, 1
b5-09PID Output GainSets a PID output gainDefault: 1.00Min.: 0.00Max.: 25.00
b5-10PID Output Reverse SelectionDetermines whether or not a negative PID output reverses the controller rotating direction.0: Reverse Disabled1: Reverse EnabledDefault: 0Range: 0, 1
b5-11PID Feedback Low /High Detection Selection0: Multi-Function Output Only1: Feedback Low /High AlarmThe controller continues operation when an alarm is displayed)2: Feedback Low /High FaultA fault will cause the controller to stop the load.3: Multi-Function Output only when PID is DisabledSame action as b5-11=0.4: Feedback Low /High Alarm (detection disabled when PID is disabled)5: Feedback Low /High Fault (detection disabled when PID is disabled)6: Multi-Function Output (Keep running without an alarm displayed)7: Multi-Function Output Only (detection working when controller running or not)Default: 0Min.: 0Max.: 7
b5-12PID Feedback Low Detection LevelSets the PID feedback level used for detection.When the PID feedback falls below this level for longer than the time set to b5-13, PID feedback loss will be detected.Default: 0%Min.: 0%Max.: 100%
b5-13PID Feedback Low Detection TimeSets the PID feedback time used for detection.When the PID feedback falls below the level set to b5-12 for longer than this time, PID feedback loss will be detected.Default: 1.0 sMin.: 0.0 sMax.: 25.5 s
b5-14PID Sleep Start LevelSets the PID level to trigger the controller to sleep.Default: 0.0HzMin.: 0.0 HzMax.: <5>
b5-15PID Sleep Delay TimeSets the delay time used to activate/deactivate the PID Sleep function. When this parameter is set to 0.0, PID Sleep function will be stopped.Default: 0.0 sMin.: 0.0 sMax.: 25.5 s
b5-16PID Command Acc./Dec. TimeSets the PID command acceleration/deceleration time used for PID target soft-start function.Default: 0.0 sMin.: 0.0 sMax.: 200.0 s
b5-17PID Target Selection0:PID Target Disabled1:PID Target EnabledDefault: 0Range: 0, 1
b5-18PID Target ValueSets the PID target value as a percentage of the maximum output frequency when b5-17=1 andno other ananlog input sets the PID Target.Default: 0.00%Min.: 0.00%Max.: 100.00%
b5-19PID Target Value Units0 : 0.01Hz1 : 0.01% (Maximum Frequency is 100%)2 : r/min. (Number of Poles must be set)3 : User Defined (Defined by b5-24 and b5-25)Default: 1Range: 0, 1, 2, 3
b5-20<7>PID Output Lower LimitSets the lower limit as a percentage of the maximum output frequency set in d1-02 for PID output.Default: 0.0%Min.: -100.0%Max.: 100.0%
b5-21<7>PID Input LimitThe higher PID Input value is, the higher PID output value will be. Sets this parameter to limit the PID input value.Default: 1000.0%Min.: 0.0%Max.: 1000.0%
b5-22PID Feedback High Detection LevelSets the level for PID feedback high detection as a percentage of the maximum output frequency.PID feedback high will be detected when the feedback exceeds the level set in b5-22 for longer than the time set in b5-23.Default: 100%Min.: 0%Max.: 100%
b5-23PID Feedback High Detection TimeSets the time for PID feedback high detection.PID feedback high will be detected when the feedback exceeds the level set in b5-22 for longer than the time set in b5-23.Default: 1.0 sMin.: 0.0 sMax.: 25.5 s
b5-24PID Target Display ValueSets a value to display to U4-00 and U4-03 when the controller runs at the maximum output frequencyDetermined by b5-19Min.: 1Max.: 60000
b5-25PID Target Display DigitsSets the number of decimal places to display.0 : No Decimal Places1 : 1 Decimal Place2 : 2 Decimal Places3 : 3 Decimal PlacesDetermined by b5-19Min.: 0Max.: 3
b5-26<7>Frequency Command Display During PID0 : Displays frequency command after the PID compensation.1 : Displays frequency command before the PID compensation.Default: 0Range: 0, 1
b5-27<7>PID Output Direction 2Sets the direction when PID output value is minus.0 : Reverse is not allowed.1 : Reverse is allowed.Default: 1Range: 0, 1
b5-28PID Disconnection Output FrequencyWhen a PID feedback disconnection alarm occurs, the controller will run at the frequency set to b5-28, and return to PID control when disconnection alarm is reset.Default: 30.0 HzMin.:0.0HzMax.: Determined by d1-02, L2-00, d1-13
b5-29<9>PID Wake-up LevelSets the PID Wake-up levelDefault:0.0 HzMin.:0.0 HzMax.:<5>
b5-30<9>PID Wake-up deley timeSets the PID Wake-up delay timeDefault: 0.0 sMin.: 0.0 sMax.: 25.5 s
b6: Dwell Function
b6-00Dwell Frequency at StartSets the frequency to b6-00 used to be held for the time set in b6-01 during acceleration.Default: Determined by A1-02Min.: 0.0 HzMax.: Determined by d1-02, L2-00, d1-13
b6-01Dwell Time at StartDefault: 0.0 sMin.: 0.0 sMax.: 10.0 s
b6-02Dwell Frequency at StopSets the frequency to b6-02 used to be held for the time set in b6-03 during deceleration.Default: 0.0HzMin.: 0.0 HzMax.: Determined by d1-02, L2-00, d1-13
b6-03Dwell Time at StopDefault: 0.0 sMin.: 0.0 sMax.: 10.0 s
b7: Droop Function
b7-00Droop Control GainSets the amount of speed reduction when the torque reference is 100%. The gain is set as a percentage of the maximum output frequency. A setting of 0.0% disables the Droop control function.Default: 100%Min.: 0%Max.: 100%
b7-01Droop Control Delay TimeAdjusts the responsiveness of Droop control. Reduce the setting if the reaction time is too long, and increase the setting if hunting occurs.Default: 0.05 sMin.: 0.03 sMax.: 2.00 s
b7-02Droop Control Limit Selection0 : Droop Control Limit Disabled1 : Droop Control Limit EnabledDefault: 1Min.: 0Max.: 1
b9 : Position Control / Zero Speed Holding <7>
b9-00Position Control/Zero Speed Holding GainSets the response of Zero Speed Holding in FOC with PG control method or response of Position Control in Position Control control method.Default: 5%Min.: 0%Max.: 100%
b9-01Zero SpeedHolding Stop WidthSets the signal output width in which the ZeroSpeed Holding function will stop.Default: 12 pulseMin.: 0 pulseMax.: 4096 pulse
b9-02Zero Speed Holding On/ Off0: Zero Speed Holding Disabled.Controller coasts to stop when the frequency is zero.1: Zero Speed Holding Enabled.Zero Speed Holding starts when the frequency is zero. The holding current is set in b2-01 and it will be limited to below 20% of the controller rated current.Default: 0Min.: 0Max.: 1
b9-03Zero Speed Holding TimeSets the Zero Speed Holding time. Controller will coast to stop when the Zero Speed Holding time is longer than this setting. Set 00.00 to disable Zero Speed Holding or set 99.99 to enable this function continuously.Default: 0.10secMin.: 00.00secMax.: 99.99sec
b9-04Position Control Input Command Direction0: Forward1: ReverseDefault: 0Min.: 0Max.: 1
Group C, Tuning
C1: Acc./Dec. Time
C1-00<4>Acceleration Time1Sets the time that the controller accelerates from 0Hz to the maximum output.Default: 10.0 sMin.: 0.0 sMax.: 6000.0 s
C1-01<4>Deceleration Time1Sets the time that the controller decelerates from the maximum output to 0Hz.
C1-02<4>Acceleration Time2Sets the time that the controller accelerates from 0Hz to the maximum output.
C1-03<4>Deceleration Time2Sets the time that the controller decelerates from the maximum output to 0Hz.
C1-04<4>Acceleration Time3Sets the time that the controller accelerates from 0Hz to the maximum output.
C1-05<4>Deceleration Time3Sets the time that the controller decelerates from the maximum output to 0Hz.
C1-06<4>Acceleration Time4Sets the time that the controller accelerates from 0Hz to the maximum output.
C1-07<4>Deceleration Time4Sets the time that the controller decelerates from the maximum output to 0Hz.
C1-08Fast Stop TimeSets the time to stop the controller faster.
C1-09Acc./Dec. Time Unit SelectionSet the units of time for C1-00 to C1-08. 0 : 0.01 s (0.00 to 600.00 s) 1 : 0.1 s (0.00 to 6000.0 s)Default: 1 Range: 0, 1
C1-10Acc./Dec. Time Switch FrequencySets the frequency level. The controller will switch the acceleration and deceleration time at this level.Default: 0.0 Hz Min.: 0.0 Hz Max.: Determined by d1-02, L2-00
C1-11Jog Acc. TimeSets the time to accelerate from 0 Hz to Jog Frequency Command (L1-16).Default: 10.0 s Min.: 0.0 s Max.: 6000.0 s
C1-12Jog Dec. TimeSets the time to decelerate from Jog Frequency Command (L1-16) to 0 Hz.Default: 10.0 s Min.: 0.0 s Max.: 6000.0 s
C2: S-Curve Characteristics
C2-00S-Curve Characteristic at Acc. StartSets S-curve times for each acceleration or deceleration. Actual Acceleration Time= Determined Acc. Time+(C2-00+C2-01)/2 Actual Deceleration Time= Determined Dec. Time+(C2-02+C2-03) / 2Default: 0.20 s Min.: 0.00 s Max.: 10.00 s
C2-01S-Curve Characteristic at Acc. EndDefault: 0.20 s Min.: 0.00 s Max.: 10.00 s
C2-02S-Curve Characteristic at Dec. StartDefault: 0.20 s Min.: 0.00 s Max.: 10.00 s
C2-03S-Curve Characteristic at Dec. EndDefault: 0.20 s Min.: 0.00 s Max.: 10.00 s
C3: Torque Compensation
C3-00 <4>Torque Compensation GainSets the gain for the #1 Torque compensationDefault: Determined by A1-02 Min.:0.00 Max.:2.50
C3-01# 2 Torque Compensation GainSets the gain for the #2 Torque compensationDefault: Determined by A1-02 Min.: 0.00 Max.: 2.50
C3-02 <4>Torque Compensation Primary Delay TimeSets the Torque compensation primary delay time.Default: Determined by A1-02 Min.: 0 ms Max.:10000 ms
C3-03TorqueCompensationPrimary Delay Time2Sets the delay time used during regeneration or Speed Search.Default: 150msMin.: 0 msMax.: 10000 ms
C3-04TorqueCompensation at Start (Forward)Sets the torque compensation at start with forward rotation as a percentage of the rated torqueDefault: 0.0%Min.: 0.0%Max.: 200.0%
C3-05TorqueCompensation at Start (Reverse)Sets the torque compensation at start with reverse rotation as a percentage of the rated torqueDefault: 0.0%Min.: -200.0%Max.: 0.0%
C3-06TorqueCompensationTime at StartSets the time to apply the torque compensation at start determined by C3-04, C3-05.Default: 10 msMin.: 0 msMax.: 200 ms
C4: ASR (Automatic Speed Regulator)
C4-00<4>ASR Proportional Gain 1 (P)Sets the ASR proportional gain 1.Default: Determined by A1-02Min.: 0.00Max.: 300.00
C4-01<4>ASR Integral Time 1 (I)Sets the ASR integral time 1.Default: Determined by A1-02Min.: 0.000 sMax.: 10.000 s
C4-02<4>ASR Proportional Gain 2 (P)Sets the ASR proportional gain 2.Default: Determined by A1-02Min.: 0.00Max.: 300.00
C4-03<4>ASR Integral Time 2 (I)Sets the ASR integral time 2.Default: Determined by A1-02Min.: 0.000 sMax.: 10.000 s
C4-04<9>ASR Filter GainIn severe cases of noise interference, the estimated value of the ASR for filtering, has reduced the effect of noise; the greater the gain, the higher the degree of filtering, but the response speed will be slowDefault:0.0Min.: 0.0 sMax.: 100.0 s
C4-05ASR Primary Delay TimeSets the primary delay time when the torque command is given by ASR.Default: Determined by A1-02Min.: 0.000 sMax.: 0.500 s
C4-06ASR Gain Switching FrequencySets the frequency to switch between C4-00 and C4-02 (ASR proportional gain), and between C4-01 and C4-03 (ASR integral time 1, 2).Default: 0.0 HzMin.: 0.0 HzMax.: Determined by d1-02, L2-00
C4-11<4>#2 ASRProportional Gain 1 (P)Sets the #2 ASR proportional gain.Default: Determined by d1-12Min.: 0.00Max.: 300.00
C4-12<4>#2 ASR Integral Time 1Sets the #2 ASR integral time.Default: Determined by d1-12Min.: 0.000 sMax.: 10.000 s
C4-13<4>#2 ASRProportional Gain 2 (P)Sets the #2 ASR proportional gain 2.Default: Determined by d1-12Min.: 0.00Max.: 300.00
C4-14<4>#2 ASR Integral Time 2Sets the #2 ASR integral time 2.Default: Determined by d1-12Min.:0.000 sMax.:10.000 s
C4-16#2 ASR Primary Delay TimeSets the #2 primary delay time when the torque command is given by ASRDefault: Determined by d1-12Min.:0.000 sMax.:0.500 s
C4-17#2 ASR GainSwitching FrequencySets the frequency to switch between C4-00 and C4-02 (ASR proportional gain), and between C4-01 and C4-03 (ASR integral time 1, 2).Default: 0.0 HzMin.:0.0 HzMax.: Determined by d1-02, L2-00
C5: Slip Compensation
C5-00<4>Slip Compensation GainSets the slip compensation gain to improve the speed accuracy for heavy loads.Default: Determined by A1-02Min.: 0.0Max.: 2.5
C5-01<4>Slip Compensation Primary Delay TimeSets the slip compensation primary delay time to stabilize the speed or to improve the speed response.Default: Determined by A1-02Min.: 0 msMax.:10000ms
C5-02Slip Compensation LimitSets the maximum slip compensation as percentage of the rated slip for #1.Default: 200%Min.: 0 %Max.: 250 %
C5-08<4>#2 SlipCompensationGainSets the slip compensation gain to improve the speed accuracy for heavy loads at #2.Default: Determined by d1-12Min.: 0.0Max.: 2.5
C5-09<4>#2 SlipCompensationPrimary Delay TimeSets the slip compensation primary delay time to stabilize the #2 speed or to improve the speed response.Default: Determined by d1-12Min.: 0 msMax.:10000ms
C5-10#2 SlipCompensationLimitSets the #2 maximum slip compensation as percentage of the rated slip for #1.Default: 200%Min.: 0 %Max.: 250 %
C6: Carrier Frequency
C6-00Carrier FrequencySelectionSets the switching frequency of the controller output transistors. Adjust this setting to reduce audible noise and leakage current.0: Determined by C6-01 to C6-031: Retain2: 2.0 kHz3: 3.0 kHz4: 4.0 kHz5: 5.0 kHz6: 6.0 kHz7: 7.0 kHz8: 8.0 kHz9: 9.0 kHz10: 10.0 kHz11: 11.0 kHz12: 12.0 kHz13: 13.0 kHz14: 14.0 kHz15: 15.0 kHz16: 16.0 kHzDefault: Determined by A1-02 and o2-03.Once A1-06 is redefined, the default will be changed accordinglyMin.: 0Max.: 16
C6-01Maximum Carrier FrequencySet 0 to parameter C6-00 to enable this setting. Sets the maximum and minimum carrier frequency in V/F Control that the controller will adjust carrier frequency according to the output frequency.Default: Determined by C6-00Min.: 2.0 kHzMax.: 16.0 kHz
C6-02Minimum Carrier FrequencyDefault: Determined by C6-00Min.: 2.0 kHzMax.: 16.0 kHz
C6-03Carrier Frequency Proportional GainDefault: Determined by C6-00Min.: 0Max.: 99
C7-00Proportional GainApplications by setting this gain, if the load is heavy increase the value, and vice versa to reduce this valueDefault:50%Min.: 1%Max.: 100%
Group L, Frequency Command
L1: Frequency Command
L1-00<4>FrequencyCommand 1To use speed commands for each multi-step speed, set E1-□□ to 5, 6, 7 and 8 (multi-step speed command 1, 2, 3, 4). Sets E1-□□ to 9 for Jog frequency command.The upper limit is determined by d1-02 and L2-00.In PM Closed-Loop Vector Control, o1-00 will be automatically set to 1 with the unit set to %.When L2-00 (Frequency Upper Limit) is adjusted, the exceeded frequency in L1-00 to L1-15 will be automatically set to the upper limit determined in L2-00.Default:5.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00
L1-01<4>FrequencyCommand 2Default: 8.00 HzMin.: 0.00 HzMax.: Determined by d1-02, L2-00
L1-02<4>FrequencyCommand 3Default: 10.00HzMin.: 0.00 HzMax.: Determined by d1-02, L2-00
L1-03<4>FrequencyCommand 4Default: 12.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00
L1-04<4>FrequencyCommand 5Default: 15.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00
L1-05<4>FrequencyCommand 6Default: 20.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00
L1-06<4>FrequencyCommand 7Default: 25.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00
L1-07<4>FrequencyCommand 8Default: 30.00HzMin.: 0.00Hz
ParameterNameDescriptionSetting Range
To use speed commands for each multi-step speed, set E1-□□ to 5, 6, 7 and 8 (multi-step speed command 1, 2, 3, 4). Sets E1-□□ to 9 for Jog frequency command.The upper limit is determined by d1-02 and L2-00.In PM Closed-Loop Vector Control, o1-00 will be automatically set to 1 with the unit set to %.When L2-00 (Frequency Upper Limit) is adjusted, the exceeded frequency in L1-00 to L1-15 will be automatically set to the upper limit determined in L2-00.Max.: Determined by d1-02, L2-00Default: 35.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 40.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 42.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 45.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50,00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.15HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 6.00 HzMin.: 0.00HzMax.: 400.00 HzMax.: Determined by d1-02, L2-00Default: 35.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 40.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 42.00HzMin.: 0.00 HzMax.: Determined by d1-02, L2-00Default: 45.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00Hz Max.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.; Determined by d1-02, L2-00Default: 50.00HzMin.: 0.00HzMax.: Determined by d1-02, L2-00Default: 6.00 HzMin.: 0.00HzMax.: 400.00 Hz
L1-08<4>FrequencyCommand 9
L1-09<4>FrequencyCommand 10
L1-10<4>FrequencyCommand 11
L1-11<4>FrequencyCommand 12
L1-12<4>FrequencyCommand 13
L1-13<4>FrequencyCommand 14
L1-14<4>FrequencyCommand 15
L1-15<4>FrequencyCommand 16
L1-16<4>Jog FrequencyCommandSets the Jog frequency command.Default: 6.00 HzMin.: 0.00 HzMax.: 400.00 Hz
L2: Frequency Upper/ Lower Limit
L2-00FrequencyCommand UpperSets the upper limit as a percentage of the maximum output frequencyDefault: 100.0 %Min.: 0.0 %
ParameterNameDescriptionSetting Range
LimitMax.: 110.0 %
L2-01FrequencyCommand LowerLimitSets the lower limit as a percentage of the maximum output frequencyDefault: 0.0%Min.: 0.0%Max.: 110.0 %
L3: Jump Frequency
L3-00Jump Frequency 1Sets the Jump frequency range to avoid operation at the speed causing resonance in the machinery.Set L3-00 to L3-03 to 0.0 Hz to disable Jump frequency.When setting more than 1 Jump frequency, follow the condition below.L3-00 ≤ L3-01 ≤ L3-02Default: 1.0 HzMin.: 0.0 HzMax.: 20.0 Hz
L3-01Jump Frequency 2
L3-02Jump Frequency 3
L3-03Jump FrequencyRangeSets the Jump frequency range to avoid.Default: 1.0 HzMin.: 0.0 HzMax.: 20.0 Hz
L4: Frequency Command Hold and Up/Down 2 Command
L4-00Up/ DownFrequencyCommand HoldDetermines whether or not to save the frequency command or the frequency bias (Up/Down 2) value when the Stop command is entered or the power supply is shut off.0 : Clear the Up/Down frequency at stop1 : Save the Up/Down frequency at stop2 : Accept the Up/Down frequency at stopDefault: 0Range: 0, 1, 2
L4-01<4>FrequencyCommand Bias(Up/Down 2)Sets the bias used to add to or subtract from the frequency command by Up/Down 2.Default:0.00 HzMin.: 0.00 HzMax.: 99.99 Hz
L4-02<4>FrequencyCommandAcc./Dec Setting(Up/Down 2 )Sets the acceleration/deceleration times to increase or decrease the frequency command bias for Up/Down 2.0 : Current Acc./Dec. Time1 : Acc./Dec. Time 4 set in C1-06 and C1-07Default: 0Range: 0, 1
L4-03<4>Up/DownFrequencyCommand SaveSaves the frequency command from Up/Down 1 or Up/Down 2Default: 0.00HzMin.: 0.00 HzMax.: Determined by d1-02, d1-13 and L2-00
L4-04FrequencyCommand Hold0: Disabled1: EnabledDefault: 0Range 0, 1
L5 : Torque Control
L5-00Torque Command Delay TimeApply a filter with the time constant set to parameter d5-02 to the torque reference signal to eliminate oscillation resulting from an unstable torque reference signal. Increase the setting when oscillation occurs during torque control.Default: 0 msMin.: 0 msMax.: 1000 ms
L5-01Speed Limit SelectionSelects the speed limit for Torque Control.1 : Frequency Command (b1-00 or b1-07)2 : L5-02 and L5-03Default: 1Min.: 1Max.: 2
L5-02Forward Speed LimitSets the forward speed limit during Torque Control as a percentage of highest speed when L5-01 = 2.Default: 10 %Min.: 0 %Max.: 120 %
L5-03Reverse Speed LimitSets the reverse speed limit during Torque Control as a percentage of highest speed when L5-01 = 2.Default: 10 %Min.: 0 %Max.: 120 %
L5-04Speed/Torque Control Switch Delay TimeSets the delay time for switching between Speed Control and Torque Control.Default: 0 msMin.: 0 msMax.: 1000 ms
L5-06<7>Torque Command Delay Time 2Apply a filter with the time constant set to parameter d5-02 to the torque reference signal to eliminate oscillation resulting from an unstable torque reference signal. Increase the setting when oscillation occurs during torque control.Default: 10 msMin.: 0 msMax.: 1000 ms
L6: Offset Frequency
L6-00<4>Offset Frequency 1Sets the offset value as a percentage of the maximum output frequency to add to or subtract from the frequency command.Select the offset frequency in E1-□□= 53, 54 and 55 (Offset Frequency 1 to 3).Default: 0.0%Min.: -100.0%Max.: 100.0%
L6-01<4>Offset Frequency 2Sets the offset value as a percentage of the maximum output frequency to add to or subtract from the frequency command.Select the offset frequency in E1-□□= 53, 54 and 55 (Offset Frequency 1 to 3).Default: 0.0%Min.: -100.0%Max.: 100.0%
L6-02<4>Offset Frequency 3Sets the offset value as a percentage of the maximum output frequency to add to or subtract from the frequency command.Select the offset frequency in E1-□□= 53, 54 and55 (Offset Frequency 1 to 3).Default: 0.0%Min.: -100.0%Max.: 100.0%
Group d, Load Parameters
d1: V/F Characteristics
d1-00Input Voltage SettingSets the input voltage of the controller. Always set the input voltage of the controller to this parameter.Default: Determined by A1-03Min.: 155 VMax.: 255V <3>
d1-01V/F Pattern Selection0 : 50 Hz (Constant Torque Characteristic 1)1 : 60 Hz (Constant Torque Characteristic 2)2 : 60 Hz (Constant Torque Characteristic 3), 50 Hz base3 : 72 Hz (Constant Torque Characteristic 4), 60 Hz base4 : 50 Hz (Derated Torque Characteristic 1)5 : 50 Hz (Derated Torque Characteristic 2)6 : 60 Hz (Derated Torque Characteristic 3)7 : 60 Hz (Derated Torque Characteristic 4)8 : 50 Hz (High Starting Torque Characteristic 1)9 : 50 Hz (High Starting Torque Characteristic 2)A : 60 Hz(High Starting Torque Characteristic 3)B : 60 Hz(High Starting Torque Characteristic 4)C : 90 Hz, 60 Hz baseD : 120 Hz, 60 Hz baseE : 180 Hz, 60 Hz baseF : 60Hz (Constant Torque Characteristic) (Default)Default: FRange: 0 to 9; A to F
d1-02Maximum Output FrequencyWhen d1-01 ≤ E, parameters d1-02 to d1-11 can be used to monitor the V/F pattern.When d1-01 = F, parameters d1-02 to d1-11 can be used to create a V/F pattern.Default: <1>Min.: 25.0 HzMax.: 400.0 Hz
d1-03Maximum VoltageDefault: <1>Min.: 0.0 VMax.: 255.0 V <3>
d1-04Base FrequencyDefault: <1>Min.: 0.0 HzMax.: Defined by d1-02
d1-05Base VoltageDefault: <1>Min.: 0.0 VMax.: 255.0 V <3>
d1-06Middle Output FrequencyWhen d1-01 ≤ E, parameters d1-02 to d1-11 can be used to monitor the V/F pattern.When d1-01 = F, parameters d1-02 to d1-11 can be used to create a V/F pattern.Default: <1>Min.: 0.0 HzMax.: Defined by d1-02
d1-07Middle Output Frequency VoltageDefault: <1>Min.: 0.0 VMax.: 255.0 V <3>
d1-08Minimum Output FrequencyDefault: <1>Min.: 0.0 HzMax.: Defined by d1-02
d1-09Minimum Output Frequency VoltageDefault: <1>Min.: 0.0 VMax.: 255.0 V <3>
d1-10Middle Output Frequency 2Default: 0.0 HzMin.: 0.0 HzMax.: Defined by d1-02
d1-11Middle Output Frequency Voltage 2Default: 0.0 VMin.: 0.0 VMax.: 255.0 V <3>
d1-12#2 Control Method Selection0 : Open-Loop V/F Control1 : Retain2 : Open-Loop Vector Control3 : RetainA permanent cannot be #2.Default: 0Min.: 0Max.: 3
d1-13#2 Maximum Output FrequencySets the #2 V/F pattern in d1-13 to d1-22.Default: <1>Min.: 25.0 HzMax.: 400.0 Hz
d1-14#2 Maximum VoltageDefault: <1>Min.: 0.0 VMax.: 255.0 V <3>
d1-15#2 Base FrequencyDefault: <1>Min.: 0.0 HzMax.: Defined by d1-13
d1-16#2 Base VoltageDefault: <1>Min.: 0.0 VMax.: 255.0 V <3>
d1-17#2 Middle Output FrequencyDefault: <1>Min.: 0.0 Hz
ParameterNameDescriptionSetting Range
Max.: Defined by d1-13
d1-18#2 Middle Output Frequency VoltageDefault: <1>Min.: 0.0 VMax.: 255.0 V <3>
d1-19#2 Minimum Output FrequencyDefault: <1>Min.: 0.0 HzMax.: Defined by d1-13
d1-20#2 Minimum Output Frequency VoltageDefault: <1>Min.: 0.0 VMax.: 255.0 V <3>
d1-21#2 Middle Output Frequency 2Default: 0.0Min.: 0.0 HzMax.: Defined by d1-13
d1-22#2 Middle Output Frequency Voltage 2Default: 0.0 VMin.: 0.0 VMax.: 255.0 V <3>
d1-23<9>Mode setting for V/F separation0 : V/F1 : V/F complete separation2 : V/F half separationDefault: 0Min.: 0Max.: 2
d1-24<9>Voltage source for V/F separation0 : Setting by d1-251 : Analog setting corresponds to the E3-01 or E3-07 = 20Default: 0Min.: 0Max.: 1
d1-25<9>Voltage digital setting for V/F separationSetting voltage digital for V/F separationDefault: A1-03Min.: 0VMax.: Defined to the rated voltage
d1-26<9>Voltage rise time of V/F separationSetting voltage rise time for V/F separationDefault:10.0 sMin.: 0.1 sMax.: 1000.0 s
d1-27<9>Voltage decline time of V/F separationSetting voltage decline time for V/F separationDefault: 10.0 sMin.: 0.1 sMax.: 1000.0 s
d1-28<9>Stop mode selection upon V/F separation0 : Frequency and voltage declining to 0 independently1 : Frequency declining to 0 after voltage declines to 0Default: 0Min.: 0Max.: 1
d2: Load Parameters
d2-00Load Rated CurrentSets the Load Rated current. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 10% of controller rated currentMax.: 200% of controller rated current
d2-01Load Rated SpeedSets the Load Rated speed used for slip compensation. This will be set automatically during Auto-Tuning. Alarm OPE17 will be detected when this value is set incorrectly.Default: A1-03Min.: 0 rpmMax.: 60000 rpm
d2-02No-Load CurrentSets the loadno-load current. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.0 AMax.: d2-00(excluding d2-00)
d2-03Number of PolesSets the number of loadpoles. This will be set automatically during Auto-Tuning.Default: 4Min.: 2Max.: 48
d2-04Line-to-Line ResistanceSets the line-to-line resistance. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.000 ΩMax.:65.000 Ω
d2-05Leakage InductanceSets the voltage drop caused by the loadleakage inductance relative to the Load Rated frequency and current. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.00 mHMax.:650.00 mH
d2-06Rotor ResistanceSets the rotor resistance. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.000 ΩMax.:65.000 Ω
d2-07Mutual InductanceSets the mutual inductance. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.0 mHMax.:6500.0 mH
d2-10Load Rated CapacitySets the Load Rated capacity. This will be set automatically during Auto-Tuning. (1HP = 0.746 kW)Default: o2-03Min.: 0.00 kWMax.: 650.00kW
d2-11#2 Rated CurrentSets #2 rated current. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 10% of controller rated currentMax.: 200% of controller rated current
d2-12#2 Rated SlipSets #2 rated slip. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.00 HzMax.: 20.00 Hz
d2-13#2 No-Load CurrentSets #2 no-load current. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0 AMax.: d2-11
d2-14Number of #2 PolesSets the number of #2 poles. This will be set automatically during Auto-Tuning.Default: 4Min.: 2Max.: 48
d2-15#2 Line-to-Line ResistanceSets the #2 line-to-line resistance. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.000 ΩMax.: 65.000 Ω
d2-16#2 Leakage InductanceSets the #2 voltage drop caused by the leakage inductance relative to the Load Rated frequency and current. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.00 mHMax.:650.00 mH
d2-17#2 Rotor ResistanceSets the #2 rotor resistance. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.000 ΩMax.: 65.000 Ω
d2-18#2 Mutual InductanceSets the #2 mutual inductance. This will be set automatically during Auto-Tuning.Default: o2-03, A1-06Min.: 0.00 mHMax.:6500.0 mH
d2-21#2 Rated CapacitySets the #2 rated capacitor. This will be set automatically during Auto-Tuning.Default: o2-03Min.: 0.00 kWMax.: 650.00kW
d3: PM Parameters
d3-00<7>PM Type Selection0 : IPM series1 : SPM seriesDefault: 1Range: 0, 1
d3-01PM Load Rated CapacitySets the Load Rated capacity.Default: Determined by o2-03Min.: 0.00 kWMax.: 650.00kW
d3-02PM Load Rated CurrentSets the Load Rated current.Default: Determined by o2-03Min.: 10% of controller rated currentMax.: 200% of controller rated current
d3-03Number of PM PolesSets the number of poles.Default: Determined by o2-03Min.: 2Max.: 48
d3-04PM Rotor Resistance (r 1)Sets the resistance per phase in units of 0.001 Ω. Refrain from change once this parameter is set.Default: Determined by o2-03Min.: 0.000 ΩMax.: 65.000 Ω
d3-05PM d-Axis Inductance (Ld)Sets the d-axis inductance in units of 0.01 mH. Refrain from change once this parameter is set.Default: Determined by o2-03Min.: 0.00 mHMax.: 600.00 mH
d3-06PM q-Axis Inductance (Lq)Sets the q-axis inductance in units of 0.01mH. Refrain from change once this parameter is set.Default: Determined by o2-03Min.: 0.00 mHMax.: 600.00 mH
d3-07PM Induction Voltage Constant 1 (Ke)Sets the induced peak voltage per phase in units of 0.1 mV/(rad/s) (electrical angle). Set this parameter when driving an IPM (SSR1 or SST4 series).Set 0 to d3-09 before setting.Default: Determined by o2-03Min.: 0.0 mV/(rad/s)Max.: 2000.0 mV/(rad/s)
d3-09PM Induction Voltage Constant 2 (Ke)Sets the induced line-to-line voltage in units of 0.1 mV/ (r/min) (mechanical angle). Set this parameter when driving an SPM.Set 0 to d3-07 before setting.Default: Determined by o2-03Min.: 0.0 mV/(r/min)Max.: 2000.0 mV/(r/min)
d3-10 <7>PM Load Rated VoltageSets the PM Load Rated voltage according to the nameplate.Default: 200.0 VMin.: 0.0 VMax.: 255.0 V <3>
d3-11 <7>PM Base FrequencySets the PM base frequency according to the nameplate.Default: 87.5 HzMin.: 0.0 HzMax.: 400.0 Hz
d3-12 <7>PM Base SpeedSets the PM base speed according to the nameplate.Default:1750 rpmMin.: 0 rpmMax.: 24000 rpm
Group E, Multi-Function Terminals
E1: Multi-Function Digital Inputs
E1-00Terminal S1Function Selection0: 2-Wire Sequence Control (Forward/Stop) /3-Wire Sequence Control (Stop)1: 2-Wire Sequence Control (Reverse/Stop) /3-Wire Sequence Control (Stop)2: 3-Wire Sequence3: Local/Remote SelectionDefault: 0Range: 0 to 73 / 100 to 173
E1-01Terminal S2Function SelectionDefault: 1Range: 0 to 73 / 100 to 173
E1-02Terminal S3Function Selection4: Command Source 1/2 Selection5 to 8: Multi-Step Speed Command 1 to 49: Jog FrequencyDefault: 23Range: 0 to 73 / 100 to 173
E1-03Terminal S4Function Selection10: Up Command11: Down Command12: Up 2 CommandDefault: 39Range: 0 to 73 / 100 to 173
E1-04Terminal S5Function Selection13: Down 2 Command14, 15: FJOG/RJOG Command16: Acc./Dec. Time Selection 1Default: 5Range: 0 to 73 / 100 to 173
E1-05Terminal S6Function Selection17: Acc./Dec. Time Selection 218: Acc./Dec. Ramp Hold19: Base BlockDefault: 6Range: 0 to 73 / 100 to 173
E1-06Terminal S7Function Selection20: No function21: Fast Stop (Normal Open)23 to 38: External Fault39: Fault Reset40: oH2 (AC controller Overheat Alarm)41: Multi-Function Analog Input Selection45: Communication Mode46: PID Disable47: PID Integral Reset48: PID Integral Hold49: PID Soft-Start On/Off50: PID Input Characteristics Switch51: #1/2 Switch52: Timer Input53, 54, 55: Offset Frequency 1/2/357: KEB Command 1 (Normal Open)60: Program Lockout61: Analog Frequency Command Hold63: External Speed Search Command65: DC Braking69: Controller Enabled70: Speed / torque control switch71: Zero Speed HoldingDefault: 9Range: 0 to 73 / 100 to 173
E1-07Terminal S8Function SelectionDefault: 19Range: 0 to 73 / 100 to 173
E1-08Terminal command0: Two-line / Three-line mode 1Default: 0
<9>mode1: Two-line / Three-line mode 2Min.: 0Max.: 1
E2: Multi-Function Digital Output
E2-00Relay 1 Function Selection0 : During Run1 : Zero Speed Holding2 : Frequency (Speed) AgreeDefault: 11Range: 0 to 49 / 100 to 149
E2-01Relay 2 Function Selection3 :User-Defined Frequency (Speed ) Agree4 : Controller Ready5 : Uv (Undervoltage) DetectionDefault: 0Range: 0 to 49 / 100 to 149
E2-02D1-DC Function Selection (Open Collector)6 : During Baseblock7 : Retain8 : Frequency Command SourceDefault: 1Range: 0 to 49 / 100 to 149
E2-03D2-DC Function Selection (Open Collector)9 : Frequency Command Loss10: Run Command Source11 : Fault12 : Communication Mode13 : Alarm14 : Fault Restart15 : Timer Output16 : Frequency (FOUT) Detection 117 : Frequency (FOUT) Detection 218: Overvoltage/ Undervoltage Detection 1 (normal open)20: Overvoltage/ Undervoltage Detection 2 (normal open)22 : During Reverse23: #1/ 2 Selection24: During Regeneration25 : During Restart26 : Overload Pre-Alarm (oL1)27 : Controller Overheat Pre-Alarm (oH)28 : Retain29 : Mechanical Weakening Detection (Normal Open)31 : During Torque Limit (Currently Control)32 : During Speed Limit33 : During Speed Limit Circuit Operation (For Torque Control)34 : Zero Speed Holding Stop35: During Frequency Output36: Controller EnabledDefault: 2Range: 0 to 49 / 100 to 149
37: Watt Hour Pulse Output38: Local/Remote Mode39: During Speed Search40: PID Feedback Low41: PID Feedback High42: During KEB Operation43: Retain44: During Fast Stop45: Internal Cooling Fan Alarm49: Brake control (Desired frequency attained)100 to 149: 0 to 49 with Inverse Output
E2-05Watt Hour Output UnitSelects the output unit for the terminal assigned to E2-00 or E2-03=37 for one pulse signal.0: 0.1 kWh units1: 1 kWh units2: 10 kWh units3: 100 kWh units4: 1000 kWh unitsDefault: 0Min.: 0Max.: 4
E2-06<7>Relay 1 On DelayThe definition of a relay1 on delay time.Default: 0.0sMin.: 0.0sMax.: 3600.0s
E2-07<7>Relay 1 Off DelayThe definition of a relay1 off delay time.Default: 0.0sMin.: 0.0sMax.: 3600.0s
E2-08<7>Relay 2 On DelayThe definition of a relay2 on delay time.Default: 0.0sMin.: 0.0sMax.: 3600.0s
E2-09<7>Relay 2 Off DelayThe definition of a relay2 off delay time.Default: 0.0sMin.: 0.0sMax.: 3600.0s
E3: Multi-Function Analog Input
E3-00Terminal A1 Signal Level Selection0: 0 to 10 V1:-10 to 10 VDefault: 0Range: 0, 1
E3-01Terminal A1 Function Selection0: Main Frequency Command1: Frequency Gain2: Output Frequency Lower Limit3: Auxiliary Frequency Command4: Output Voltage Bias5: Acc./Dec. Time Gain (Decrease Only)6: DC Braking (DB) Current7: Stall Prevention Level During Run8: PID Feedback9: PID Target10: Differential PID Feedback11: Overtorque/ Undertorque Detection12, 13, 14, 17: Forward/Reverse/RegenerationRange/Forward and Reverse Torque Limit15: Toque Command / Torque Limit During Speed Control16: Torque Compensation18: Communication Mode 119: Communication Mode 220: V/F separation voltage21: No functionDefault: 0Range: 0 to 21
E3-02<4>Terminal A1 Input GainSets the terminal A1 input gain as a percentage when inputting 10VDefault: 100.0 %Min.: -999.9 %Max.: 999.9 %
E3-03<4>Terminal A1 Input Voltage BiasSets the terminal A1 input voltage bias as a percentage when inputting 0VDefault: 0.0 %Min.: -999.9 %Max.: 999.9 %
E3-05Terminal A1 Input Filter TimeSets the terminal A1 primary delay filter time, which can eliminate the interferenceDefault: 0.05 sMin.: 0.00 sMax.: 2.00 s
E3-06Terminal A2 Signal Level Selection0: 0 to 20 mA1: 4 to 20 mA2: 0 to 10 V3: 0 to 5 VDefault: 1Range: 0, 1, 2, 3
E3-07Terminal A2 Function Selection0: Main Frequency Command1: Frequency Gain2: Output Frequency Lower Limit3: Auxiliary Frequency Command4: Output Voltage Bias5: Acc./Dec. Time Gain (Decrease Only)6: DC Braking (DB) Current7: Stall Prevention Level During Run8: PID Feedback 9: PID Target Value10: Differential PID Feedback11: Overtorque/Undertorque Detection12, 13, 14, 17: Forward/Reverse /Regeneration Range/ Forward and Reverse Torque Limit15: Torque Limit Using Torque Command/Speed Limit16: Slip Compensation18, 19 :Communication Mode20: V/F separation voltage21: No functionDefault: 3Range: 0 to 21
E3-08<4>Terminal A2 Input GainSets the terminal A2 input gain as a percentage when inputting 10VDefault: 100.0 %Min.: -999.9 %Max.: 999.9 %
E3-09<4>Terminal A2 Input Voltage BiasSets the terminal A2 input voltage bias as a percentage when inputting 0V.Default: 0.0%Min.: -999.9 %Max.: 999.9 %
E3-10<7>Terminal A2 (4-20mA) Loss Action Selection0: Disabled1: Run According to P4-03 Setting and Display ANL2: Disacceleration to 0Hz and Display ANL3: Controller Stop and Display ACEDefault: 0Range: 0 to 3
E3-11Terminal A2 Input Filter TimeSets the terminal A2 primary delay filter time, which can eliminate the interference.Default: 0.05 sMin.: 0.00 sMax.: 2.00 s
E3-12Analog Input Terminal Enable/Disable SelectionEnables the analog inputs when Multi-Function Terminal Input E1-□□ = 41 (Multi-Function Analog Input Selection).0: Both Terminal A1 and A2 Disabled1: Only Analog Input Terminal A1 Enabled2: Only Analog Input Terminal A2 Enabled3: Both Terminal A1 and A2 EnabledDefault: 3Range: 0, 1, 2, 3
E4: Multi-Function Analog Output
E4-00Terminal FM Signal Level Selection0 : 0 to 10 V1 : -10 to 10 VDefault: 0Range: 0, 1
E4-01Terminal FM Monitor SelectionSelects the terminal FM monitor.0 : Frequency Command1 : Output Frequency2 : Output Current3 : Speed4 : Output Voltage5 : DC Voltage6 : Output Power7 : Torque Command8 : AI1 Input9 : AI2 Input10 : Soft Starter Output Frequency11 : Pulse Train Input12 : No functionDefault: 1Range: 0 to 12
E4-02<4>Terminal FM Monitor GainSets the terminal FM monitor gain.Default: 100.0 %Min.: -999.9 %Max.: 999.9 %
E4-03<4>Terminal FM Monitor Voltage BiasSets the terminal FM voltage bias.Default: 0.0 %Min.: -999.9 %Max.: 999.9 %
E4-04Terminal AM Signal Level Selection0: 0 to 10 V1: 0 to 20 mA2: 4 to 20 mADefault: 0Range: 0, 1, 2
E4-05Terminal AM Monitor SelectionSelects the terminal AM monitor.0 : Frequency Command1 : Output Frequency2 : Output Current3 : Speed4 : Output Voltage5 : DC Voltage6 : Output Power7 : Torque Command8 : AI1Input9 : AI2Input10: Soft Starter Output Frequency11 : Pulse Train Input12 : No functionDefault: 2Range: 0 to 12
E4-06<4>Terminal AM Monitor GainSets the terminal AM gain.Default: 100.0 %Min.: -999.9 %Max.: 999.9 %
E4-07<4>Terminal AMMonitor VoltageBiasSets the terminal AM voltage bias.Default: 0.0 %Min.: -999.9 %Max.: 999.9 %
E5:Pulse Train Input/ Output
E5-00Pulse Train InputFunction SelectionSelects the function for terminal RP.0 :Frequency Command1 : PID Feedback2 : PID Target3 : Speed Detection (Closed-Loop V/F Control)(Only enabled when #1 is selected in V/F control method)Default: 0Range: 0, 1, 2, 3
E5-01<4>Pulse Train InputScalingSets the frequency equal to 100% frequency in Hz.Default: 1440 HzMin.: 100 HzMax.: 32000 Hz
E5-02<4>Pulse Train InputGainSets the level of the input gain to terminal RP.Default: 100.0%Min.: 0.0 %Max.: 1000.0 %
E5-03<4>Pulse Train InputVoltage BiasSets the level of the input voltage bias when no signal (0Hz) is input to terminal RP.Default: 0.0%Min.: -100.0Max.: 100.0
E5-04<4>Pulse Train InputFilter TimeSets the pulse train input primary filter time in seconds.Default: 0.10 sMin.: 0.00 sMax.: 2.00 s
E5-05Pulse Train InputMinimumFrequencySets the minimum frequency detected by the pulse train input. Enabled when E5-00 = 0, 1, 2.Default: 0.5 HzMin.: 0.1 HzMax.: 1000.0 Hz
E5-06<4>Pulse TrainMonitor SelectionSets the function of pulse train output terminal MP0 : Frequency Command1 : Output Frequency2 : Soft Starter Output Frequency3 : PID Feedback Value4 : PID Target ValueDefault: 0Range: 0 to 4
E5-07<4>Pulse TrainMonitor ScalingSets the pulse train output frequency when the specified monitor item is at 100%.Default: 1440 HzMin.: 100 HzMax.: 32000 Hz
E5-08Terminal RPFunction Selection0 : Pulse train input1 : PWM signal inputDefault: 0Min.: 0Max.: 1
E5-09Average PWM1 to 100 timesDefault: 1
<4>Signal TimesMin.: 1Max.: 100
E5-10PWM Signal Cycle1 to 999 msDefault: 100 msMin.: 1 msMax.: 999 ms
E6: Optional Communication Card Settings
E6-04<7>Torque Command Source Selection0 : Torque Command Given by AI1 : Torque Command Given by CommunicationDefault: 0Min.: 0Max.: 1
E6-06Controller Station AddressSets the controller station address.Default: 1Range: 1 to 31
E6-07RS-485CommunicationBaud Rate SettingSets the baud rate for terminals SG(+) and SG(-) of RS-485 communication.0: 1200 bps (bit/sec)1: 2400 bps2: 4800 bps3: 9600 bps4: 19200 bps5: 38400 bps6 : 57600 bps7 : 76800 bps8 : 115200 bpsDefault: 3Range: 0 to 8
E6-08RS-485CommunicationParity SelectionSelects the communication parity for terminals SG(+) and SG(-) of RS-485 communication.0: 8, N, 2 (Modbus RTU)1: 8, N, 1 (Modbus RTU)2: 8, E, 1 (Modbus RTU)3: 8, O, 1 (Modbus RTU)4: 8, N, 2 (Modbus ASCII)5: 8, N, 1 (Modbus ASCII)6: 8, E, 1 (Modbus ASCII)7: 8, O, 1 (Modbus ASCII)8: 7, N, 2 (Modbus ASCII)9: 7, N, 1 (Modbus ASCII)10: 7, E, 1 (Modbus ASCII)11: 7, O, 1 (Modbus ASCII)Default: 1Range: 0 to 11
E6-09CommunicationError DetectionTimeDetermines the detection time to trigger the communication error. (This function is disabled when set to 0)Default: 0.0 sRange: 0.0 to 10.0 s
E6-10Transmit Wait TimeSets the wait time between sending and receiving data.Default: 5msRange: 0 to 65 ms
E6-11Controller Operation During Communication Error0 : Display CE Alarm Only. Controller continues operation.1 : Display CE Fault. Controller coasts to stop.Default: 0Range: 0 to 1
Group P, Protections
P1: Protection Function
P1-00Protection Function Selection0 : Disabled(Overload Protection Disabled)1 : General-Purpose (Standard)2 : Controller Dedicated(Constant Torque Range 1 : 10)3 : Vector (Constant Torque Range 1 : 100)4 : Derated Torque PM5 : Constant Torque PM(Constant Torque Range 1 : 500)Sets 0 (disabled) when using one controller to run more than one. Install an overload relay between the controller and each.Default: 0Range: 0 to 5
P1-01Overload Protection TimeSets the time for the controller to shut down on overload.Default: 1.0 minuteMin.: 0.1 minutesMax.: 5.0 minutes
P1-03Overheat Fault Operation Selection (MT Input)Selects the controller operation when the MT input signal reaches the level of overheat fault.0 : Ramp to Stop1 : Coast to Stop2 : Fast Stop (Follows the fast stop time set in C1-08)Default: 1Range: 0 to 2
P2: Momentary Power Loss
P2-00Momentary Power Loss Operation Selection0 : Disabled (Default)1 : Recover if CPU Has Power2 : KEB function if CPU Has Power3 : Ramp to Stop with KEB DecelerationDefault: 0Range: 0, 1, 2, 3
P2-01Minimum Baseblock (bb) TimeSets the minimum baseblock time when power is restored right after a momentary power loss.This determines the time the controller waits for the residual voltage in the to dissipate.Increase this value if overcurrent or overvoltage occurs at the beginning of Speed Search and DC Braking.Default: Determined by o2-03, A1-06Min.: 0.1 sMax.: 5.0 s
P2-03Uv (Undervoltage) Detection LevelSets the voltage level of undervoltage detection or KEB function activation.Default: Determined by d1-00, o2-03Min.: 150VMax.: 210V <3>
P2-04KEB Deceleration TimeSets the time to decelerate during KEB function.Default: 0.0 sMin.: 0.0 sMax.: 6000.0 s
P2-05Acceleration Time after KEBSets the time to reaccelerate from the speed when KEB function was deactivated to the set frequency command (operation frequency before power loss).When set to 0.0 s, the controller will accelerate to the previously active frequency according to the active acceleration time set by any of C1-00, C1-02, C1-04 or C1-06.Default: 0.30 sMin.: 0.00sMax.: 6000.0s
P2-06 <7>Emergency stop level before power offSetting P2-06 for Emergency stop. When the detected voltage is below P2-06, the controller will immediately decelerate in accordance with the emergency stop time (C1-08).Default: 250VMin.: 150VMax.: 280V
P2-07KEB Detection TimeSets the minimum duration of KEB operation after activation.KEB function will operate according to this detection time even if power recovers within this duration.Default: 50 msMin.: 0 msMax.: 2000 ms
P2-08Voltage Target During KEBSets the target value for the main circuit DC voltage or to deactivate KEB.Default: Determined by d1-00Min.: 150VMax.: 400V <3>
P2-09KEB Method Selection0 : KEB Operation Method 11 : KEB Operation Method 22 : KEB Operation Method 3Default: 0Range: 0, 1, 2
P2-10Automatic voltage regulation (AVR)0 : AVR is disabled1 : AVR is enabledDefault: 1Range: 0, 1
P2-11 <7>Emergency stop Selection before power off0 : Disabled1 : EnabledDefault: 0Range: 0, 1
P3: Stall Prevention
P3-00Stall Prevention during Acceleration0 : Disabled1 : Enabled the value set in P3-01.Acceleration stops when the output currentexceeds the value set in P3-01. Acceleration continues when the output current drops 15% below the value set in P3-01.Default: 1Range: 0, 1
P3-01Stall Prevention Level during AccelerationSets the output current level to activate the Stall Prevention function during acceleration.Default: Determined by A1-06Min.: 0%Max.: 150%
P3-02Stall Prevention Limit during AccelerationSets the lower limit of Stall Prevention in the constant power range as a percentage of the controller rated output current.Default: 50%Min.: 0%Max.: 100%
P3-03Stall Prevention during Deceleration0 : DisabledThe controller decelerates according to the set deceleration time1 : Enabled (Without Braking Resistor)Default: 1Range: 0, 1
P3-04Stall Prevention Level during DecelerationSets the voltage level to activate the Stall Prevention function during deceleration.Default: <8>Min.: 330VMax.: 410V <3>
P3-05Stall Prevention during Run0 : Disabled1 : Enabled (Deceleration Time 1)2 : Enabled (Deceleration Time 2)Default: 1Range: 0, 1, 2
P3-06Stall Prevention Level during RunSets the current level to activate the Stall Prevention function during run.Default: Determined by A1-06Min.: 30%Max.: 150%
P3-11Stall Deceleration Time during AccelerationSets the deceleration time for a stall during accelerationDefault: 0.0 sMin.: 0.0 sMax.: 6000 s
P4: Frequency Detection
P4-00Frequency Detection LevelSets the detection level and width for the multi-function output terminal.Default: 30.0 HzMin.: 0.0 HzMax.: Determined by d1-02, L2-00
P4-01Frequency Detection WidthDefault: 2.0 HzMin.: 0.1 HzMax.: 25.5 Hz
P4-02Frequency Command Loss Detection SelectionSets the controller operation when a frequency command loss is detected.0: Controller Stop1: Continue operation according to the setting in P4-03.Default: 0Range: 0, 1
P4-03FrequencyCommand at FrequencyCommand LossSets the frequency command level at which the controller runs when detecting a frequency command loss and when L4-02 is set to 1. Sets the value as a percentage of the maximum output frequency set in d1-02. (Sets the value as a percentage of the #2 maximum output frequency set in d1-13.)Default: 80%Min.: 0.0%Max.: 100.0%
P4-04FrequencyCommand LossDetection TimeWhen the frequency command falls below 90% of the command within this detection time, the frequency command loss will be detected.Default: 20 msMin.: 20 msMax.: 400 ms
P5: Fault Restart
P5-00Number of Auto Restart AttemptsSets the number of times to automatically attempt to restart the controller when detecting GF, OVA, OVD, OVC, OCA, OCD, OCC, OH, OL1, OL2, OT1, OT2, PF and LF1.Default: 0Min.: 0Max.: 10
P5-01Auto Restart Fault Output Operation0 : Fault Output Disabled1 : Fault Output EnabledDefault: 0Range: 0, 1
P5-02Fault Restart Interval TimeSets the amount of time between restart attempts.Default: 10.0 sMin.: 0.5 sMax.: 600.0 s
P6: Over torque / Undertorque Detection
P6-00Over torque /UndertorqueDetectionSelection 1Sets the operation when the current or torque exceeds the P6-01 level for longer than the time set to P6-02.0 : Disabled1 : Over torque Alarm at Speed Agree2 : Over torque Alarm at Run3 : Over torque Fault at Speed Agree4 : Over torque Fault at Run5 : Undertorque Alarm at Speed Agree6 : Undertorque Alarm at Run7 : Undertorque Fault at Speed Agree8 : Undertorque Fault at RunDefault: 0Range: 0 to 8
P6-01Over torque /UndertorqueDetection Level 1Sets the level for over torque/undertorque detection 1.Default: 150%Min.: 0%Max.: 300%
P6-02Over torque /UndertorqueDetection Time 1Sets the time for over torque/undertorque detection 1.Default: 0.1 sMin.: 0.0 sMax.: 10.0 s
P6-03Over torque /UndertorqueDetectionSelection 20 : Disabled1 : Over torque Alarm at Speed Agree2 : Over torque Alarm at Run3 : Over torque Fault at Speed Agree4 : Over torque Fault at Run5 : Undertorque Alarm at Speed Agree6 : Undertorque Alarm at Run7 : Undertorque Fault at Speed Agree8 : Undertorque Fault at RunDefault: 0Range: 0 to 8
P6-04Over torque /UndertorqueDetection Level 2Sets the level for over torque/undertorquedetection 2.Default: 150%Min.: 0%Max.: 300%
P6-05Over torque /UndertorqueDetection Time 2Sets the time for over torque/undertorquedetection 2.Default: 0.1 sMin.: 0.0 sMax.: 10.0 s
P6-06MechanicalWeakeningDetectionOperationSets the speed range to detect mechanicalweakening and the operation when detected.0 :Disabled1 : Continue Operation if the Speed (Signed) isabove P6-072 : Continue Operation if the Speed (Unsigned)is above P6-073 : Stop Operation if the Speed (Signed) isabove P6-074 : Stop Operation if the Speed (Unsigned) isabove P6-075 : Continue Operation if the Speed (Signed) isbelow P6-076 : Continue Operation if the Speed (Unsigned)is below P6-077 : Stop Operation if the Speed (Signed) isbelow P6-078 : Stop Operation if the Speed (Unsigned) isbelow P6-07Default: 0Range: 0 to 8
P6-07MechanicalWeakeningDetection SpeedLevelSets the speed level for Mechanical WeakeningDetection as a percentage of the maximumoutput frequency.Default: 110.0%Min.: -110.0%Max.: 110.0%
P6-08MechanicalWeakeningDetection TimeIf the condition set in P6-06 lasts the time set inthis parameter, Mechanical Weakening isdetected.Default: 0.1 sMin.: 0.0 sMax.: 10.0 s
P6-09MechanicalWeakeningDetection StartTimeSets the cumulative controller operation time toactivate Mechanical Weakening Detection. IfU3-00 reaches the value set in this parameter,Mechanical Weakening is detected.Default: 0Min.: 0Max.: 65535
P6-10Forward Torque LimitSets the torque limits as a percentage of the Load Rated torque.Default: 200%Min.: 0%Max.: 300%
P6-11Reverse Torque LimitDefault: 200%Min.: 0%Max.: 300%
P6-12Forward Regenerative Torque LimitDefault: 200%Min.: 0%Max.: 300%
P6-13Reverse Regenerative Torque LimitDefault: 200%Min.: 0%Max.: 300%
P6-14Torque Limit Integral Time ConstantSets the integral time constant for the torque limit. Set shorter time for faster torque limitDefault: 200 msMin.: 5 msMax.: 10000 ms
P6-15Torque Limit Control Selection during Acc./Dec0 : Proportional Control (Integral Control at constant speed)1 : Integral ControlDefault: 0Range: 0, 1
P7: Controller Protection
P7-00Input Phase Loss ProtectionEnables or disables the input phase loss detection.0 : Disabled1 : EnabledDefault: 1Range: 0, 1
P7-01Output Phase Loss ProtectionSets the output phase loss detection.0 : Disabled1 : Enabled when One Phase is Lost2 : Enabled when Two Phases are LostDefault: 0Range: 0, 1, 2
P7-02Output Ground Fault DetectionEnables or disables the output ground fault detection.0 : Disabled1 : EnabledDefault: 0Range: 0, 1
P7-03Heatsink Cooling Fan Operation <6>Sets the heatsink cooling fan operation.0 : Enabled when controller is running1 : Enabled when power supply is On2 :When the fin temperature reaches 60 degrees, the fan starts runningDefault: 0Range: 0, 1
P7-04Heatsink Cooling Fan Off-Delay TimeWhen P7-04=0, sets the cooling fan off-delay time that the controller waits to disabled the cooling fan after run command is released.Default: 60 sMin.: 0 sMax.: 300 s
P7-05AmbientSets the ambient temperature.Default: 40 °C
Temperature SettingAutomatically decreases the controller rated current when the ambient temperature is higher than the temperature specified in controller specifications.Min.: -10 °CMax.: 50 °C
P7-06oL2 Detection Time Reduction at Low SpeedDetermines whether to reduce the oL2 (Controller Overload) fault detection time at low speed (below 6 Hz) to prevent premature output transistor failures.0 : Detection time is not reduced1 : Detection time is reducedDefault: 0Range: 0, 1
P7-11High Current Alarm SettingSets the High Current Alarm (HCA) when the output current is too high0 : Disabled (No Alarm)1 : Enabled (Alarm)Default: 0Range: 0, 1
P7-12Installation Method SelectionSelects the installation type. The controller overload detection limit will be changed according to the selection.0 : IP20 Enclosure in a Cabinet1 : Side-by-Side Mounting2 : NEMA 1 EnclosureDefault: 0Range: 0, 1, 2
P7-13DC Braking Level SettingSets the DC braking transistor level.Default: Defined by d1-00 <3><8>Range: 330 to 400V<3>
Group n, Special Adjustments
n1: Hunting Prevention
n1-00Hunting Prevention Setting0 : Disabled1 : EnabledDefault: 0Range: 0, 1
n1-01<4>Hunting Prevention GainIf the oscillates during light load, gradually increase this value by units of 0.1. If the stalls, gradually decrease this value by units of 0.1.Default: 1.00Min.: 0.00Max.: 2.50
n2 : Speed Feedback Control Selection
n2-00<9>Speed Feedback Control SelectionSelect Speed Feedback inhibition of valid / invalidDefault: 0.00Min.: 0.00Max.: 200.00
n4 : Feed Forward Control <7>
n4-00Feed Forward Control Selection0: Disabled1: EnabledDefault: 0Range: 0, 1
n4-02Feed Forward Control Gain0.00 ~ 100.00Default: 0.00Min.: 0.00Max.: 100.00
n4-03Inertia input0.000 ~ 0.100Default: 0.000Min.: 0.000Max.: 0.100
n6: PM Control
n6-02Initial Rotor Position DetectionSelects the method used to detect the rotor position at start.0 : Pull In1 : High Frequency Injection2 : Pulse InjectionDefault: 1Range: 0, 1, 2
n6-03Speed Feedback Detection Control GainIncrease the gain if oscillates. Decrease the gain if controller response is too slow.Default: 0.80Min.: 0.00Range: 10.00
n6-11Output Voltage LimitSets the limit for output voltage to avoid voltage saturation. Set this value lower than the actual input voltage.Default: 200.0 VMin.: 0.0Max.: 230.0
Group o, Keypad Function Settings
o1: Display Setting
o1-00Frequency Command Setting/Display Unit0 : Use units of 0.01 Hz1 : Use units of 0.01% (100% as maximum output frequency)2 : Use units of min-1 (automatically calculated by maximum output frequency and number of poles)3 : Use user-defined units (defined by o1-02 and o1-03)Default: 0Range: 0 to 3
o1-01<7>V/f Frequency ParameterUint Setting0 : Hz1 : min -1(r/min)Default: 0Range: 0 to 1
o1-02User-Defined Frequency Command Setting/Display1 to 60000Default: Determined by o1-00Min.: 1Max.: 60000
o1-03Frequency Command Setting/DisplayDecimal Places0 to 3Default: Determined by o1-00Min.: 0Max.: 3
o2: Multi-Function Selection
o2-00LO/RE (LOCAL/REMOTE) Key Function SelectionEnables or disables LO/RE key on the keypad.0 : Disabled1 : EnabledSwitches between Local and Remote OperationDefault: 1Range: 0, 1
o2-01STOP Key Function SelectionEnables or disables the STOP key on the keypad when the controller is controlled from a remote source.0 : Disabled1 : EnabledThe STOP key always stops controller operation even if the command source is not set to the keypad.Default: 1Range: 0, 1
o2-03 <2>Controller Capacity SelectionSet this parameter after replacing the terminal block or controller modules.Default: <2>Determined by controller capacity
o2-04ENTER Key Function During Frequency Command Setting0 : ENTER Key Required1 : ENTER Key Not RequiredWhen entering a frequency command, the output frequency changes immediately by UP or DOWN key without pressing ENTER.Default: 0Range: 0, 1
o2-05 <7>Action Select When LCM Keypad Disconnection0 : Disabled1 : EnabledDefault: 0Range: 0, 1
o2-06Operation Direction at Power Up when Using Keypad0 : Forward1 : ReverseThis parameter is enabled only when the keypad is selected as the Run command source.Default: 0Range: 0, 1
o4: Maintenance Settings
o4-00Cumulative Operation Time SettingSets the initial value by 10 hours to start keeping track of cumulative operation time.Default: 0 hMin.: 0 hMax.: 6000 h
o4-01Cumulative Operation Time SelectionSelects the conditions in which the controller keeps track of the cumulative operation time.0 : Time of Power OnKeeps track of time from the power up to power cutoff.1 : Time of RunKeeps track of time when the output voltage is active.Default: 0Range: 0, 1
o4-02Cooling FanOperation TimeSettingSets the initial value to start keeping track of cumulative fan operation time. View the cumulative fan operation time in U3-01.Default: 0 hMin.: 0 hMax.: 6000 h
o4-06U2 Reset SettingResets the data for U2-□□ (Fault Information) as these data will not be reset by A1-03 (Reset).0 : Disabled1 : EnabledDefault: 0Range: 0, 1
o4-07kWh MonitorInitialization0 : U3-08 and U3-09 monitor data is not reset when the controller is initialized.1 : U3-08 and U3-09 monitor data is reset when the controller is initialized.Default: 0Range: 0, 1
Group t, Auto-Tuning
t1: IM Auto-Tuning
t1-00#1/2 Selection1 : #1Set details in d1-00 to d1-11, d2-00 to d2-10.2 : #2Set details in d1-12 to d1-22, d2-11 to d2-22.Default: 1Range: 1, 2
t1-01Auto-TuningMethod Selection0 : Rotational Auto-Tuning1 : Stationary Auto-Tuning2 : Stationary Auto-Tuning for Line-to-Line ResistanceDefault: 0Range: 0, 1, 2
t1-02Output PowerSets the Load Rated output power in kW units.Note: 1HP (Horse Power) = 0.746kWDefault: <2>Min.: 0.00 kWMax.: 650.00 kW
t1-03Load Rated VoltageSets the Load Rated voltage according to the nameplate.Default: 200.0 VMin.: 0.0 VMax.: 255.0 V <3>
t1-04Load Rated CurrentSets the Load Rated current according to the nameplate.Default: <2>Min.: 10% of controller rated currentMax.:200% of controller rated current
t1-05Base FrequencySets the base frequency according to the nameplate.Default: 50.0 HzMin.: 0.0 HzMax.: 400.0 Hz
t1-06Number of PolesSets the number of poles according to the nameplate.Default: 4Min.: 2Max.: 48
t1-07Base SpeedSets the base speed according to the nameplate.Default: 1450 rpmMin.: 0 rpmMax.: 24000 rpm
t1-08PG Number of Pulses Per RevolutionSets the number of pulses per revolution for the PG (pulse generator or encoder).Default: 1024 pprMin.: 0 pprMax.: 60000 ppr
t1-09No-Load Current (Stationary Auto-Tuning)Sets the no-load current for the .After the output power and rated current are set in t1-02 and t1-04, this parameter will automatically display the no-load current of a standard . The no-load current must be entered according to the test report.Default: Defined by o2-03 · A1-06Min.: 0 AMax.: t1-04
t1-12Auto-Tuning SettingEnables or disables Auto-Tuning when A1-02=0 to 30 : Disabled1 : EnabledDefault: 0Range: 0, 1
t2: PM Auto-Tuning
t2-00PM Auto-Tuning Method Selection0 : PM Initial Position Stationary Auto-Tuning1 : PM Rotor Resistance Stationary Auto-Tuning2 : PM Synchronous Inductor Stationary Auto-Tuning3 : PM Back EMF Rotational Auto-TuningTo ensure the torque accuracy, perform one of the following before selecting.Perform Auto-Tuning.Set the correct value according to the test report or nameplate.Default: 0Range: 0, 1, 2, 3
t2-02PM Type Selection0 : IPM1 : SPMDefault: 1Range: 0, 1
t2-03PM Output PowerSets the PM Load Rated output power in kW units.Note: 1HP (Horse Power) = 0.746kWDefault: <2>Min.: 0.00 kWMax.: 650.00 kW
t2-04PM Load Rated VoltageSets the PM Load Rated voltage according to the nameplate.Default: 200.0 VMin.: 0.0 VMax.: 255.0 V <3>
t2-05PM Load RatedCurrentSets the PM Load Rated current according tothe nameplate.Default: 50% ofcontroller rated currentMin.: 10% of controller rated currentMax.: 200% of controller rated current
t2-06PM Base FrequencySets the PM base frequency according to the nameplate.Default: 87.5 HzMin.: 0.0 HzMax.: 400.0 Hz
t2-07Number of PM PolesSets the number of PM poles according to the nameplate.Default: 6Min.: 2Max.: 48
t2-08PM Base SpeedSets the PM base speed according to the nameplate.Default:1750 rpmMin.: 0 rpmMax.: 24000 rpm
t2-09PM Rotor ResistanceSets the PM rotor resistance per phase according to the nameplate.Default: 0.000 ΩMin.: 0.000 ΩMax.: 65.000 Ω
t2-10PM d-Axis InductanceSets the PM d-axis inductance according to the nameplate.Default: 0.00 mHMin.: 0.00 mHMax.: 600.00 mH
t2-11PM q-Axis InductanceSets the PM d-axis inductance according to the nameplate.Default: 0.00 mHMin.: 0.00 mHMax.: 600.00 mH
t2-12PM Induced Voltage Constant Unit Selection0 : mV/(r/min)d3-09 will be used, and d3-07 will automatically be set to 0.1 : mV/ (rad/s)d3-07 will be used, and d3-09 will automatically be set to 0.Default: 1Range: 0, 1
t2-13PM Induced Voltage Constant (Ke)Sets the PM induced voltage constant according to the nameplate.Default: <2>Min.: 0.1Max.: 2000.0
t2-14PM Auto-Tuning CurrentSets the amount of current for Auto-Tuning as a percentage of the Load Rated current. Increase this value when inertia is high.Default: 30%Min.: 0%Max.: 120%
t2-15<7>PM PG Number of Pulses PerRevolutionSets the number of pulses per revolution for the PG (pulse generator or encoder).Default: 1024 pprMin.: 0 pprMax.: 60000 ppr
t2-17PM Auto-Tuning Setting0 : Disabled1 : EnabledDefault: 0Range: 0, 1
Group F, Option Settings
F1: PG Card Settings
F1-00PG Pulse NumberSets the number of pulses (pulse generator and encoder) per resolution for PG.Default: 1024 pprMin.: 1 pprMax.: 60000 ppr
F1-01PG Rotation SettingSelects the direction indicated by the PG pulses.0 : A pulse leads with Forward fun command.1 : B pulse leads with Forward fun command.Default: Determined by A1-02Range: 0, 1
F1-02PG Output Division RatioSets the division ratio of pulse output for a PG card. Set X for a ratio of 1/X.When only A pulse is set, monitor pulse output will be 1:1 regardless of the setting in F1-02.Default: 1Min.: 1Max.: 255
F1-03PG Signal Selection0 : Channel A Only1 : Channels A and BDefault: 1Range: 0, 1
F1-04PG Disconnection Detection0 : Disabled1 : EnabledDefault: 1Range: 0, 1
F1-06PG Open (PGo)Operation SettingSets the operation for a PGo fault.0: Ramp to Stop (Active Deceleration))1: Coast to Stop2: Alarm OnlyDefault: 1Range: 0, 1, 2
F1-07PG Open (PGo)Detection TimeSets the time to detect the signal before triggering PGo fault.Default: 2.0 secMin.: 0.0 sMax.: 10.0 s
F1-08Overspeed (oS)Operation SettingSets the operation for an oS fault.0: Ramp to Stop (Active Deceleration)1: Coast to Stop2: Alarm OnlyDefault: 1Range: 0, 1, 2
F1-09Overspeed (oS)Detection LevelSets the Overspeed (oS) detection level as a percentage of the maximum output frequency (d1-02). An oS fault will be triggered if the speed feedback is greater than the level set in F1-09 for longer than the delay time set in F1-10.speed feedback = F1-09 *d1-02.Default: 115%Min.: 0 %Max.: 120 %
F1-10Overspeed (oS)Detection Delay TimeDefault: 0.5 secMin.: 0.0 secMax.: 2.0 sec
F1-11Speed Deviation (dEv) OperationSettingSets the operation for a dEv fault.0: Ramp to Stop (Active Deceleration)1: Coast to Stop2: Alarm OnlyDefault: 2Range: 0, 1, 2
F1-12Speed Deviation (dEv) Detection LevelSets the speed deviation (dEv) detection level as a percentage of the maximum output frequency (d1-02). A dEv fault will be triggered if the difference between the speed feedback and frequency command is greater than the level set in F1-12 for longer than the delay time set in F1-13.Default: 10%Min.: 0 %Max.: 50 %
F1-13Speed Deviation (dEv) Detection Delay TimeDefault: 0.5 secMin.: 0.0 secMax.: 10.0 sec
F1-14PG Number of Gear Teeth 1Sets the number of the gear teeth (ratio) on the side between the shaft and PG encoder.When 0 is set to either F1-14 or F1-15, the ratio will be 1.Default: 0Min.: 0Max.: 60000
F1-15PG Number of Gear Teeth 2Sets the number of the gear teeth (ratio) on the machinery side between the shaft and PG encoder.When 0 is set to either F1-14 or F1-15, the ratio will be 1.Default: 0Min.: 0Max.: 60000
F1-16PG dv3 (Inversion Detection)Detection Setting0 :Disabledn :Sets the number of detection times to trigger dv3.Default: 10 timesMin.: 0 timesMax.: 10 times
F1-17PG dv4 (Inversion Prevention Detection)Detection Setting0 :Disabledn :Sets the number of pulses to trigger dv4Default: 128Min.: 0Max.: 5000
F2-00Retain
F2-01<9>CANopen Station AddressSetting CANopen Station AddressDefault: 1Min.: 1Max.: 127
F2-02<9>CANopenrCommunicationBaud Rate SettingSetting CANopen Communication Baud Rate0 : 1Mbps1 : 800Kbps2 : 500kbps3 : 250 kbps4 : 125 kbps5 : 100 kbps6 : 50 kbps7 : 20 kbps8 : 10 kbpsDefault: 0Min.: 0Max.: 8
F2-03 ~ F2-12Retain

d2: Load Parameters

Group U, Monitor Settings
U2:FaultB Information5
U2-00Current Fault Displays the current fault. -
U2-01 1st Most Recent FaultDisplays the first most recent fault. -
U2-02 2nd Most Recent FaultDisplays the second most recent fault. -
U2-03 3rd Most Recent FaultDisplays the third most recent fault. -
U2-04 4th Most Recent FaultDisplays the fourth most recent fault. -
U2-05Frequency Command at 1st Most Recent FaultDisplays the frequency command at the first most recent fault.-
U2-06Output Frequency at 1st Most Recent FaultDisplays the output frequency at the first most recent fault.-
U2-07Output Current at 1st Most Recent FaultDisplays the output current at the first most recent fault.0.01A
U2-08<peed at 1st Most Recent FaultDisplays the speed at the first most recent fault. -
U2-09Output Voltage command at 1st Most Recent FaultDisplays the output voltage command at the first most recent fault.0.1V
U2-10Main Circuit DC Voltage at 1st Most Recent FaultDisplays the main circuit DC voltage at the first most recent fault.0.1V
U2-13Input >terminal <tatus at 1st Most Recent FaultDisplays the input terminal status at the first most recent fault. (<ame status display as U1-09)-
U2-14Output>terminalDisplays the output terminal status at the first most recent fault. (-
U2-15OperationDisplays the operation status at the first most recent fault. (-
U2-17Cumulative Operating>ime at 1st Most Recent FaultDisplays the cumulative operating time at the first most recent fault1h
U2-19Frequency Command at 2nd Most Recent FaultDisplays the frequency command at the second most recent fault.-
U2-20Output Frequency at 2nd Most Recent FaultDisplays the output frequency at the second most recent fault.-
U2-21Output Current at 2nd Most Recent Fault 2nd Displays the output current at the second most recent fault.0.01A
U2-22Displays the speed at the second most recent fault. -
U2-23Output Voltage command at 2nd Most Recent FaultDisplays the output voltage command at the second most recent fault.0.1V
U2-24Main Circuit DC Voltage at 2nd Most Recent FaultDisplays the main circuit DC voltage at the second most recent fault.0.1V
U2-27Input>terminalDisplays the input terminal status at the second most recent fault. (-
U2-28Output>terminalDisplays the output terminal status at the second most recent fault. (-
U2-29OperationDisplays the operation status at the second most recent fault. (-
U2-31CumulativeOperating >ime at 2nd Most Recent FaultDisplays the cumulative operating time at the secondmost recent fault1h
U2-33Current Alarm Displays the current alarm. -
U2-34 1st Most Recent AlarmDisplays the first most recent alarm. -
U2-35 2nd Most Recent AlarmDisplays the second most recent alarm. -
U2-39 3rd Most Recent AlarmDisplays the third most recent alarm. -
U2-37 4th Most Recent AlarmDisplays the fourth most recent alarm. -

Chapter 6 | Troubleshooting

6.1 Alarm and Fault Displays

he cause of alarm or fault have been closed out, part of alarm display code will be automatically clear

Table 6.1 Alarm and Fault Displays, Causes, and Possible Solutions

Keypad DisplayFault NameCausePossible Solution
EF0Retain
EF1 to EF8External Fault (Input Terminal S1 to S8)1. An external controller tripped an alarm2. Incorrect wiring3. Multi-function input wiring is not correct1. Remove the cause of the external fault then reset the multi-function input.2. Confirm if the signal lines is properly connected to the terminals assigned for external fault detection (E1-□□= 23 to 38)3. Confirm if E1-□□=23 to 38 is set to the unused terminals.
dEvSpeed Deviation (for Closed-Loop Control Methods)The deviation between the pulse input speed feedback and speed command is greater than then level set to F1-12 for longer than the time set to F1-13.1. Over loaded2. The load is locked up3. It is being braked1. Increase the deceleration and acceleration times (C1-00 to C1-07)2. Check if F1-12 and F1-13 are set correctly.3. Check the loadbrake and make sure it is released
FbHPID Feedback HighPID feedback input is greater than the detection level set to b5-22 for longer than the detection time set tob5-231. b5-22 andb5-23 inappropriate setting2. PID feedback wiring incorrect3. Feedback sensor malfunction4. Feedback input circuitmalfunction1. Confirm b5-22 and b5-23 settings2. Correct the wiring3. Replace the sensor if it is damaged4. Replace the PCB or controller. Contact the local distributor.
FbLPID Feedback LowWhen the PID feedback detection is enabled in b5-11, a FbL will be triggered while the PID feedback falls below the level set to b5-12 for longer than the time set to b5-13.1. Inappropriate setting in b5-12 and b5-132. Incorrect PID feedback wiring3. Feedback sensor malfunction4. Incorrect feedback input circuit1. Correct b5-12 and b5-13 settings2. Correct the wiring3. Replace the sensor if it is damaged4. Contact the local distributor to replace the board or the controller.
oHHeatsink OverheatHeatsink temperature over 90 to 100°C (Overheat level is determined by rating of the controller)1. Ambient temperature is too high2. Internal cooling fan stopped operating3. Bad air flow due to insufficient room.1. Check the temperature surrounding the controllera. Improve the air flow inside the enclosure panelb. Install an air conditioner or fan to cool the environmentc. Remove any possible source of heat2. Measure the output currenta. Reduce the loadb. Lower setting in C6-00 ( Carrier Frequency Option )3. Replace the cooling fan
oH1OverheatThe temperature signal from temperature sensor via the terminal MT exceeded the overheat detection level of the controller.1. Incorrect temperature input (terminal MT) wiring2. Fault on the machinery (e.g., machinery is locked up)3. overheat1. Correct the wiring for terminal MT.2. Check the machinery status3. Check the load, acceleration / deceleration time and cycle timea. Reduce the load.b. Increase the C1-00 to C1-07 (Acc./Dec. Time) settingsc. Adjust d1-02 to d1-11 (V/F Characteristics)
ot1Overtorque Detection 1The current has exceeded the torque level set to P6-01 for longer than the time set to P6-021. Incorrect parameter settings2. Malfunction on machinery1. Reset P6-01 and P6-022. Check machinery and load status
ot2Over torque Detection 2The current has exceeded the torque level set to P6-04 for longer than the time set to P6-051. Incorrect parameter settings2. Malfunction on machinery1. Reset P6-04 and P6-052. Check machinery and load status
ovOver voltageVoltage in the DC bus exceeded the over voltage detection level1.200 V class: 410 V2.400 V class: 820 V1. Controller input power has surge voltage entering2. Machinery output short circuit3. Ground fault in the output circuit causes the DC bus capacitor to overcharge4. Electrical signal interference causes controller malfunction5. PG cable is disconnected6. Incorrect PG cable wiring7. PG encoder wiring is interference by electrical signal1. Install a DC link choke Voltage surge can result from a thyristor convertor and phase advancing capacitor using the same input power supply2. Check the power cable, relay terminals and terminal box3. Correct grounding shorts and reapply power4. Check the solutions for interference suppression»Check the control circuit lines, main circuit lines and grounding wiring.»If the MC is the source of interference, connect a suppressor to it.5. Reconnect the cable6. Correct the wiring7. Separate the wiring from the source of the electrical signal interference. It is usually the output lines from the controller
UvUndervoltage1.Voltage in the DC bus fell below the undervoltage detection level (P2-03)2.200 V class: 190 V3.400 V class: 380 V1. Input power phase loss2. Loose wiring terminals of controller input power3. Problem with the voltage from the controller input power4. The controller main circuit capacitors are weakened.5. The contactor or relay on the soft-charge bypasscircuit is damaged1. Correct the controller input power wiring2. Tighten the terminals3. Check the voltagea. Adjust the voltage according to the controller input power specificationsb. Check the main circuit magnetic contactor if there is no problem with the power supply 4&5. Turn on and turn off thepower to see if any problem occursReplace either the entire controller or the control board if the problem continues to occur. Contact the local distributor for more information.
Ut1Undertorque Detection 1The current has dropped below the torque detection level set to P6-01 for longer than the time set to P6-021. Incorrect parameter settings2.Malfunction on machinery side1. Reset P6-01 and P6-022. Ensure there is no problem on the machinery side.
Ut2Undertorque Detection 2The current has dropped below the torque detection level set to P6-04 for longer than the time set to P6-051. Incorrect parameter settings2.Malfunction on machinery side1. Reset P6-04 and P6-052. Ensure there is no problem on the machinery side.
ULMechanical Weakening Detection for UndertorqueUndertorque in the conditions set to P6-06Undertorque in the conditions set to P6-06Check the condition of mechanical weakening
oLMechanical Weakening Detection for OvertorqueOvertorque in the conditions set to P6-06Overtorque in the conditions set to P6-06Check the condition of mechanical weakening
oSOverspeedThe speed feedback exceeded the level setto F1-091. Overshoot occurs2. Incorrect PG pulse train settings1. Increase setting of C4-00 (ASR Proportional Gain 1) and C4-01(ASR Integral Time 1)2. Reset F1-09 (OverspeedDetection Level) and F1-10 (Overspeed Detection Delay Time)
BbBaseblockController output interrupted by an external baseblock signalAn external baseblock signal was input via one of the multi-function input terminals (S1 to S8)Check baseblock signal input timing and external sequence
oH2Controller Overheat WarningController Overheat Warning input via a multi-function input terminal (S1to S8) when E1-□□=40An overheat warning in the controller was triggered by an external controller1. Search the controller which caused the overheat warning.Remove the cause of the problem.2. Reset Controller Overheat Warning input at the assigned multi-function input terminal (S1to S8)
HCACurrent AlarmController current exceeded the level of over current warning (150% of the rated current)1. The load is too heavy2. Deceleration and acceleration times are too short3.The controller is attempting to run a greater than the maximum allowable capacity, or a special-purpose is being used4.The current level went up because of Speed Search while attempting to perform a fault restart or after a momentary power loss1. Reduce the load or use a controller of higher rating2. Calculate the torque required during acceleration and the inertia»Take the following steps if the torque level is not right for the load· Increase the settings for acceleration and deceleration time (C1-00 to C1-07)· Use a controller of higher rating3. Check the capacity· Make sure the capacity is right for the controller rating.4. During a momentary power loss or an attempt to reset a fault, the alarm is displayed. However, there is no need to take any action because the fault display will disappear shortly
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : CyberPower

Model : CPSPI3700EVF380

Category : Solar panel