| Product Type | Dehumidifier |
| Brand | Wood's |
| Model | WP-200AP |
| Max Working Area | 180 m² |
| Recommended Working Area | 10-140 m² |
| Air Flow | 220 m³/h |
| Capacity (20°C, 60% RH) | 14.4 liters/day |
| Power Consumption (20°C, 70% RH) | 1.2 kW |
| Power Consumption (35°C, 80% RH) | 1.5 kW |
| Fan Speeds | 1 |
| Dimensions (L x W x H) | 440 x 300 x 678 mm |
| Weight | 30 kg |
| Sound Level | 51 dB |
| IP Rating | IPX2 |
| Temperature Range | -20°C to +35°C |
| Power Supply | Three-phase AC, voltage and frequency per nameplate |
| Installation | Indoor and outdoor |
| Control Modes | Manual (MAN) and Automatic (AUT) |
| Humidity Setting Range | 1% - 99% RH |
| Air Filter | Check and clean regularly; ensure intact |
| Safety Features | Earthed power source, overload protection, three-phase protection |
Frequently Asked Questions - WP-200AP Wood's
User questions about WP-200AP Wood's
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Humidifier in PDF format for free! Find your manual WP-200AP - Wood's and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. WP-200AP by Wood's.
USER MANUAL WP-200AP Wood's
Users manual Wood's WP-200AP
Please read this manual carefully before installing and save the manual for future reference and product warranty.
GB
Operating instructions
S
Bruksanvisning
THANK YOU!
Thank you for choosing a Wood's dehumidifier. In this manual you'll find everything you need to know about your Wood's dehumidifier.
Please keep this manual in a safe place for future reference.

Wet Air Outlet Reactivation Air inlet
INDOOR INSTALLING
The Reactivation Air Outlet and Wet Air Inlet must be installed outside. The ideal distance between the pipes is 2m. No pipe is needed for the Process Air Inlet.
INDUSTRY INSTALLING
The Dry Air Outlet and Process Air Inlet should be set in the moist area inside. The remaining pipes should be set inside.
OUTDOOR INSTALLING
The pipes for Dry Air Outlet and Process Air Inlet should be set in the moist area indoors. No pipes are needed for the remaining holes.

Reactivation Air Inlet
TECHNICAL DATA
| Max. working area | 180 m2 |
| Recommended working area | 10-140 m2 |
| Air flow | 220 m3/h |
| Capacity at 20°C & 60% RH | 14,4 litres |
| Power at 20°C & 70% RH | 1,2 kW |
| Power at 35°C & 80% RH | 1,5 kW |
| Fan speeds | 1 |
| Dims LxWxH | 440x300x678 mm |
| Weight | 30 kg |
| Sound level | 51 dB |
| IP rating | IPX2 |
WOOD'S - THE WORLD'S LEADING DEHUMIDIFIERS
Wood's dehumidifiers have been known as market leaders for many years. Wood's dehumidifiers are suitable for use in the most demanding climates, and have high dehumidifying capacity even at lower temperatures and humidity levels. They are used with good results in premises that become damp such as cellars, garages or summer-houses. They are also excellent for drying washing, attics, pool rooms and laundry, being efficient and low on energy consumption. Wood's dehumidifiers will dry your clothes efficiently without wearing them out.
The amount of humidity that the dehumidifier removes depends on temperature, humidity level and placement. External weather conditions may also affect the performance of the dehumidifier. In cold weather the actual humidity, (in grams per cubic meter air) decreases and thus the extraction of humidity from the air by the dehumidifier is reduced. The dehumidifier is suitable for use in the temperature range -20°C to +35°C. Wood's dehumidifiers are safe in operation and intended for continuous use over many years.
EXCESSIVE AIR HUMIDITY - A DANGER
Condensation occurs when water vapour in the air comes into contact with a cold roof, window or wall. When water vapour is cooled down, condensation occurs, and water-drops are formed. In high air humidity, the air may get musty and mould is formed, causing damage to a house and its furnishings. This environment may even cause illness for the residents, since mites and other creatures thrive in a damp environment. A dehumidifier with high performance creates a good, healthy humidity level, and for greatest efficiency the doors and windows of rooms that are being dehumidified should be kept closed. Wood's dehumidifiers remove odours, dries wood and remove moisture from sportswear outdoors equipment. A dehumidifier may be used in cellars, washrooms, garages, crawl spaces, caravans, summer-houses and on boats.
1. INSTALLATION
The WP-200AP dehumidifiers are suitable for indoor & outdoor installation. To ensure the quality and reliability of the dehumidifier, each machine has passed inspection tests before delivery. If the machine will be stored for a long time before being used, please comply with notes as below:
- Do not abandon or destroy the original package.
- Avoid any physical damage.
- Prevent dust, frost and rain.
IMPORTANT :
Wood's dehumidifiers must be connected to an earthed power source.
1.1 Inspection
First, check if any damage has occurred during transportation. Open the package, and connect the power cord to test the product. If any damage is found, please contact the manufacturer.
Secondly, connect the pipes to the machine, and check if the layout of the pipes is appropriate. If environmental and installation conditions are not satisfactory, please contact the manufacturer for help.
1.2 Safe Operation
Warning! Use a carrying & lifting device to carry the unit to prevent any injury or damage as the dehumidifier weighs more than 30 kg. Avoid turning the unit upside down.
Warning! Please read the nameplate data before electrical works. Local professionals must do all electrical connecting works. Ensure that the machine is connected to the specified voltage and frequency of power supply.
Be careful! To prevent damage, never connect the dehumidifier directly to an air conditioning system.
1.3 Location requirements
The dehumidifier is suitable for indoor & outdoor use. For the convenience of maintenance and inspection, some space around the machine should be retained. In order to prevent condensation inside the machine, it should not be placed in conditions in which the air temperature is below the dew point. In addition, if the machine is installed outdoors, some protective measures should be done to prevent rain, snow and dust, etc.
1.4 Installation base
The dehumidifier must be installed on flat ground or a platform of which the capacity is enough to bear the total weight of the dehumidifier. After installation works, re-check that the dehumidifier is placed flat and continue the installation. If the dehumidifier requires a fixed installation, the mounting holes should be done in the pre-fabricated steel feet.
1.5 Pipe Connection
The dimension of pipes for processing air and reactivation air should be in line with ISO7807 recommended values. Pipes should be connected with the connection part on the flange; meanwhile, the screw bolt is limited to within 20mm. While connecting the input and out pipes, please follow the notes below:
- In order to reduce loss of static pressure, shorten the length of the pipe if possible.
- To ensure the performance of the machine, all rigid (galvanized) pipe fittings are required to have air-tightness.
- The pipes should have good thermal insulation capacity to prevent moisture condensation on the inner pipe wall, which could otherwise lead to corrosion.
- To reduce noise and vibration transmitted along the pipes, use high-quality, soft, and strong airtight adapters at the joints.
- If necessary, install air valves on the process air and reactivation air pipes.
If the reactivation air is taken from outdoors, the terminal of the reactivation air pipe should be positioned high enough above the ground to prevent intake of dust and debris. It must also be located far from pollution sources such as exhaust emissions, steam, and gases. To prevent moist air from being drawn into the machine, maintain a distance of at least one meter between the wet air pipe terminal and the reactivation air pipe terminal. Additionally, the pipe should be designed to prevent snow and rain from entering.
The wet air pipe contains high moisture. Therefore, ensure it is installed with a downward slope so that no water flows back into the dehumidifier.
Caution: Since the wet air pipe is very moist, condensation water can easily form on the inner wall. If there is a risk of freezing, take thermal insulation measures when temperatures are low. Provide adequate support under the pipes.
1.6 Electrical connection
Caution: All electrical connections must comply with local electrical installation standards and be performed by qualified professionals. The machine requires a three-phase AC power supply. The voltage and frequency are specified on the nameplate.
- It is forbidden to connect the power supply beyond the specified voltage and frequency.
- Before supplying three-phase AC power, verify that the actual voltage and frequency fluctuations do not exceed ±10%.
- The unit must be grounded. Install a power isolation switch to ensure the machine is completely shut off during maintenance. The main switch should be directly connected to the main power components.
1.7 Inspection before starting the dehumidifier
Warning: All electrical work must be performed by professionals who are aware of potential hazards such as high pressure and high temperature. Before initial start-up, perform inspections with the power turned off. The inspections include:
- Check that the switch is in the "OFF" position.
- Check that the air inlet filter is intact and that all equipment parts are clean.
- Check and ensure that all of the air hoses are undamaged, and that the air hose is smooth.
- Switch the unit on, and place it into "Manual (MAN)" position, an indication light is illuminated.
- Check the blower, ensure that the rotation direction is correct. The correct direction of rotation is
- indicated by the arrow on the fan casing. If the fan's rotation is incorrect, the dehumidifier is provided a reversed phase sequence. • Check and ensure that the desiccant wheel rotation direction is consistent with the direction of the
- arrow, and confirm that there is no skidding between the wheel and belt.
- Switch to "off" (OFF) position, the machine should stop running.

NOTE:
Always disconnect the cord before cleaning or maintenance.

NOTE:
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid hazard.
CONTROLS
2. CONTROL PANEL OVERVIEW
The standard control orders of WP-200AP dehumidifiers have been set well before delivery if no special requirements from customers. The WP-200AP is easy to operate. Before operation, please read the technical manuals and other related equipment information.
Warning! Please read this Manual carefully before using the machine, the manufacturer and seller won't bear the loss caused by wrong operation
Warning! If the electronic control system fails, please turn off the power immediately, and carry out the general inspection and maintenance. Never arbitrarily modify the circuit and related settings before the cause is found out. Other the manufacturer or seller won't bear the loss.
2.1 Control panel

Timer: showing the cumulative working time
Ammeter: Showing the current of the reactivation heater
Humidometer: The humidometer has three buttons; "mode", "down" and "up"
Power switch:
O: Off mode; —- 1 = Manual (MAN) working model, 2 = Automatic (AUT) working mode
MAN: The unit will run continuously until it is turned off.
AUT (Automatic running): The unit will run until set humidity level is reached and then shut off. When the ambient humidity rises above set humidity level, the machine will automatically restart.
Be careful! When switched on (MAN or AUT position), the blowers, wheel and heater will run simultaneously, the ammeter will show the current of reactivation heater while it becomes stable, in addition, the timer will begin to accumulate the total cumulative working time.
When set in MAN position, the dehumidifiers fan wheel and heater will run continuously. No controls can be set by the user. When set in AUT position, the desired humidity level must be set through the control panel. Switch OFF, all parts will stop working.
2.2 Set steps:
While the machine is on "MAN working mode", the humidometer light is off, user can not set it either, and the machine will keep working continuously in the area until shut off.
While the machine is in "Auto working mode", the humidometer light is on, it will show the current RH level, and is set as below:
A:Press the "mode" button one time to enter the setting mode, press "down" or "up" until the humidometer shows the desired RH level. The setting range is 1%-99%;
B:Press the "mode" button a second time, the humidometer will show the current RH level again;