IFM PY2006 - Sensor

PY2006 - Sensor IFM - Free user manual and instructions

Find the device manual for free PY2006 IFM in PDF.

📄 19 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice IFM PY2006 - page 4
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Electronic Pressure Sensor
Brand IFM
Model PY2006
Measuring Range -125...2500 mbar (-1.82...36.26 psi)
Maximum Permissible Pressure 20000 mbar (290 psi)
Bursting Pressure 50 bar (725 psi)
Output 1 IO-Link (process data)
Output 2 Analogue 4...20 mA
Operating Modes 2-wire, 3-wire
Power Supply SELV/PELV, typically 18...30 V DC
Process Connection G1 Aseptoflex Vario
Pressure Type Relative pressure
Vacuum Resistance Yes
Scalable Measuring Range Yes (up to 20% of final value)
Damping Settings Analogue output (dAA) and process data (dAP)
Zero-Point Calibration Via teach button (E30425)
IO-Link Communication Yes (IODD available at ifm.com)
Protection Class IP rating not specified, but hygienic design
Hygienic Compliance 3A, EHEDG (with suitable adapters)
Ventilation Diaphragm GORE diaphragm with protective cover
Replaceable Filter Cover Yes (several versions available)
Torque for Process Connection 35 Nm (G1 Aseptoflex Vario)
Operating Temperature Not specified (refer to data sheet)
Maintenance Clean ventilation diaphragm with lime-deficient water

Frequently Asked Questions - PY2006 IFM

How do I install the PY2006 pressure sensor?
Before installation, ensure no pressure is applied and no medium is in the pipe. Use a suitable process connection (e.g., G1 Aseptoflex Vario) and tighten to 35 Nm. Do not exert axial leverage on the rotatable filter cover. Align the cover for proper drainage.
What are the electrical connection options?
The sensor supports 2-wire and 3-wire operation. In 2-wire mode, OUT2 provides the analogue signal (4...20 mA). In 3-wire mode, OUT1 is IO-Link and OUT2 is analogue. Connect according to the wiring diagram using brown (BN), white (WH), blue (BU), and black (BK) wires per DIN EN 60947-5-2. Power supply must be SELV/PELV.
How can I configure the sensor parameters?
Parameters can be set via IO-Link using a PC with IO-Link software (e.g., LINERECORDER DEVICE) and an ifm interface. Alternatively, use a memory plug (ifm storage module) to transfer settings. A teach button (E30425) allows zero-point calibration.
What is IO-Link and how does it benefit me?
IO-Link is a communication interface that provides direct access to process data, diagnostic information, and parameter settings. It enables remote monitoring, configuration, and fault detection. The device supports IO-Link with fully bidirectional communication.
Can I scale the measuring range?
Yes, the measuring range is scalable to up to 20% of the final value. Set [ASP2] for the start point (4 mA) and [AEP2] for the end point (20 mA). The minimum distance between ASP and AEP is 20% of the measuring span.
How do I set damping for the output?
For the analogue output, set parameter [dAA] (rise time 10...90%) between 0.000 and 4.000 seconds. For the switching signal (IO-Link process data), set [dAP] (t value 63%) in the same range. Damping filters out short pressure peaks.
What does the fault indication mean?
If a fault is detected, the analogue output goes to 21.5 mA (Namur indication). This indicates a malfunction. Read parameters via IO-Link or contact the manufacturer to identify the issue.
How do I clean and maintain the sensor?
Clean the ventilation diaphragm immediately with plenty of lime-deficient splash water if soiled. Avoid contact with liquids when the sensor is cooling. Replace the filter cover if damaged or as needed (versions: E30142, E30148, E30139). Follow the orientation guidelines for the GORE diaphragm.
What spare parts are available?
Spare parts include the filter cover with GORE diaphragm (E30142), closed filter cover (E30148), tube fitting version (E30139), and accessory set (E30467). Also available: sealing rings (EPDM, FKM, PEEK), memory plug, and teach button (E30425).
Is the sensor suitable for hygienic applications?
Yes, when used with certified adapters (3A or EHEDG), it meets hygienic standards. Ensure self-draining installation and use leakage ports. Not suitable for 3A standard E1.2/63-03 criteria. Observe temperature and material resistance limits from the data sheet.

User questions about PY2006 IFM

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Sensor in PDF format for free! Find your manual PY2006 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. PY2006 by IFM.

USER MANUAL PY2006 IFM

Operating instructions Electronic pressure sensor

PY200x

UK

80283564 / 00 09 / 2019

IFM PY2006 - 1

natural_image Line drawing of a cylindrical mechanical component with a flanged top and base (no text or symbols)

Contents

1 Preliminary note....3

1.1 Symbols used .... 3

2 Safety instructions ....3

3 Functions and features .... 4

3.1 Applications ....4

4 Function....5

4.1 IO-Link 5

4.2 Set-up via IO-Link....5

4.3 Scalable measuring range....6

4.4 Process data via IO-Link 6

4.5 Defined state in case of a fault 6

4.6 Operating modes....6

4.6.1 2-wire operation....6

4.6.2 3-wire operation....6

4.7 Analogue function 7

5 Installation....7

5.1 G1A Aseptoflex Vario adaptation (PM17xx)......8

5.2 Use in hygienic areas to 3A....10

5.3 Use in hygienic areas to EHEDG 10

5.4 Ventilation diaphragm with protective cover 11

5.4.1 Function ventilation diaphragm.... 11

5.4.2 Orientation of the filter cover 12

5.5 Filter cover....12

6 Electrical connection....14

7 Parameter setting 15

7.1 Parameter setting via PC....15

7.2 Parameter setting via the memory plug....16

7.3 Teach offset with the teach button 16

7.3.1 Scale analogue value 17

7.3.2 Select the standard unit of measurement (option)....17

7.4 User settings (optional)....17

7.4.1 Set damping for the analogue output 17

7.4.2 Set damping for the switching signal....17

7.4.3 Zero-point calibration....18

7.5 List of the parameters....18
8 Operation....18

1 Preliminary note

1.1 Symbols used

▶ Instruction

Reaction, result

[...] Designation of keys, buttons or indications

→ Cross-reference

IFM PY2006 - Symbols used - 1

Important note

Non-compliance may result in malfunction or interference

IFM PY2006 - Symbols used - 2

Information

Supplementary note

2 Safety instructions

- The device described is a subcomponent for integration into a system.

  • The manufacturer is responsible for the safety of the system.
  • The system manufacturer undertakes to perform a risk assessment and to create a documentation in accordance with legal and normative requirements to be provided to the operator and user of the system. This documentation must contain all necessary information and safety instructions for the operator, the user and, if applicable, for any service personnel authorised by the manufacturer of the system.

  • Read this document before setting up the product and keep it during the entire service life.

  • The product must be suitable for the corresponding applications and environmental conditions without any restrictions.
  • Only use the product for its intended purpose (→ Functions and features).

IFM PY2006 - Safety instructions - 1

  • Only use the product for permissible media (→ Technical data).
  • If the operating instructions or the technical data are not adhered to, personal injury and/or damage to property may occur.
  • The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator.
  • Installation, electrical connection, set-up, operation and maintenance of the product must be carried out by qualified personnel authorised by the machine operator.
  • Protect units and cables against damage.

3 Functions and features

The unit measures and monitors the system pressure of machines and installations.

2 outputs are available:

- OUT1: Measured pressure value via IO-Link.

More information 4.1 and 7.

- OUT2: Analogue signal proportional to pressure 4...20 mA

3.1 Applications

Type of pressure: relative pressure

Order numberMeasuring rangePressure rating (max. permissible pressure) *)Bursting pressure
Pressure sensors with G1 Aseptoflex Vario
mbar psimbar psi bar psi
PY2007-50...1000-0.73...14.51000014530435
PY2006-125...2500-1.82...36.262000029050725
*) With static overload pressure.
MPa = (measured value in bar) ÷ 10 kPa = (measured value in bar) x 100

IFM PY2006 - Applications - 1

Avoid static and dynamic overpressure exceeding the indicated pressure rating by taking appropriate measures.

The indicated bursting pressure must not be exceeded.

Even if the bursting pressure is exceeded only for a short time, the unit may be destroyed.

ATTENTION: Risk of injury!

IFM PY2006 - Applications - 2

Not suitable for systems that have to meet the criteria of E1.2 / 63-03 of the 3A standard 63-03.

IFM PY2006 - Applications - 3

The units are vacuum resistant.

IFM PY2006 - Applications - 4

4 Function

The unit converts the system pressure into an analogue output signal (4...20 mA). Moreover, it provides the process data via IO-Link.

The device has an IO-Link communication interface which requires an IO-Link capable module (IO-Link master).

The IO-Link interface enables direct access to the process and diagnostic data and provides the possibility to set the parameters of the unit during operation.

In addition, communication is possible via a point-to-point connection with a USB adapter cable.

The IODDs necessary for the configuration of the unit, detailed information about process data structure, diagnostic information, parameter addresses and the necessary information about the required IO-Link hardware and software can be found at www.ifm.com.

The device parameters can be set via IO-Link:

  • The device parameters are set via the IO-Link interface ( 4.1 and 7).
  • All settings can also be carried out before installation of the unit.

4.3 Scalable measuring range

The measuring range can be scaled to up to 20% of the final value of the measuring range:

  • Setting the parameter [ASP2] defines at which measured value the output signal is 4 mA.
  • Setting the parameter [AEP2] defines at which measured value the output signal is 20mA.

All process data is available via IO-Link:

  • The unit is designed for fully bidirectional communication.
    • The following options are available:
  • Remote display: read and display the current system pressure.
  • Remote parameter setting: read and change the current parameters via IO-Link parameter setting ( 4.1)

4.5 Defined state in case of a fault

- If a fault is detected, the analogue output passes into a defined state (= 21.5mA) .

IFM PY2006 - Defined state in case of a fault - 1

In case of a fault indication (= 21.5 mA)

▶ Read parameters via IO-Link or contact the manufacturer

4.6 Operating modes

The operating mode is defined by the wiring ( 6 electrical connection) and automatically recognised by the unit.

4.6.1 2-wire operation

OUT2 (pin 2) Analogue signal proportional to pressure 4...20 mA

4.6.2 3-wire operation

OUT1 (pin 4) Communication via IO-Link OUT2 (pin 2) Analogue signal proportional to pressure 4...20 mA

4.7 Analogue function

OUT2 is an analogue output:

Minimum distance between [ASP2] and [AEP2] = 20 % of the measuring span.

Factory setting Measuring range scaled
IFM PY2006 - Analogue function - 1

line | MEWMAW P | I [mA] | | -------- | ------ | | Low | 4 | | High | 20 |

IFM PY2006 - Analogue function - 2

line | MEWMAW/REP2ASF | I [mA] | | -------------- | ------ | | Start | 4 | | Peak | 20 |

P = System pressure

MAW = Initial value of the measuring range

ASP2 = Analogue start point [ASP2]

MEW = Final value of the measuring range

AEP2 = Analogue end point [AEP2]

In the set measuring range, the output signal range is between 4 and 20 mA.

It is also indicated:

  • System pressure above [AEP2]: 20...20.5 mA
  • System pressure below [ASP2]: 4...3.8 mA
    • Fault indication according to Namur: 21.5 mA

5 Installation

IFM PY2006 - Installation - 1

▶ Before installing and removing the unit make sure that no pressure is applied to the system and there is no medium in the pipe.

▶ Note dangers related to external system / medium temperatures.
▶ In case of a recessed sensor installation, please use an open ring spanner or a hexagon socket with the corresponding inside contour.

IFM PY2006 - Installation - 2

IFM PY2006 - Installation - 3

▶ During sensor installation, do not exert any axial leverage with the tool (1) on the rotatable filter cover (2) ( fig. 1).

IFM PY2006 - Installation - 4

In case of installation by means of a hexagon socket (3), make sure that the tool's spanner flat has an inner height of at least 30 mm ( fig. 2). Align the rotatable filter cover so that it is flush with one of the spanner flats.

Technical diagram of a mechanical assembly with labeled parts 1 and 2, showing a pipe connection and internal components.

③ ≥30mm 2

▶ Insert the unit in a process connection.
▶ Tighten firmly. Recommended tightening torque:

Process connection Tightening torque in Nm
G1A Aseptoflex Vario 35
Depends on the sealing type, the pressure load and the lubrication!

IFM PY2006 - Installation - 7

A zero-point calibration of the measured value is possible via the teach function ( 7.3 Teach offset with the teach button)

5.1 G1A Aseptoflex Vario adaptation (PM17xx)

▶ Insert the unit with process adapter into the process connection and tighten using a spanner.

IFM PY2006 - G1A Aseptoflex Vario adaptation (PM17xx) - 1

Information about available adapters at www.ifm.com.

▶ Observe the instructions of the adapter.
▶ Use a lubricating paste which is suitable and approved for the application.

The unit can be fixed to different process connections.

Options are as follows:

1Installation using an adapter with sealing ring (hygiene-compliant)
Order no. E332xx / E333xx.To meet the hygiene regulations use a process adapter with leakage port.The adapters are supplied with EPDM O-ring (order no. E30054).More sealing rings are available as accessories:FKM O-ring (order no. E30123)PEEK sealing ring (order no. E30124). The PEEK sealing ring is long-term stable and maintenance-free.When you replace the PEEK sealing ring or change from a PEEK sealing ring to an O-ring, the process adapter also needs to be replaced with a new equivalent adapter.
2Installation using a welding adapter with sealing ring (hygiene-compliant)
To meet the hygiene regulations use a process adapter with leakage port.Make sure that the process adapter does not warp during welding. Use welding mandrel E30452.The sealing edge must not be damaged by subsequent surface treatment. (→ instructions in operating instructions of the adapter).The adapter is supplied with EPDM O-ring (order no. E30054). Another sealing ring is available as accessory:FKM O-ring (order no. E30123).
3Installation using a process adapter with metal-to-metal seal
Order no. E337xx / E338xxA long-term stable and maintenance-free fitting without bug traps in the metal-to-metal seal is only valid for once-only mounting.If the sealing has to be installed several times, use a new adapter.
4Installation to G 1 flange / G 1 bush
The sensor is sealed with the sealing ring at the back of the process connection.► The sealing area at the flange / bush must be flush with the tapped hole and have a surface characteristic of min. Rz = 6.3.

5.2 Use in hygienic areas to 3A

① ② ③ ④ ⑤

The following applies to units with 3A certification:

▶ Only use adapters with 3A certification for the process connection.
▶ Do not install the unit at the lowest point of the pipe or tank ( position 5) in order that the medium can run off the area of the measuring element.

5.3 Use in hygienic areas to EHEDG

IFM PY2006 - Use in hygienic areas to EHEDG - 1

The sensor is suited for CIP (cleaning in place) when installed correctly.

▶ Observe the application limits (temperature and material resistance) according to the data sheet.

▶ Make sure that the sensor is integrated into the system according to EHEDG:
▶ Use self-draining installation.
▶ Only use process adapters permitted according to EHEDG with special seals required by the EHEDG position paper.

IFM PY2006 - Use in hygienic areas to EHEDG - 2

The gasket of the system interface must not be in contact with the sealing point of the sensor.

▶ In case of structures in a tank, the installation must be flush mount. If not possible then direct water jet cleaning and cleaning of dead spaces must be possible.
▶ Leakage ports must be clearly visible and must be installed facing downwards for vertical pipes.

L D ①

▶ To avoid dead space adhere to the dimensions:

$$ L < (D). $$

IFM PY2006 - Use in hygienic areas to EHEDG - 4

1: Leakage port

5.4 Ventilation diaphragm with protective cover

5.4.1 Function ventilation diaphragm

The ventilation diaphragm enables the relative pressure measurement since barometric and temperature-dependent pressure fluctuations between the measuring cell and the environment are compensated for.

The ventilation diaphragm is protected against damage by a screwed cap with circumferential ports.

IFM PY2006 - Function ventilation diaphragm - 1

For a correct functioning of the diaphragm please take the following into account:

▶ Remove soiling and cleaning agents immediately using plenty of lime-deficient splash water.

IFM PY2006 - Function ventilation diaphragm - 2

If the sensor is in a cooling stage:

▶ Avoid contact of the diaphragm with liquids to avoids negative pressure in the measuring system resulting in a slightly falsified measured value and additional strain on the diaphragm.

5.4.2 Orientation of the filter cover

The filter cover is freely rotatable around the sensor's axis and thus adaptable to the environmental conditions.

When the sensor is mounted in a vertical position, the condensate escapes through the ports in the protective cap due to gravity.

When the sensor is mounted in a horizontal position or similar, the filter protection cap must be rotated towards one of the two lateral faces to bring the GORE diaphragm into a vertical position. This guarantees the optimum drainage for liquids.

IFM PY2006 - Orientation of the filter cover - 1

To ensure an optimum function of the pressure compensation element, align the filter cover as shown in fig. 1.

IFM PY2006 - Orientation of the filter cover - 2

flowchart
graph TD
    A["Step 1"] --> B["Step 2"]
    B --> C["Step 3"]
    C --> D["Step 4"]
    D --> E["End"]

▶ Ideal orientation (1):
Filter cover in horizontal position.
The ventilation diaphragm (2)
in the filter cover is in a vertical position.
▶ Maximum inclination: 30^ (3)

fig. 1: orientation

5.5 Filter cover

Replace filter cover:

1Exchange the filter cover incl. GORE diaphragm (E30142).
2Replace the filter cover with a closed version (E30148) (*)

Improve the protection of the filter cover:

3Replace the filter cover with a version with a tube fitting and a vent tube that ends in a protected and dry area (E30139).
4Set of accessories (E30467) with integrated replacement diaphragm (GORE), for high degree of soiling and / or high climate pollution.Function: (→ installation instructions E30467)

IFM PY2006 - Filter cover - 1

▶ Avoid soiling and moisture during the exchange
▶ Clean the thread carefully and without residues
▶ Do not damage the adhesive area of the sensor
▶ Observe the orientation of the filter cover
(→ installation instructions E30139 / 30467)

IFM PY2006 - Filter cover - 2

flowchart
graph TD
    A["①"] --> B["②"]
    B --> C["③"]
    C --> D["④"]
    D --> E["④"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333
    style E fill:#cff,stroke:#333

IFM PY2006 - Filter cover - 3

(*) When using the closed cover cap, there is no pressure compensation of the measuring cell any more. This results in measurement deviations caused by:

• fluctuations of the atmospheric pressure
- pressure fluctuations inside the unit in case of temperature changes ( 10 K ≤ 30 mbar ).

6 Electrical connection

IFM PY2006 - Electrical connection - 1

The unit must be connected by a qualified electrician.

The national and international regulations for the installation of electrical equipment must be adhered to.

Voltage supply according to EN 50178, SELV, PELV.

▶ Disconnect power.
▶ Connect the unit as follows:

Core coloursIFM PY2006 - Electrical connection - 22-wire operation (2w) IFM PY2006 - Electrical connection - 3
1 BN brown
2 WH white
3 BU blue
4 BK black
3-wire operation (3w) IFM PY2006 - Electrical connection - 4
OUT1: communication via IO-Link OUT2: analogue output Colours to DIN EN 60947-5-2
Wiring example
(2w) 1 x analogue (3w) 1 x analogue
IFM PY2006 - Electrical connection - 5IFM PY2006 - Electrical connection - 6
(3w) 1 x analogue / 1 x IO-Link (3w) 1 xIO-Link
IFM PY2006 - Electrical connection - 7IFM PY2006 - Electrical connection - 8

IFM PY2006 - Electrical connection - 9

7 Parameter setting

IFM PY2006 - Parameter setting - 1

The unit can be configured via the IO-Link function.

▶ Prepare IO-Link hardware and software for parameter setting.
▶ Connect the unit with e.g. an IO-Link interface ( 7.1) or a programmed memory plug ( 7.2).
▶ Set the parameters.
▶ Put the unit into operation.

The parameters can be set before installation or during operation.

IFM PY2006 - Parameter setting - 2

Changing parameters during operation can influence the function of the plant.

▶ Ensure that there will be no malfunctions in your plant.

7.1 Parameter setting via PC

For parameter setting, an IO-Link capable software is necessary (e.g. LINERECORDER DEVICE).

IO-Link interfaces from ifm are available for the connection of the unit via the USB interface of a computer → www.ifm.com.

▶ Prepare computer, software and interface.
▶ Connect the unit with the IO-Link interface.
▶ Follow the menu of the IO-Link software.
▶ Set the parameters.
▶ Put the unit into operation.

Adjustable parameters( 7.5).

IFM PY2006 - Parameter setting via PC - 1

7.2 Parameter setting via the memory plug

A parameter set can be written to the unit / can be recorded by the unit via a memory plug (ifm storage module) → www.ifm.com.

IFM PY2006 - Parameter setting via the memory plug - 1

In order to allow for data to be written from the memory plug to the sensor, the sensor must have the factory setting.

IFM PY2006 - Parameter setting via the memory plug - 2

If the sensor has been configured, the memory plug records the parameter set which can then be transferred to other sensors of the same type.

▶ Load a suitable parameter set (e.g. from a PC or from a sensor of the same type) to the memory plug.
▶ Connect the memory plug between sensor and socket.

Sensor with factory setting: When voltage is supplied, the parameter set is transferred from the memory plug to the sensor.
Sensor with changed settings: When voltage is supplied, the memory plug records the sensor's parameter set.
▶ Remove the memory plug.
▶ Put the unit into operation.

Adjustable parameters ( 7.5).

You can find more information about the memory plug in the corresponding technical documentation → www.ifm.com.

7.3 Teach offset with the teach button

An external teach button (E30425) allows for a zero-point calibration (calibration offset). The current measured value is taken as internal zero point if it lies within a range of +/- 3% of the final value of the measuring range.

IFM PY2006 - Teach offset with the teach button - 1

For connection information see the E30425 data sheet If a teach button is connected, no IO-Link communication is possible

▶ Integrate the teach button between the installed sensor and the supply cable.
▶ Maintain the plant pressure constantly at zero (configurable range = +/- 3% of the measuring span).
▶ Press the button for > 2 ... < 10 s.

When voltage is supplied, the LED in the button flashes at 2 Hz and configures the zero point (calibration offset).
In case of a fault, the LED flashes at 8 Hz.

7.3.1 Scale analogue value

▶ Select [ASP2] and set the value at which 4 mA is provided.▶ Select [AEP2] and set the value at which 20 mA is provided. Minimum distance between ASP2 and AEP2 = 20 % of the measuring span (scaling factor 5).[ASP2][AEP2]

7.3.2 Select the standard unit of measurement (option)

▶ Select [uni.P] and set the unit of measurement:[bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [mWS] / [inH2O]The selectable units of measurement depend on the respective unit.[uni]

7.4 User settings (optional)

7.4.1 Set damping for the analogue output

▶ Select [dAA] and set the damping constant (rise time 10...90 %) in seconds. Setting range: 0.000...4.000 s.[IMAGE] Damping [dAA] only influences the analogue output / analogue signal path.[dAA]

7.4.2 Set damping for the switching signal

▶ Select [dAP] and set the damping constant in seconds (t value 63 %). Setting range: 0.000...4.000 s.[dAP]
Damping [dAP] influences the process data flow (IO-Link communication).

IFM PY2006 - Set damping for the switching signal - 1

7.4.3 Zero-point calibration

▶ Select[cof]Compared to the real measured value, the internal measured value (operating value of the sensor) is shifted.• Teach range: - 3...+ 3 % of the measuring span.[cof]

IFM PY2006 - Zero-point calibration - 1

Setting to zero is made with the command "Teach COF".

[coF] is reset with the command "Reset COF".

7.5 List of the parameters

Parameter Function
ASP2Analogue start pointMeasured value at which 4 mA is provided.
AEP2Analogue end pointMeasured value at which 20 mA is provided.Minimum distance between ASP and AEP = 20 % of the measuring span.
Lo Minimum value memory for system pressure.
Hi Maximum value memory for system pressure.
tcoFZero-point calibration (calibration offset)Compared to the real measured value, the internal measured value (operating value of the sensor) is shifted.• Teach range: - 3...+ 3 % of the measuring span.
dAADamping for the analogue outputPressure peaks of short duration or high frequency can be filtered out using this function.
dAP Damping of the process value (only applies to IO-Link evaluation)
uni Standard unit of measurement for system pressure.

8 Operation

After power on, the unit is in the Run mode (= normal operating mode). It carries out its measurement and evaluation functions and provides output signals according to the set parameters.

Further technical data

IFM PY2006 - Further technical data - 1

Further technical data and scale drawing at www.ifm.com.

UK

More information at www.ifm.com

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : IFM

Model : PY2006

Category : Sensor