Growatt MAX 100-150KTL3-X MV - Unknown

MAX 100-150KTL3-X MV - Unknown Growatt - Free user manual and instructions

Find the device manual for free MAX 100-150KTL3-X MV Growatt in PDF.

📄 37 pages English EN Download 💬 AI Question
Notice Growatt MAX 100-150KTL3-X MV - page 3
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about MAX 100-150KTL3-X MV Growatt

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Unknown in PDF format for free! Find your manual MAX 100-150KTL3-X MV - Growatt and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MAX 100-150KTL3-X MV by Growatt.

USER MANUAL MAX 100-150KTL3-X MV Growatt

natural_image Stylized globe with leafy tree above Earth (no text or symbols)

Growatt MAX 100-150KTL3-X MV - 1
Download Manual

Growatt MAX 100-150KTL3-X MV - 2

Growatt MAX 100-150KTL3-X MV - 3

Growatt MAX 100-150KTL3-X MV - 4

Growatt MAX 100-150KTL3-X MV - 5
Growatt New Energy

Shenzhen Growatt New Energy Co., Ltd 4-13/F, Building A, Sino-German(Europe) Industrial Park, Hangcheng Ave, Bao'an District, Shenzhen, China

T: +86 755 2747 1942 E :service@ginverter.com W :www.ginverter.com

GR-UM-241-A-02

Growatt MAX 100-150KTL3-X MV - 6

natural_image Exterior view of a GROWATT industrial control unit (no visible text or symbols beyond branding)

Installation

& Operation Manual

List

1 Overview
2 Safety Precautions
3 Product Introduction
4 Unpacking
5 Installation

1.1 Product Overview
1.2 Applicable Personnel

2.1 Safety Overview
2.2 Symbol
2.3 Meaning of Symbol

3.1 Appearance
3.2 Dimensions
3.3 Nameplate
3.4 Working Principle
3.5 Inverter Storage
3.6 Grid Types
3.7 AFCI Detection Function
3.8 Anti-PID Function

5.1 Basic Installation Requirements
5.2 Installation Environment Requirements
5.3 Moving Requirements
5.4 Wall Mounted Installation
5.5 Installing the Inverter

6 Connecting Cables

6.1 Connection on AC side
6.2 Connection on DC side
6.3 Connection of Communication Cables
6.4 Connecting the Ground Cables

7 System Commissioning

7.1 Inverter Commissioning
7.2 Modes
7.3 LED display

8 Monitoring

8.1 Remote Data Monitoring
8.2 Local Data Monitoring

9 Maintenance

9.1 Routine Maintenance
9.2 Trouble Shooting

10 Product Specification

11 Decommissioning
12 Quality Assurance
13 Contact Us

1 Overview

1.1 Product Overview

This manual is aimed at providing sufficient information and installing instruction for consumers buying Shenzhen Growatt New Energy Co., Ltd (short as Growatt) MAX-X Series solar inverters. Please read this manual carefully before using the MAX-X series inverters and store the manual in a reachable place for an authorized technician. No further notice if there is any change in this manual.

1.2 Applicable Personnel

Only qualified electrical technicians are allowed to install MAX-X series inverter. With reading through this manual and following all the precautions, qualified electrical technician can properly install MAX-X serial inverter, finish trouble shooting and communication settings.

If there is any problem during the installation, the installer can either log on www.ginverter.com and leave a message or call consumer service hotline +86 755 27471942.

2 Safety Precautions

2.1 Safety Overview

1>Before installation please make sure reading through this manual, any damage caused by improper installation. Growatt reserve the right to disclaim any warranty.

2>All the operations and connections must be done by trained qualified electrical technician.

3>During installation except for terminals, do not touch any inside part of the inverter. 4>All the electrical connections must meet local country's safety regulations.

5>If you need maintenance for this inverter, please contact our local authorized installing and maintenance technician.

6>You must get the local power supplier's permit before connecting this inverter to the grid.

Handle Process:

WARNING•The inverter is heavy,please treat with care while handling,in case of crushing injury.

Installation:

NOTICE•Before installation,please read through this manual,any damage cause by improper installation,Growatt reserve the right to disclaim any warranty.
DANGER•Ensure that the inverter is not connected to a power supply and is not power on before installation.
WARNING•Please follow this installation manual as installation condition environment,space and so on.•Please install the inverter in a dry and ventilated environment,otherwise may affect the performance of the inverter.•Please follow the installation procedures in this manual.

Electrical Connections:

Before electrical connection, please ensure the inverter DC switch is at "OFF" also disconnect AC switch, otherwise the high voltage from inverter may cause life risk.Only trained authorized electrical technician can do the electric connection also please follow the connection procedures in this manual along with local country's regulations.High voltage may cause electric shocks and serious injury please do not touch the inverter.Please do not store inverter in area with flammable and explosive material.
Each inverter must install one AC breaker, AC breaker is forbidden to share with other inverters.It is forbidden to add load between inverter and breaker.If the cable is thick, after tightening the cable do not shake it and ensure the cable is well-connected and then start the inverter. Loose connection may cause overheat.Before connecting between PV panels and inverter please ensure the positive and negative poles are correct connected.

Maintenance and replacement:

•Must be installed by trained and authorized electrical technician and accurately follow this manual.•Please disconnect the DC and AC switch for at least five minutes, all the operations should be carried after power disconnection.•If there is PV isolation low alarm, the inverter case may be ungrounded, please do not touch the inverter case.•High voltage of inverter may result in electric shock.
•For better cooling purpose, please regularly clean the fans.•Do not use air pump to clean the fans, cause it may damage the fans.

Other:

After you receiving the inverter please check the packing materials for damage,if there is any damage please contact your supplier.
The Max PV input voltage should not exceed 1100V.For the disposed inverter,the consumer should dispose it according to local disposal rules for electrical equipment waste.

2.2 Symbol Conventions

SymbolDescription
Indicates an imminently hazardous situation which,if not avoided, will result in serious injury or death.
Indicates potentially hazardous situation which,if not avoided,will result in serious injury or death.
Indicates potentially hazardous situation which,if not avoided,will result in minor or moderate injury.
Indicates certain hazardous situation which,if not avoided,will result in property damage.
Reminds operator to read installation manual before operating or installing inverter.
i·After you receiving the inverter please check the packing materials for damage,if there is any damage please contact your supplier.
WARNING·The Max PV input voltage should not exceed 1100V. ·For the disposed inverter,the consumer should dispose it according to local disposal rules for electrical equipment waste.
2.2 Symbol Conventions
SymbolDescription
DANGERIndicates an imminently hazardous situation which,if not avoided, will result in serious injury or death.
WARNINGIndicates potentially hazardous situation which,if not avoided,will result in serious injury or death.
CAUTIONIndicates potentially hazardous situation which,if not avoided,will result in minor or moderate injury.
NOTICEIndicates certain hazardous situation which,if not avoided,will result in property damage.
iReminds operator to read installation manual before operating or installing inverter.

2.3 Lable Description

SymbolNameMeaning
High Voltage Electric ShockInverter operating with high voltage,any operation regarding inverter need to be done by trained and authorized electrical technician.
Burn WarningDo not touch a running inverter cause it generates high temperature on the case.
Protective GroundingConnect inverter to grounding bar.
Delay dischargeResidual voltage exists after the inverter is powered off,it takes 5 minutes for the inverter to discharge to the safe voltage.
Read the installation manualReminds operator to read installation manual before operating or installing inverter.
DCMeans this terminal is for DC side.
ACMeans this terminal is for AC side.
CE MarkThe inverter complies with the requirements of the applicable CE guidelines.

3 Product Introduction

3.1 Appearance

Front view:

Fig 3.1 A B

Bottom view(Termial):

C D E F G H I J

Fig 3.2

Side view:

K L Fig 3.3

M YELRYB

MarkDescriptionMarkDescription
AFront panelHCOM interface
BLEDIComer guard
CPV terminalJWaterproof silicone pad
DDC switchKJunction Box
EBreathing valveLGround screw hole
FExternal fansMHeat sink
GUSB interface

3.2 Basic Data

ModelSize(mm)Weight(kg)
WidthHeightThickness
MAX-X Series Inverter97064034584
MAX-X Series Inverter with package109576550098

3.3 Nameplate

GROWATT PV Grid Inverter
Model nameMAX-125KTL3-X LV
Max. PV voltage1100 d.c.V
PV voltage range180-1000 d.c.V
PV Isc40 d.c.A*10
Max. input current32 d.c.A*10
Max. output power125 kW
Max. apparent power137.5 kVA
Nominal output voltage3W/N/PE 230/400 a.c.V
Max. output current208.9 a.c.A
Nominal output frequency50/60 Hz
Power factor range0.8leading~0.8lagging
Safety levelClass I
ingress protectionIP66
Operation ambient temperature-30°C ~ +60°C

Note: Other models of MAX-X series share the same label design with MAX125KTL3-X LV, only with different model name and parameters, detail parameter please refer to specification in Chapter 10.

3.4 Working Principle

The MAX-X series inverter works as follows:

1>The PV panels gather solar to generate DC power to inverter.

2>With input current detection circuit, it can monitor all the PV panels' working status

and use MPPT to track the maximum power point.

3>With inverter circuit change DC power to AC power, and feed power back to grid per grid requirement.

4>With output isolation relay can isolate AC output and grid, if anything goes wrong on either inverter side or grid side, isolation relay can disconnect inverter immediately.

On grid connection system diagram:

Growatt MAX 100-150KTL3-X MV - Working Principle - 1

flowchart
graph LR
    A["Stage A: Solar Panel"] --> B["Stage B: Refrigerator"]
    B --> C["Stage C: Dishwasher"]
    C --> D["Stage D: Tower Bridge"]

Fig 3.4

symbolDescriptionsymbolDescription
APV stringCElectric meter
BInverterDGird

3.5 Inverter Storage

1>Do not unpack the inverter and store it in a ventilation dry place.

2>Keep the storage temperature at -30 °C- +60°C and humidity at 0-95%.

3>A maximum of three inverters with package can be stacked.

4>If the inverter has been long-term stored, inspections and tests should be conducted by qualified personnel before it is put into use.

Growatt MAX 100-150KTL3-X MV - Inverter Storage - 1

After being stored for a month or longer, the inverter's time and date could be wrong, you need set the time and date before using, for more details please refer to Chapter 7.1 inverter commissioning.

3.6 Grid Types

The MAX-X series, MAX100-133KTL3-X LV inverters connect to the grid like following drawing 3.5, MAX 125-150KTL3-X MV inverters connect to the grid like following drawing 3.6.

400V 400V 230V 230V 230V 480V 480V Fig 3.5

490V 480V Fig 3.6

3.7 AFCI Detection Function

AFCI (Arc Fault Circuit Interrupter) is a kind of circuit protection device, the main function is to prevent the fire caused by fault arc. The electrical insulation aging, breakage, loose connection, air breakdown caused by air humidity and so on, all of these may cause an electric spark, which is called arc.

The AFCI function of the MAX-X series inverter is optional, and the detection equipment is assembled inside the inverter. When an arc-drawing condition is detected on the PV input side, the arc current could be detected by the CT assembled on the PV input-side wire. Then the inverter will shut down. Meanwhile, the inverter will display the corresponding fault message and the buzzer will sound, which could help to avoid harm and economic loss to the user.

NOTE: AFCI function is optional.

3.8 Anti-PID Function

The full name of PID is Potential Induced Degradation. Since the PID effect, a large amount of charge could accumulate on the surface of the photovoltaic module, which makes the surface passivation of the module worse. Eventually, the fill factor, open-circuit voltage, and short-circuit current of the module are reduced, and the power of the photovoltaic module is attenuated.

The Anti-PID function uses the principle of reversible PID changes. MAX-X series inverters rectify AC voltage at night and boost it to generate a DC voltage. The DC voltage is connected to PV + and the ground respectively. When add a positive bias voltage to the module to make the PID effect reverse, the Anti-PID function could repair the photovoltaic modules at night and prolong the service life of photovoltaic modules.

NOTE: Anti-PID function is optional.

4 Unpacking

Checking before installation

1>Before unpacking the inverter, check the outer packing materials for damage.

2>After unpacking the inverter, check that the contents are intact and complete. If any damage is found or any component is missing, contact your supplier.

Package contents:

A B C D E 安装手册 F G H I J K L

Fig 4.1

MarkDescriptionsNumber
AInverter1
BWall mount1
CPV + terminal, PV- terminal20/20
DPV terminal metal core20/20
ERemoval tool of PV terminals1
FInstallation manual1
GWarranty card1
HCommunication terminal1
IRemoval handle(opt)2
JM10*90 Expansion screw4
KM6*28 stainless steel screw2
LAC wiring copper terminal (opt)4 or 5

Installation 5

Growatt MAX 100-150KTL3-X MV - Installation 5 - 1
CAUTION

• To prevent device damage and personal injury, keep balance when moving the inverter because it is heavy.

- Do not place the inverter with its wiring and signal terminals at the bottom contacting with floor or any other object because the terminals are not designed to support the weight of inverter.

- When placing inverter on the floor, put foam or paper under the inverter to protect its cover.

5.1 Basic Installation Requirements

A. Ensure that the installation wall is solid enough to bear the inverter(Inverter weight please refer to installation manual Chapter3, 3.2).

B. There must be enough installation space to fit the size of inverter.

C. Do not install inverter on flammable or heat-intolerant buildings.

D. This inverter is IP 66 protection, you can install it indoor or outdoor.

E. To avoid inverter performance de-rate due to the over heat, please do not expose the inverter under direct sunlight.

F. The installation humidity should be from 0-95%.

G. The surrounding temperature of inverter should be from -30^ - + 60^ .

H. Inverter should be installed in a vertically or rear tilted surface, please refer to following drawings.

Technical drawing showing orthographic projections and cross-sections of a truck, with dimension annotations like 5/18" and 20+°.

Fig 5.1

I. To ensure the inverter can work smoothly and easy for personnel to operate, please notice there is sufficient space for inverter, refer to following drawing.

Technical diagram showing a brick wall with a labeled component and dimension annotations

Fig 5.2

J. Do not install inverter close to strong electromagnetic signal. K. Install the inverter out of children's reach.

5.2 Installation Environment Requirements

A. Although the inverter's protection level is IP 66, to extent inverter lifespan you still need to avoid rain and snow, please refer to following drawings.

Growatt MAX 100-150KTL3-X MV - Installation Environment Requirements - 1

B. To reduce the de-rate performance of the inverter and extend inverter's life span, we strongly recommend you install an awning, for the distance between an awning and inverter, please refer to following drawing.

>600mm 398mm 500mm

>1500mm 图2-3-4-1-1

Fig 5.4

C. When you install multiple inverters on one surface, inverters should be installed as following drawing.

≥1000 Roof ≥2000 ≥3000 Ground wt. mm

Fig 5.5

D. Do not install inverter into an enclosed space like following drawing.

Growatt MAX 100-150KTL3-X MV - Installation Environment Requirements - 5

natural_image 3D wireframe diagram of a mechanical part with a curved cutout and label (no readable text or symbols)

Fig 5.6

5.3 Moving Requirements

Growatt MAX 100-150KTL3-X MV - Moving Requirements - 1
WARNING

- The inverter is heavy, please move it with care and keep balance to avoid personnel injury.

- Do not place the inverter with its wiring and signal terminals at the bottom contacting with floor or any other object because the terminals are not designed to support the weight of inverter.

Plan 1:

1>As shown in Fig5.7, use a rope to tie at ring and handle, lift the inverter from package and move to installation position.

2>When you are moving the inverter, please keep the balance.

Notice: There is front and bottom mark on the package.

Plan 2(Optional):

1>As shown in Fig5.8, 4-6 persons lift the inverter out of package, swap the ring to moving handles.

2>When you are moving the inverter, please keep the balance.

Notice: There will be front and bottom mark on the package.

Growatt MAX 100-150KTL3-X MV - Moving Requirements - 2

natural_image Isometric line drawing of a crane lifting a rectangular box inside a transparent cube (no text or symbols)

Fig 5.7

Growatt MAX 100-150KTL3-X MV - Moving Requirements - 3

natural_image Technical line drawing of an electronic device casing with internal components and mounting ports (no text or symbols)

Fig 5.8

5.4 Wall Mount Bracket Installation

Before install the inverter you need install the wall mount bracket so that the inverter can be firmly installed on the wall.

Wall mount plan:

840 190

Fig 5.9

1>Use the wall mount plate as a template drill holes on the wall and put in expansion bolts.

Growatt MAX 100-150KTL3-X MV - Wall Mount Bracket Installation - 2

natural_image Diagram showing a brick wall with circular holes and an inset circle highlighting a hole (no text or symbols)

Fig 5.10

Notice: Expansion bolt should be installed on solid walls with at least 100mm thickness.

2>Follow the following drawing put the bolt to install the wall mount plate on the wall.

Growatt MAX 100-150KTL3-X MV - Wall Mount Bracket Installation - 3

natural_image Pure architectural grid pattern with no text, numbers, or symbols

Fig 5.11

Notice: Do not install inverter unless you have confirmed the wall mount plate has been firmly installed on the wall.

5.5 Installing The Inverter

After the wall mount bracket has been firmly installed on the wall, put the inverter on that plate.

1>Use the rope(must meet the weight requirement of the inverter) through two rings and lift the inverter up, just as following Figure.

2>Before hanging the inverter on the wall mount bracket use screws to fix the inverter and please keep the inverter balance.

3>Check the inverter if it is firm enough and lock all the screws.

Growatt MAX 100-150KTL3-X MV - Installing The Inverter - 1

natural_image Line drawing of a crane lifting a rectangular box (no text or symbols)

图5.12

Growatt MAX 100-150KTL3-X MV - Installing The Inverter - 2

natural_image Technical line drawing of a mechanical device with mounting bracket and control panel (no text or symbols)

图5.13

Growatt MAX 100-150KTL3-X MV - Installing The Inverter - 3

natural_image Technical line drawing of a wall-mounted device mounted on a brick wall, with an inset showing a close-up detail (no text or symbols)

图5.14

Connecting Cable 6

Decisive Voltage Class (DVC) indicated for ports

Port NameClass
ACC
DCC
DRMSA
RS485&USBA

6.1 Connection on AC side

•Before electrical connection, please ensure the inverter DC switch is at 'OFF' also disconnect AC switch, otherwise the high voltage from inverter may cause life risk.
Growatt MAX 100-150KTL3-X MV - Connection on AC side - 1•Only trained authorized electrical technician can do the electric connection also please follow the connection procedures in this manual along with local country's regulations.
DANGER•High voltage may cause electric shocks and serious injury please do not touch the inverter.•Please do not store inverter in area with flammable and explosive material.
Growatt MAX 100-150KTL3-X MV - Connection on AC side - 2•Each inverter must install one AC breaker, AC breaker is forbidden to share with other inverters.
WARNING•It is forbidden to add load between inverter and breaker.

DANGER
WARNING

Preparation before connection:

1>Disconnect inverter DC switch and AC breaker or switch.

2>When you lock the AC cable's screw, the torque force should be 20-30N·m (200-300kgf·cm).

When you lock the cover screw, the torque force should be 2.5-3.0N·m (25-30kgf·cm). 3>Measure the grid voltage and frequency, please refer to chapter 10.

AC breaker specification:

Inverter modelBreaker model
MAX 100KTL3-X LV200A/400Vac
MAX 110KTL3-X LV250A/400Vac
MAX 120KTL3-X LV250A/400Vac
MAX 125KTL3-X LV250A/400Vac
MAX 133KTL3-X LV250A/400Vac
MAX 125KTL3-X MV200A/500Vac
MAX 136KTL3-X MV250A/500Vac
MAX 150KTL3-X MV250A/500Vac

Cable specification:

Inverter ModelCopper wire crosssectional area( mm^2 )Copper wire recommendation ( mm^2 )Aluminum wire recommendation ( mm^2 )
MAX 100KTL3-X LV70-2407095
MAX 110KTL3-X LV
MAX 120KTL3-X LV
MAX 125KTL3-X LV
MAX 133KTL3-X LV
MAX 125KTL3-X MV
MAX 136KTL3-X MV
MAX 150KTL3-X MV

Notice: The cable must be unbroken.
When using aluminum alloy cables, please use copper-aluminum transition terminals.

AC side connection steps:
Growatt MAX 100-150KTL3-X MV - Connection on AC side - 3
- If the cable is thick, after tightening the cable do not shake it and ensure the cable is well-connected and then start the inverter. Loose connection may cause overheat.
1>Following drawing shows inverter's AC terminal, R, S, T are three live lines, N is Neutral line.

Technical diagram of an electrical enclosure with labeled components and status indicators

Fig 6.1

2>Determine the stripping length (approximately 30mm) according to the specifications of the crimping terminal. Use crimping tools to crimp the wires and terminals, then connect the cables to the corresponding channels through the waterproof interface, and tighten the screws.

M12(L1/L2/L3/N):20-30N·m M8(PE):6-8N·m

Fig 6.2

NOTE: Use a torque wrench to tighten the screws/nuts with reference to the torque ranges provided above.

Diagram of how to install a terminal:

Growatt MAX 100-150KTL3-X MV - Connection on AC side - 6
Fig 6.3

3>Apply fireproof mud to the threading holes on the waterproof silicone pad to prevent the risk of water ingress, as shown in the figure below.

Growatt MAX 100-150KTL3-X MV - Connection on AC side - 7
- The gaps in the cable threading holes must be blocked, otherwise there will be a risk of water leakage.

Tighten waterproof cover

Fig 6.4

6.2 Connection On DC Side

Growatt MAX 100-150KTL3-X MV - Connection On DC Side - 1

•Before electrical connection, please ensure the inverter DC switch is at "OFF" also disconnect AC switch, otherwise the high voltage from inverter may cause life risk.
•Only trained authorized electrical technician can do the electric connection also please follow the connection procedures in this manual along with local country's regulations.
•High voltage may cause electric shocks and serious injury please do not touch the inverter.
•Do not place flammable or explosive materials around the inverter.

Notice: The sunlight will generate voltage on the solar panels, after serial connection, the high voltage may injure personnel, so before connect DC input cable you need cover solar panels with light-tight materials and make sure the inverter DC switch is at "OFF" status, otherwise high voltage may injure personnel.

Growatt MAX 100-150KTL3-X MV - Connection On DC Side - 2

Each string's maximum open circuit voltage cannot exceed 1100Vdc, otherwise it could lead to fire or damage the inverter. If the inverter was damaged by higher maximum open circuit voltage (higher than 1100Vdc) product warranty will be forfeited and Growatt will not take any responsibility.The inverter shall be used with IEC 61730 Class A rating PV module.When the group is suspended, be sure to use dust plugs to block up to prevent entering the water into the dust.

1>Each string solar panels should be same brand and same model. 2>Under any circumstance, the maximum short circuit current should not exceed 32A. 3>The total panels power should not exceed 1.5 times of inverter input power. 4>To optimize system settings, recommend two strings with same amount solar panels. Notice: Connectors need to be fit with male and female terminals, before connecting panels with inverter please make sure the positive pole and negative pole, namely the solar panels' positive pole connect to "+" negative pole connect to"-"

Growatt MAX 100-150KTL3-X MV - Connection On DC Side - 3

natural_image Technical line drawing of a mechanical assembly with multiple components and a directional arrow (no text or symbols)

Fig 6.5

5>Decide the length of peeling base on cable terminal, use the wire stripper to connect cable and terminal, and separately connect to specific connector.

6>Connect the positive and negative poles to inverter terminals, different inverter's maximum single string input current please refer to following table.

Inverter modelMax. single string input current
MAX-X serial inverter16 A* 2

7>Cable specifications:

Inverter modelCross-sectional area(mm2)Recommendation (mm2)Cable outer diameter(mm)
MAX-X serial inverter4-644.5-7.8

Notice: 1.Under any circumstance, the total current of all strings cannot exceed the

inverter's maximum current.

  1. Do not touch any working solar panels.

  2. Make sure the cable is unbroken.

6.3 Connection Of Communication Cables

6.3.1 RS485 port

RS485 can carry out single-machine communication or multi-machine (32pcs) long-distance (500 meters) high-speed (baud rate 38400) communication. It is recommended to use twisted-pair shielded wire for RS485 communication line. For single-machine communication, the communication line can be connected to pin 3/4, and its shielding layer can be connected to pin 1. When multiple machines are connected in parallel, two RS485-1 ports can be connected at the same time. When used, the shielding layer can be connected to pin 1/2.

Growatt MAX 100-150KTL3-X MV - RS485 port - 1
Fig 6.6

PortPINDescriptionPortPINDescription
Shield ground 12 485-1 PE ShieldDRMS9DRM1/5
RS485-1 IN3485-1 A110DRM2/6
4485-1 B111DRM3/7
RS485-1 OUT5485-1 A112DRM4/8
6485-1 B113REF/GEN
RS485-27485-2 A114DRM0/COM
8485-2 B1RS485-1Matching resistance15/16485-1Matching resistance

Notice: When multiple inverters communicate in parallel, the last machine needs to add matching resistance. The method is to use a wire to connect the pin 15/16 together.

In MAX-X series inverters, RS485 interface is standard. The connection steps of RS485 communication line are as follows:

1) Unscrew the waterproof cover of the COM interface and remove it.

2) Connect the RS485 communication line to the port of 485-1.

3) The inverter is connected hand in hand through the RS485 communication line, and the end of the communication line 485_A/8 is connected to the monitoring equipment to realize multi-machine remote monitoring.

Note: When locking the RS485 cable screw, the torque is 0.4-0.6N·m (4-6kgf·cm).

Growatt MAX 100-150KTL3-X MV - RS485 port - 2

natural_image Technical line drawing of a rack-mounted electronic device with multiple ports and a close-up inset showing a circular component detail (no text or symbols)

Fig 6.7

6.3.2 USB port

The MAX-X series inverters are equipped with a USB interface as standard, which can be connected to a USB to WIFI module, Shine GPRS-X2, Shine WIFI-X, Shine 4G-X, Shine Link-X and other optional monitoring modules to realize remote Monitoring function. In addition, you can also quickly upgrade the inverter software through the U disk. Steps to install the monitoring module:

1> Loosen the waterproof cover of the USB interface and remove it.

2> As shown in Figure 6.8A, insert the Shine GPRS-X2 module into the USB interface, and the LED of the Shine GPRS-X2 module will be on.

3> As shown in Figure 6.8B, make sure that the is facing upwards, insert the monitoring module into the USB interface, and tighten the lock.

Note: If you use a USB to WIFI module, when the operator leaves, please take the module and the data cable away, and tighten the waterproof cover to prevent water from entering the interface.

Growatt MAX 100-150KTL3-X MV - USB port - 1

natural_image Technical line drawing of a mechanical assembly with no visible text or symbols

Fig 6.8A

Installation The Inverter Side ↑ up The Inverter Side

Remove The Inverter Side The Inverter Side

Fig 6.8B

6.4 Connecting The Ground Cables

In this solar system all the unloaded metal components and cases should be connected to the ground.

Single inverter need grounding over a PE point, multiple inverters need connect all the inverter PE cable and solar panels shelves to the same grounding point to achieve equipotential.

The grounding steps as following:

Take out the ground screw at the inverter bottom, connect the ground cables as following figure

Notice: 1. The machine is safely separated from the lightning protection and the distance is as far as possible.

2.Do not expose Grounding terminal in the air and precaution for the rain.

  1. When you lock the case ground screw, the torque force should be 6-8N·m (60-80kgf·cm).

Growatt MAX 100-150KTL3-X MV - Connecting The Ground Cables - 1

natural_image Technical line drawing of a mechanical assembly with no visible text or symbols

Fig 6.9

According to the relevant provisions of IEC 61643-32. "Connecting to photovoltaic devices surge protectors - selection and use of guidelines", whether for household or outdoor photovoltaic power plants, it is necessary to ensure the implementation of lightning protection measures for photovoltaic systems.

WARNINGThe lightning protection measures for photovoltaic systems shall be carried out in accordance with the corresponding national standards and IEC standards. Otherwise, photovoltaic devices such as components, inverters and power distribution facilities may be damaged by lightning.In this case, the company does not carry out warranty and assumes any responsibility.

Growatt MAX 100-150KTL3-X MV - Connecting The Ground Cables - 2

flowchart
graph LR
    A["Photovoltaic panel"] --> B["Inverter"]
    B --> C["Distribution Cabinet"]
    C --> D["Grounding bar"]
    D --> E["Equipment ground wire"]
    E --> F["Total grounding point"]
    G["Safety interval S"] --> A
    H["Power grid"] --> C
    I["Lightning down the line"] --> E

Fig 6.10

1) It is generally recommended to install lightning protection devices (such as lightning rods / lightning protection belts and down conductors) to prevent lightning from hitting the PV array.

2) Lightning protection devices and down-conductors and related equipment in photovoltaic systems (including photovoltaic panels, inverters, cables, power distribution equipment) should maintain a safe separation distance S. Suggested value of S: According to the general 5 storey height (about 15m) building roof, S takes 2.5m enough, this distance can be simplified according to the inverse relationship of the floor height.

A. When the safety distance S is satisfied:

The position ①③ of the figure should be equipped with a lightning protection module. In general, it is recommended to install Type II in position ① and Type I in position ③. B. When the safety and safety distance S is not met:

In addition to position 3, Type I lightning protection module should be installed in Figure ①②④.

3) The lightning down conductor and the equipment ground wire eventually sink at a total ground point, but the two cannot share the wire. That is, the equipment grounding wire should be pulled separately, and the wire diameter requirement >6mm² when the safety interval distance S is satisfied.

4) About the above lightning protection lightning receptor system related design reference GB/T 21714.3-2015.

7 Commissioning

7.1 Commission The Inverter

Growatt MAX 100-150KTL3-X MV - Commission The Inverter - 1

- If the inverter is stored over one month, its default time and date may looks wrong, the time and date should be reset before connection to the grid.

The inverter will be set to the appropriate model according to the standards of different countries or regions before leaving the factory. For example, the inverters shipped to Australia are configured as Australian model in the factory. Note: The inverter is configured for Australia at the factory.

7.1.1 Set inverter address

After inverter is started normally, inverter address can be set via RS485/USB converting to WIFI. When multiple inverters are connected in parallel via RS485, the inverter must be set to a different communication address. When a single inverter communicates, the default communication address can be used.

Note: The default communication address of the inverter is 1, which can be set to 1-254.

7.1.1.1 Set RS485 address with Shinebus

The 485 address of the inverter can be modified by Shinebus, This operation is performed by a professional.

7.1.1.2 Set RS485 address on ShinePhone APP

Refer to 8.2 download mobile APP ShinePhone and connect to inverter WIFI to enter local monitoring page, this operation is performed by a professional.

1>Click "Parameters";

2>Enter password.(When you use it for the first time, you need to set the password first. Click "Reset password" to enter the OSS account number and password. The distributor and installer can apply for the OSS account from Growatt. Click "Sign in" to set the password. After the setting is successful, you can start using it.) 3>Click top item "COM Address";

4>Click the "Read" button in the upper right corner to read the current communication address of the inverter;

5> Set inverter com address;

6>Read inverter com address to ensure setting is successful;

Back Auto refresh Energy None Resource Current Level New/Control Error Close Help Device control Reset password OK/OK/Cancel Set down mode code Device Information PV Web/Current Strong Vol/Current AC Vol/Current/Power/Plug PID Vol/Current Internal parameters 1 Device Information PV Web/Current Strong Vol/Current AC Vol/Current/Power/Plug PID Vol/Current Internal parameters 2 Note Not allowed for unauthorized person? Being setting new cable system stop which is kept order password. Cancel Yes 2 Device information 1 2 3 4 5 6 7 8 9 0 - / : : ( ) $ & # - , . ? ! - ABC 80000 Returns Back Reset COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web(10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) Value 0 Set COM Web (10) value 0 Set COM Web (10) value 0 Set COM Web (10) value 0 Set COM Web (10) value 0 Set COM Web (10) value 0 Set COM Web (10) value 0 Set COM Web (10) value 0 Set COM Web (10) value 0 Set COM Web (10) value 0 Succeed Yes

Fig 7.1

7.1.2 Set inverter time and date

Method 1

Please refer to section 8.2.1 and login ShinePhone APP.Click "system time(45-50)" to set inverter time and date on the parameter setting page.

Back System time(15-10) 2018-05-20 20 09:44 Value 2018-05-20 2018:16 Set Back System time(15-10) Click to select Cancel Done Today 8 09 PM Tue May 29 9 10 Wed May 30 11 Thu May 31 12 Fri May 32 13 Succeed Yes

Fig 7.2

7.2 Operation Mode

7.2.1 Waiting mode

When the DC voltage is more than 180Vdc, inverter will be powered on and enters the "waiting" state.

At this mode, inverter will check the system parameter. If the system is normal and PV voltage is more than 195Vdc, inverter will try to connect to the grid.

7.2.2 Working mode

At this mode, inverter work normally, and the Power or fault code indicator light shows the power delivered by the inverter to the grid.

When the DC voltage is more than 180Vdc, inverter converts the DC power generated by the PV modules into AC power and supplies them to the grid.

When the DC voltage is lower than 180Vdc, inverter will enter into "waiting" state and try to connect to the grid, at this status, inverter consume very small power to check the internal system status.

Note: only when the PV modules supply enough power(voltage>>195Vdc) then the inverter will start automatically.

7.2.3 Fault mode

Inverter intelligent control system will continuously monitor and adjust system status. When there is a fault detected, LED will show the fault message. Note: Please refer to section 8.2 to check the fault message and take corrective measures.

7.2.4 Off mode

When the sunlight is weak or no light, inverter will stop working automatically. When it is off, inverter will not consume gird power or PV module. At the same time, the LED of inverter will be turned off.

Note: When PV string DC voltage is too low(≤150Vdc), inverter will be off.

7.3 LED Display

Inverter current operation status can be visually checked from LED display directly.

MAX A B C D E

Fig 7.3

MAX == ~ ① (Hz)

Fig 7.4

Description of LED status
Position of LEDType of LEDInverter statusLED status
APV voltage indicator lightPV voltage reaches grid voltageGreen light is on
PV voltage does not reach the grid voltageLight is not on
BAC voltage indicator lightInverter is in the grid stateGreen light is on
No AC voltageLight is not on
With AC voltage, inverter is in the grid countdown stateThe green light flashes slowly, and the alarm or fault indicator light is not on
BAC voltage indicator lightWith AC voltage, inverter is in a fault stateThe green light flashes slowly, and the alarm or fault indicator light is steady red.
CAlarm or fault indicator lightInverter works normallyLight is not on
Inverter is in alarm stateRed light flashes slowly
Inverter is in fault stateRed light is on
DCommunication indicator lightInverter has external communication, such as RS485, GPRS, etc.Green light is on
Inverter has no external communicationLight is not on
Inverter upgrade or USB interface is reading and writing dataGreen light flashes
EPower or fault code indicator lightInverter is in the grid stateThe eight LEDs from left to right represent the power of the inverter: if 8 green lights are on, it represents 100% of the inverter power. As shown in Figure 7.3, it represents 37.5% of the inverter power, and so on.
Inverter is in fault stateThe 8 LED lights from right to left represent the fault codes currently reported by the inverter. From right to left, they represent 1, 2, 4, 8, 16, 32, 64, and 128. For example, the first and fourth green LEDs on the right are always on, which means 1+8=9 . In addition, add 200 to get 209, which means the inverter reports fault 209, and so on.

Monitoring

8

8.1 Remote Data Monitoring

MAX-X series inverter remote monitoring ways include APP(ShinePhone) and server Web page, RS485,GPRS,4G,PLC(reserved) can satisfy both ways of monitoring.

8.1.1 Mobile phone APP(ShinePhone) remote monitoring

1>Scan the following QR code, or download from Android store or App store by searching "Shinephone", download and install software.

Growatt MAX 100-150KTL3-X MV - Mobile phone APP(ShinePhone) remote monitoring - 1
Fig 8.1

Note: 1. Make you it's the latest version

  1. Please find more details on http://server.growatt.com.

2>Users can register their mobile APP account by following the steps below:

Run ShinePhone, go to login page, click "register". Registration is required to fill in the information, with the * is required, the agreement is mandatory, you can log in to the main interface of ShinePhone after registration, the registration page and the main interface are as shown below.

Shinephone login and main page:

Enter password Enter password Target password Register Sign In Delhi

Fig 8.2

Growatt MAX 100-150KTL3-X MV - Mobile phone APP(ShinePhone) remote monitoring - 3

other | Category | Value | |---|---| | Total Units | 3.5 | | Energy (kWh) | 568.3 | | Renewable Energy (kWh) | 682 | | Total Units (kWh) | 454.2 | | Efficiency (%) | 11.7 | | Total Units (kWh) | 14088.72 | My device list | SASF 810013 | Discretionary | | SASF 830201 | Discretionary | | SASF 810007 | Discretionary | | SASF 830202 | Discretionary |

Fig 8.3

Device page:

1>Main page top middle is the name of current plant, user can click the "v" button to switch to other plants under this account.
2>User can add datalogger, check datalogger and add plant by click" + "button at the top right corner.
3>Top half shows current plant power, revenue today and total production.
4>My device list shows current plant device, user can see more details by click the device, left cross the device to stick the device and edit, edit operation includes change device alias, icon, and delete device.

Back Add debugger Find debugger 5h Find debugging checkcode Yes Review a debug

Fig 8.4 add datalogger

Back Catalogger Net Add Name: 7610030028 (Ctrl+Alt) Serial Number: 7610030026 Device Type: ImageRGB Data encoding time: 5 Name: 7610030029 (Ctrl+Alt) Serial Number: 7610030028 Device Type: ImageRGB Data encoding time: 0.1 Name: ACACCTG012 (Ctrl+Alt) Serial Number: ACACCTG029

Fig 8.5 datalogger list

Part management Add plant Point name: Installation date: Country China Time zone In Next

Fig 8.6 add plant

Datalogger:

1>User can add more datalogger under the particular plant.

Way: Click "+" in the upper right corner of the device page and select "Add Collector (WiFi/GPRS, etc.)", as shown in Figure 8.7.

Note: You can choose to manually enter the collector serial number for addition, or you can add it by scanning the barcode on the nameplate.

Growatt MAX 100-150KTL3-X MV - Datalogger: - 1

3>User can add more plants with the add Plant function.

Device page and function:

1>Device page: User can click the device to see more details, the device page show current power and Energy today and daily power chart, user can find more with control, parameter, data and Events page.
2>Control: user set inverter on/off, set active power, set reactive power, set PF, set inverter time, set grid voltage high, set grid voltage low. The operation password is : inverter+date, for example inverter20170722.
3>Parameter: user can see device SN, rated power, firmware version, PV1 voltage, current, and power etc.

Growatt MAX 100-150KTL3-X MV - Device page and function: - 1

Growatt MAX 100-150KTL3-X MV - Device page and function: - 2

area | Date | Power (W) | |---|---| | 06/01 | 0 | | 06/02 | 0 | | 06/03 | 0 | | 06/04 | 0 | | 06/05 | 0 | | 06/06 | 0 | | 06/07 | 0 | | 06/08 | 0 | | 06/09 | 0 | | 06/10 | 0 | | 06/11 | 0 | | 06/12 | 0 | | 06/13 | 0 | | 06/14 | 0 | | 06/15 | 0 | | 06/16 | 0 | | 06/17 | 0 | | 06/18 | 0 | | 06/19 | 0 | | 06/20 | 0 | | 06/21 | 0 | | 06/22 | 0 | | 06/23 | 0 | | 06/24 | 0 | | 06/25 | 0 | | 06/26 | 0 | | 06/27 | 0 | | 06/28 | 0 | | 06/29 | 0 | | 06/30 | 0 | | 07/01 | 0 | | 07/02 | 0 | | 07/03 | 0 | | 07/04 | 0 | | 07/05 | 0 | | 07/06 | 0 | | 07/07 | 0 | | 07/08 | 0 | | 07/09 | 0 | | 07/10 | 0 | | 07/11 | 0 | | 07/12 | 0 | | 07/13 | 0 | | 07/14 | 0 | | 07/15 | 0 | | 07/16 | 0 | | 07/17 | 0 | | 07/18 | 0 | | 07/19 | 0 | | 07/20 | 0 | | 07/21 | 0 | | 07/22 | 0 | | 07/23 | 0 | | 07/24 | 0 | | 07/25 | 0 | | 07/26 | 0 | | 07/27 | 0 | | 07/28 | 0 | | 07/29 | 0 | | 07/30 | 0 | | 11/1 | -1.5 | | 11/2 | -1.5 | | 11/3 | -1.5 | | 11/4 | -1.5 | | 11/5 | -1.5 | | 11/6 | -1.5 | | 11/7 | -1.5 | | 11/8 | -1.5 | | 11/9 | -1.5 | | 11/10 | -1.5 | | 11/11 | -1.5 | | 11/12 | -1.5 | | 11/13 | -1.5 | | 11/14 | -1.5 | | 11/15 | -1.5 | | 11/16 | -1.5 | | 11/17 | -1.5 | | 11/18 | -1.5 | | 11/19 | -1.5 | | 11/20 | -1.5 | | 11/21 | -1.5 | | 11/22 | -1.5 | | 11/23 | -1.5 | | 11/24 | -1.5 | | 11/25 | -1.5 | | 11/26 | -1.5 | | 11/27 | -1.5 | | 11/28 | -1.5 | | 11/29 | -1.5 | | 12/3 | -2.5 | | 12/4 | -2.5 | | 12/5 | -2.5 | | 12/6 | -2.5 | | 12/7 | -2.5 | | 12/8 | -2.5 | | 12/9 | -2.5 | | 12/10 | -2.5 | | 12/11 | -2.5 | | 12/12 | -2.5 | | 12/13 | -2.5 | | 12/14 | -2.5 | | 12/15 | -2.5 | | 12/16 | -2.5 | | 12/17 | -2.5 | | 12/18 | -2.5 | | 12/19 | -2.5 | | 12/20 | -2.5 | | 12/21 | -2.5 | | 12/22 | -2.5 | | 12/23 | -2.5 | | 12/24 | -2.5 | | 12/25 | -2.5 | | 12/26 | -2.5 | | 12/27 | -2.5 | | 12/28 | -2.5 | | 13/3 | -3.5 | | 13/4 | -3.5 | | 13/5 | -3.5 | | 13/6 | -3.5 | | 13/7 | -3.5 | | 13/8 | -3.5 | | 13/9 | -3.5 | | 13/10 | -3.5 | | 13/11 | -3.5 | | 13/12 | -3.5 | | 13/13 | -3.5 | | 13/14 | -3.5 | | 13/15 | -3.5 | | 13/16 | -3.5 | | 13/17 | -3.5 | | 13/18 | -3.5 | | Note: The actual values may vary due to the random nature of the data generation system or the event type (e.g., 'Data' or 'Events'). The provided values are estimated based on the provided code.

Fig 8.8

SASFB03003 Set inverter on/off > Set active power > Set reactive power > Set power factor > Set inverter time > Set grid voltage high > Set grid voltage low >

Fig 8.9

SASB05003 Serial number SASB05003 Font CMTSTST901 model initial Rated power(A) 80000 Firmware version T1.02(SATB76121) Mode A2800TSFFUINIBEA Volt(V) Current(A) Power(W) PV1 14.83 0.00 10.00 PV2 55.63 0.00 0.00 PV3 58.53 0.00 0.00 PV4 68.00 0.00 0.00 PV5 54.23 0.00 0.00 PV6 54.33 0.00 0.00 PV7 54.43 0.00 0.00

Fig 8.10

4>Data page: user can see the PV power, voltage, current, R phase power, S phase power, S phase power, T phase power, output power by day, month, year, by finger up cross the screen.

5>Events: User can see the fault message if there it is.

Pv Power Psc B-prulse Power S-prulse Power Slide up to check detail data

Fig 8.11

BASF00002 VOLI-152PWR0001 Power No. 135 Type Max Tag/Py, input insulation PV Input insulation impedance too low 2018-04-18 10:01:20 VOLI-152PWR0001 Power No. 135 Tag/Py, input insulation PV Input insulation impedance too low 2018-04-18 10:01:06:0 VOLI-152PWR0001 Power No. 135 Tag/Py, input insulation PV Input insulation impedance too low 2018-04-18 10:04:08:0 VOLI-152PWR0002 Power No. 135 Tag/Py, input insulation PV Input insulation impedance too low

Fig 8.12

8.1.2 GPRS /4G

8.1.2.1 Register account

1>Register account

Open browser, input "server.growatt.com", click "New User" at login page, input the necessary information then go back to login page, input the registered username and password, click "Sign In".

ShineDesign Download Help Update Log Langua ShineDesign, make PV plant design easy Designing PV plants is much easier than ever, with Goodwill ShineDesign. You can design your system in any Web browser or an an-iPadAndroid tablet. Then simply enter all the required information and you will receive the optimum plant configuration as a few minutes. ShineDesign Start to go Sign In Empty UserName! DHE Sign In New User Experience APP Download iOS APP Android APP

Fig 8.13

Register Country Username Password Password confirm Language English E-Mail Installer code Enter the installer code or Agree with the Companies terms Register Back to login

Fig 8.14

2>Add datalogger

At Plant page, click device manage, then click add datalogger, input the SN and valid code then save, after device is powered on, datalogger will show after 5mins, also the device will come online (our device is monitored by datalogger, so need to add the datalogger here first).

Welcome : MAXtest (Normal user) Exit MAX • Dashboa Plant User Cen Setting Download English Plant data device list event list Plant Detail datalog inverter storage hybrid inverter Pcs MAX Hps more No. SN alias device type user name connect status 1 79Z0000024 79Z0000024 ShineGPRS MAXtest connection /192. 2 79Z0000015 79Z0000015 ShineGPRS MAXtest connection /192. 3 WLC082102D WLC082102D ShineGPRS MAXtest connection /192. 4 79Z0000020 79Z0000020 ShineGPRS MAXtest connection /192.16l 5 79Z0000008 79Z0000008 ShineGPRS MAXtest connection /192.16l 6 79Z0000033 79Z0000033 ShineGPRS MAXtest connection /192 7 79Z0000023 79Z0000023 ShineGPRS MAXtest connection /192. 8 79Z0000014 79Z0000014 ShineGPRS MAXtest connection /192. 9 WLC0821017 WLC0821017 ShineGPRS MAXtest lost /192. 10 79Z0000021 79Z0000021 ShineGPRS MAXtest lost /192.

Fig 8.15

add data logger SN belongs MAX _

Fig 8.16
Welcome : MAXtest (Normal user) : Exit MAX Dashboard Plant User Center Setting Download English Plant data device list event list Plant Detail catalog inverter storage hybrid inverter Pcs MAX Hps more No. SN alias datalog location(connect status Nepal last login/update time operating 1 SASF803004 SASF803004 79Z0000024 1 normal 2018-05-28 17:04:31

Fig 8.17
Welcome : MAXtest (Normal user) Exit MAX Dashboard Plant User Center Setting Download English Plant data device list event list Plant Detail datalog inverter storage hybrid inverter Pcs MAX Hps more No. SN alias datalog location connect status last login/update time operating 1 SASF803004 SASF803004 7920000024 1 normal 2018-05-28 17:04:31

Fig 8.18

3> Data reading

A. Basic production reading, Energy today, total production, revenue today and accumulative revenue are showing on this page.

Growatt MAX 100-150KTL3-X MV - 2>Add datalogger - 5

line | Date | Solar Production (kWh) | Total Revenue (¥) | | :--- | :--- | :--- | | May 2018-05 | 184334.6 | 2524 | | May 2019-05 | 2103.3 | 221201.5 |

Fig 8.19

B. Plant data page can check device power, voltage curve by time, day, month or year.

Growatt MAX 100-150KTL3-X MV - 2>Add datalogger - 6

line SASF803003 PV POWER | Date | Power (W) | | :--- | :--- | | 00:00:02:05 | 60000 | | 15:08:20:10 | 45000 | | 20:25:12:30 | 40000 | | 16:40:18:45 | 35000 | | 18:52:25:35 | 30000 | | Max(SASF803003) Power: pes PV POWER ○R-P-ASE POWER ○S-PASE POWER T-P-ASE POWER Voltage: PV2 VOLTAGE ○PV2 VOLTAGE ○PV2 VOLTAGE Current: PV2 ELEC-CURRENT ○PV2 ELEC-CURRENT ○PV3 ELEC-CURRENT

Fig 8.20

4>Set up the equipment

The device management page selects MAX. The serial number of the device to be set can be found in the list.

Notice: The following operations are requested by professionals.

Welcome : MAXtest (Normal user) Exit MAX Dashboard Plant User Center Setting Download English ® Plant data device list event list Plant Detail datalog inverter storage hybrid inverter Pos MAX Hpx more No. SN alias datalog location connect status last login/update time operating 1 SASF803004 SASF803004 79Z0000024 1 normal 2018-05-29 1401:43 D ©

Fig 8.21

Flunt data device list event list Plant Detail datalog master storage hybrid inverter Pcs MAX Fips molar No. SN alias datalog location connect status last login/update time operating 1 SASF803004 SASF80300 79Z0000024 1 normal 2018-05-28 17:20:18 2 SASF803004 SASF80300 79Z0000024 1 normal 2018-05-28 17:20:18 3 SASF803004 4 NASF803004 5 SASF803004 6 SASF803004 7 NASF803004 8 SASF803004 9 SASF803004 10 SASF803004 11 SASF803004 12 SASF803004 13 SASF803004 14 SASF803004 15 SASF803004 16 SASF803004 17 SASF803004 18 SASF803004 19 SASF803004 20 SASF803004 21 SASF803004 22 SASF803004 23 SASF803004 24 SASF803004 25 SASF803004 26 SASF803004 27 SASF803004 28 SASF803004 29 SASF803004 30 SASF803004 31 SASF803004 32 SASF803004 33 SASF803004 34 SASF803004 35 SASF803004 36 SASF803004 37 SASF803004 38 SASF803004 39 SASF803004 40 SASF803004 41 SASF803004 42 SASF803004 43 SASF803004 44 SASF803004 45 SASF803004 46 SASF803004 47 SASF803004 48 SASF803004 49 SASF803004 50 SASF803004 51 SASF803004 52 SASF803004 53 SASF803004 54 SASF803004 55 SASF803004 56 SASF803004 57 SASF803004 58 SASF803004 59 SASF803004 60 SASF803004 61 SASF803004 62 SASF803004 63 SASF8O3O1 64 SASF8O3O1 65 SASF8O3O1 66 SASF8O3O1 67 SASF8O3O1 68 SASF8O3O1 69 SASF8O3O1 7MAX SN:SASF8O3O1 4Alias:SASF8O3O1 2property:T1L.OL/tiaA572B1O24/ADBODI76PFU1 MBSA Port:79ZOOOOO 24 Command Enter the serial nSwitch to MAX Shut down *< img src="box"> save cancel advanced set

Fig 8.22

5>Check detailed data

Double-click the device serial number in the device list. The detailed data page is displayed. Data pages can be viewed by date or exported.

Welcome : MAXtest (Normal user) Exit MAX Dashboard Plant User Center Setting Download English Plant data device list event list Plant Detail datalog inverter storage hybrid inverter Pcs MAX Hips more No SN alias datalog location connect status last login/update time operating 1 SASF803004 SASF803004 792000024 1 normal 2018-05-29 14:01:43

Fig 8.23

History Data start date 2018-05-2 end date 2018-05-2 search export
No.Serial numberTimeStatusEacToday(kWh)EacTotal(kWh)Vpx1(V)Vpx20
1SASF8030042018-05-28 17:22:30 Normal235.61341.0542.6609.0
2SASF8030042018-05-28 17:22:23 Normal235.61341.0543.4611.9
3SASF8030042018-05-28 17:22:16 Normal235.61341.0552.7612.8
4SASF8030042018-05-28 17:22:10 Normal235.61341.0549.4617.2
5SASF8030042018-05-28 17:22:05 Normal235.61341.0541.8619.9
6SASF8030042018-05-28 17:21:59 Normal235.61341.0543.6619.2
7SASF8030042018-05-28 17:21:53 Normal235.61341.0542.5622.5
8SASF8030042018-05-28 17:21:48 Normal235.61341.0537.0615.8
9SASF8030042018-05-28 17:21:40 Normal235.61341.0537.1619.2
10SASF8030042018-05-28 17:21:35 Normal235.61341.0540.3624.9
11SASF8030042018-05-28 17:21:29 Normal235.51340.9549.9618.2
12SASF8030042018-05-28 17:21:26 Normal235.51340.9544.2608.8
13SASF8030042018-05-28 17:21:17 Normal235.51340.9543.9618.6
14SASF8030042018-05-28 17:21:09 Normal235.51340.9543.3614.4
15SASF8030042018-05-28 17:21:05 Normal235.51340.9545.9616.5
16SASF8030042018-05-28 17:21:00 Normal235.51340.9544.9617.6
17SASF8030042018-05-28 17:20:55 Normal235.51340.9549.1619.0

Fig 8.24

8.1.2.2 Shinemaster monitoring

This is a cost-effective and compact monitoring device that is specially designed for solar power plants, with a high-speed CPU and a stable Linux system that intelligently records the user's system characteristics.

Multiple inverters ShineMaster cable Router 485-1 IN 485-1 OUT 485-1 IN Add matching resistance RS485 twisted pair cable

Feature :

1> A versatile and high-performance communication data logger that notifies the user of system status at any time.

2> Flexible parameter setting, system information management, error prompting and recording, high-capacity storage.

3> Collect data and upload data to Growatt in real time over the network. Note: The smart meter and environmental monitor must be Growatt's designated manufacturer, otherwise monitoring will not be possible. When RS485 of multiple machines is used in parallel, please connect the ground wire according to section 6.3.1.

The system framework of communication monitoring is shown in the figure below. Users can choose the most suitable monitoring method according to the actual situation.

Growatt MAX 100-150KTL3-X MV - 2&gt;Add datalogger - 11

flowchart
graph TD
    A["Multiple inverters"] --> B["GPRS/4G"]
    A --> C["ShineMaster"]
    A --> D["Computer"]
    A --> E["Connecting communication cable"]
    E --> F["router"]
    F --> G["Connecting communication cable"]
    G --> H["Internet"]
    H --> I["Connecting communication cable"]
    I --> J["DB data storage"]
    H --> K["4G/GPRS"]
    H --> L["4G/GPRS"]
    K --> M["Computer"]
    K --> N["Phone"]
    K --> O["Pad"]
    style A fill:#f9f,stroke:#333
    style H fill:#ccf,stroke:#333

1>ShineMaster IP Address query

A. The PC and shinemaster lan ports are connected to the router's port through the network cable, so that they are in the same local area network.

B. Go to the router's management page and check the "Internet host list" to query the IP address of the ShineMaster serial number as the name of the connected device. This IP is the IP address assigned by the router to the ShineMaster. If you do not know how to do this, contact your network administrator for operation.

Note: The router needs to enable automatic IP assignment, that is, open the DHCP function.

C. Enter the shinemaster IP address in the browser to enter the shinemaster built-in page.

2>ShineMaster Built-in page access

Before accessing, check whether the communication cable between the devices is securely connected. After the check is correct, you can enter the ShineMaster IP address in the IE browser to access the built-in page of the ShineMaster. As long as the ShineMaster is on the same network segment as the computer you are accessing, you can access the ShineMaster built-in server.

A. If the user successfully visits the shinemaster built-in page, they can go directly to the built-in page login interface, as shown in figure 8.25 below.

Growatt ShineMaster Setting Center English Datalogger State Datalogger Setting Network Setting System Management Device State Username Password Login

Fig 8.25

B. Enter user name and password, default login username: admin password: admin. click login after filling in, enter growatt shinemaster system page.

3>ShineMaster Data collector status view

Click on the status of the shinemaster data collector to view shinemaster "system state information", "serial number," server address, "number of connected devices," and so on.

Growatt ShineMaster Setting Center Database Information State Info. Online EN AE/CESO/21 Server IP Server-CN growth.com Server PORT 5270 Database Location IP 132 198.0.6 File 5 Database M/C 8247 15-6C/32.AB Network Server V1.0 Network Version 1 0.1.1 Database Type ShinaAlbster Device Number 1 Off-line Dashset 0 Location Test 2218.05.29 15:01:26 Audio/Red Feature DISABLE E Audio/Red Power(M) 0

Fig 8.26

4>ShineMaster Data collector add or delete device

ShineMaster Before monitoring photovoltaic devices, we need to enter the page of the built-in shinemaster data collector settings to add devices.

A. Add device

1) Select the monitoring mode for monitoring photovoltaic devices in the first drop-down list of add or remove devices.

Growatt ShineMaster Setting Center Database Setting Test Status: LTM Test Before: ↑ ON ↑ OFF Test And After Before test status: 0 Output (Present): 0 Antifocalizer: 100% Catalogger Select/Remove data: 2016-05-29 17:42 AM Output Time: 0 Yes ↑ No Add or Remove data: 0.043, 1 Set Connection: NULL Add: 0.043, 1 Data: 0.043, 1 Data: 0.043, 1 Data: 0.043, 1 Data: 0.043, 1 Data: 0.043, 1 Data: 0.043, 1 Data: 0.043, 1 Data: 0.043, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1 Data: 0, 1

Fig 8.27

2) Select the type of photovoltaic device monitored in the second drop-down list.

Growatt ShineMaster Setting Center Dogslogger Setting Net Mode: LAV Add Mode: ON OFF Select Add Network Base water Output Molar Acid or SN Network Power(0%) (XX to Grid, XX to User) Add Network Diameter: 54.0-05.25 17:24:46 Dogslogger Type: No Add to network devices: RSDR_1, RSDR_2, RSDR_3, RSDR_4, RSDR_5, RSDR_6, RSDR_7, RSDR_8, RSDR_9, RSDR_10, RSDR_11, RSDR_12, RSDR_13, RSDR_14, RSDR_15, RSDR_16, RSDR_17, RSDR_18, RSDR_19, RSDR_20, RSDR_21, RSDR_22, RSDR_23, RSDR_24, RSDR_25, RSDR_26, RSDR_27, RSDR_28, RSDR_29, RSDR_30, RSDR_31, RSDR_32, RSDR_33, RSDR_34, RSDR_35, RSDR_36, RSDR_37, RSDR_38, RSDR_39, RSDR_40, RSDR_41, RSDR_42, RSDR_43, RSDR_44, RSDR_45, RSDR_46, RSDR_47, RSDR_48, RSDR_49, RSDR_50, RSDR_51, RSDR_52, RSDR_53, RSDR_54, RSDR_55, RSDR_56, RSDR_57, RSDR_58, RSDR_59, RSDR_60, RSDR_61, RSDR_62, RSDR_63, RSDR_64, RSDR_65, RSDR_66, RSDR_67, RSDR_68, RSDR_69, RSDR_70, RSDR_71, RSDR_72, RSDR_73, RSDR_74, RSDR_75, RSDR_76, RSDR_77, RSDR_78, RSDR_79, RSDR_80, RSDR_81, RSDR_82, RSDR_83, RSDR_84, RSDR_85, RSDR_86, RSDR_87, RSDR_88, RSDR_89, RSDR_90, RSDR_91, RSDR_92, RSDR_93, RSDR_94, RSDR_95, RSDR_96, RSDR_97, RSDR_98, RSDR_99, RSDR 100

Fig 8.28

3) Fill in the third drop-down list with the photovoltaic device correspondence address.

Growatt ShineMaster Setting Center Data Source Setting Data Mode: CAT Data Source: ON / CFT Select Data Source name: Input Master Add or Ski Database Password: XX to Grid, XX to User Data Sources (Channel): 0123-0124 Data Source: Data Source (Channel) - 578-45-21 17:42:40 - Get Color Time Database Type: Yes / No Add to Service Device: RS480_1 / SWINTER_2 - Add - Cut Set Search Area: FULL - RS480_1 - RS480_2 Save Cancel

Fig 8.29

4) Select "Add" and then click "Save".

5) Go to the device status page after saving success to confirm that the device was added successfully.

Growatt ShineMaster Setting Center System/Device Information Device Adder Device Type Device 36 Device Data Communication mode 011 System TLEACORR01 System 01-02-1 Load

Fig 8.30

B. Delete device

1) Select the first drop-down list of "add or remove devices" to monitor the monitoring mode of photovoltaic devices.

2) Select the type of photovoltaic device monitored in the second drop-down list. 3) Fill in the third drop-down list with the photovoltaic device correspondenc address.. 4) Select the following "del" and click Save to complete the device addition. 5) Enter the device status page after successful save to confirm that the device was deleted successfully.

5>ShineMaster Data upload to ShineServer

A. Register, Login

1) Enter the server domain name in the computer browser to enter the shineserver login page, if you are logged in for the first time, please register the user name. Enter the domain name access page, as shown in figure 8.32 below. Chinese user server domain name: http://server-cn.growatt.com. The domain name of the international user server is: http://server.growatt.com.

ShineDesign Download Help Update Log Langua NEW architecture for better user experience Smart monitoring system resorts for your PV system all day! New service function, clients use communicate with GrowMe via App! ShinePhone4.0 Download Sign In Empty Password! 397 Sign In New User Experience APP Download iOS APP Android APP

Fig 8.31

2) Register user name, input user information according to prompt, after information is completed, click "register".

Note: "collector serial number" and "collector check code" see shinemaster serialnumber box or guarantee box.

Register Country Username Password Password confi rm Language English E-Mail Installer code Enter the installer code or Agree with the Companys terms Register Back to login

Fig 8.32

B. View monitoring data

1) After registration is complete, jump to the shineserver main interface automatically. Click on "power station" and "work information" to display the information for the power station's total power flow chart on the same day. The drop-down list "Select collector" allows you to view the daily power flow chart of a single inverter for the power station.

Growatt MAX 100-150KTL3-X MV - View monitoring data - 1

line | Time | Power (kW) | | -------- | ---------- | | 00:00 | 0 | | 02:05 | 1000 | | 04:10 | 2500 | | 06:15 | 3000 | | 08:20 | 4000 | | 10:25 | 5000 | | 12:30 | 4500 | | 14:35 | 3500 | | 16:40 | 2000 | | 18:45 | 1000 | | 20:50 | 500 | | 22:55 | 0 |

Fig 8.33

2) By clicking on "power station" and "equipment management" in turn, the real-time data of "data collector", "inverter", "environment monitor", "intelligent meter" and "confluence box" MAX can be viewed.

8.2 Local Data Monitoring

MAX-X series Inverter local data monitoring mode has a mobile phone app phone) and PC direct connection, udisk, details are as follows.

8.2.1 Mobile phone app (Shinephone) Local Monitoring

8.2.1.1 Log on to app for local monitoring Method 1

When you open the app login front page, click the top right corner toolbox icon. Pop up the toolbox, click the local debugging tool, and you can get the wifi name of the collector by scanning the QR code or barcode(The default password for WIFI is 12345678. If you have already connected, you can click "Skip" to connect directly to the WIFI.)

Growatt MAX 100-150KTL3-X MV - Mobile phone app (Shinephone) Local Monitoring - 1

flowchart
graph LR
    A["Store selection"] --> B["User input: 'Local Address Only' with 'Latest' label"]
    B --> C["Device setup: 'Local Address Only' with 'Latest' label"]
    C --> D["Device Configuration: 'Local Address Only' with 'Latest' label"]

Fig 8.34

Method 2

Open app enter user name and password click login, enter me (personal center). Click the enter tool, find the local debugger to enter, and you can get the wifi name of the collector by scanning the QR code or barcode (The default password for WIFI is 12345678. If you have already connected, you can click "Skip" to connect directly to the WIFI.)

Growatt MAX 100-150KTL3-X MV - Method 2 - 1

flowchart
graph TD
    A["Input: File Manager"] --> B["Add Management"]
    B --> C["Configuration Of PV Plant"]
    C --> D["Tools"]
    D --> E["Message Center"]
    E --> F["About"]
    F --> G["Device Information"]
    G --> H["Back"]
    H --> I["Start to WiFi name"]
    I --> J["Next"]

Fig 8.35

8.2.1.2 Use of local monitoring and debugging

When viewing local monitoring, you must keep the phone's wifi connected to the collector's wifi to view local monitoring (to enter the local monitoring page, first click auto refresh to get the latest data information).

Electricity generation: the option to view the latest generation, daily generation, monthly and annual generation of detailed information;

Power: you can see the current power and rated power value; failure: can read the equipment detailed fault information.

1>device control

Note: In addition to resetting the password to connect to the network, other WIFI modules that must connect to the collector can view information.

A. Reset password

Need network connection login oss account to set up or modify the local debug password.

B. Setting configuration

The configuration data of inverter, voltage, power and so on can be modified according to the usage (Fig 8.36).

Back Auto refresh Energy 100% 5.0V/Off Power Current Power Normal power Error Freq Waiting Device control Reset password 3RD OAD Parameters Smart Diagnostics Advanced Device Information FV Volt/Current String Volt/Current AC Volt/Current/PowerFreq PID Volt/Current Internal parameters Waiting 0.0m/Off hix(0) 1. Safety standard enable(1) 2. Active power percenting(3) 3.0ms/Ex. Resistx/Power(4) 4. Undertx Resistx/Power(4) 5. UnderEx PF(5) 6.0ms/Ex. PF(5) 7. PV voltage(8) 8. Communication fault risk(22) 9. Run PF is 1(89) 10. Over frequency deating point(93) 11. Over Frequency LoadSpots(92) 12.0 (x) RP Delaytime (107)

Fig 8.36

C.Parameter configuration

The parameter data of the equipment can be modified according to the usage (Fig 8.37).

D. Intelligent detection

Detailed and accurate view of the device's detailed data and status (Fig 8.38).

Back Auto refresh Energy Focus Libraries Power Current Power Not available Error Enter Warning Device control Reset password SRD(MCI) Parameters Smart Diagnostics Advanced Alsting Set model code 0.COM Ader(30) 1.System time(45-80) 2.bpv start(17) 3.Time start(18) 4.Time rest(19) 5.Language(15) 6.Country(15) 7.System/Week(51) 8.bsc Komin Avg(51) 9.PV over voltage (81) 10.Modbus version(85) 11.PID Mode(201) 12.PID Opt(202)

Fig 8.37

Back Auto refresh Energy Solar Ultrate Power Current Power Normal power Error Enter Warning Device control Reset password GRID CMD Parameters Smart Diagnosis Advanced Device Information PV Volt/Current String Volt/Current AC Volt/Current/Power/Freq PID Volt/Current Internal parameters Waiting Smart I-V diagnosis Get i-V curve for each MFFT Fault waveform record Quickly rotate postterm sensitivity via waveform record. Real-time waveform record Check real-time waveform of inverter voltage and current, etc. One click diagnosis including iV values, AC waveform record, THOW and gain Noble Impellance

Fig 8.38

E. Intelligent I-V curve scanning

Can remotely scan each mppt (Fig 8.39).

Table Auto refraction Energy Video Physics Power External Power Power Energy Device control Smart I-V diagnosis Self-IV band for each MHT Fault waveform record Security system parameter usually be wavelet record Real-time waveform record Close real-time waveform of trigger voltage and current, etc. One click diagnosis Acturing -1 V, 2C, and 3V in record, then and grid cable experience. Smart I-V diagnosis Sensitivity time: 2018-04-2011 04:45 MPV/Max. (Peak) (Var. Max.) 1 (227.5363) (8.0) 2 (204.3033) (8.0) 3 (194.2652) (8.0) 4 (165.1783) (8.0) 5 (142.6902) (8.0) 6 (113.126) (8.0) 7 (51.3) (8.0) Internal parameters Device information PV Volt/Current String Volt/Current AC Volt/Current/Power/Freq PID Volt/Current Internal parameters

Fig 8.39

F.Fault recording detection

Remote, fast and accurate fault location (Fig 8.40).

Back Auto refresh Waiting Back Real-time waveform record Energy Smart I-V diagnosis Set I-V record for each MRT Power Fault waveform record Device control Reset password SAP CND Parameters Smart Diagnosis Advanced Real-time waveform record Check real-time waveform of Inverter voltage and current, etc. Device information PV Volt/Current String Volt/Current AC Volt/Current/PowerFreq PID Volt/Current Internal parameters One click diagnosis Washing I-V test, AC waveform record, TCOV and grid clock detection ID Zoom factor Value Set CI X 1 ... Set CI X 1 ... Set CI X 1 ... Set CI X 1 ... Start

Fig 8.40

G. Real-time recording detection

Inverter voltage and current quality can be observed in real time (Fig 8.41).

Back Auto refresh Energy Time Lightline Power Current Power Noted power Error Error Warning Device control Reset password USB CVD Parameters Smart Diagnostics Advanced I Device information PV Volt/Current String Volt/Current AC Volt/Current/PowerFree PID Volt/Current Internal parameters Walking Smart I-V diagnosis Del V surge for each MPPT. Fault waveform record Slightly enable position correctly on waveform record. Real-time waveform record Check real-time waveform of motor voltage and current, etc. One click diagnosis Including I-V type, AC waveform record, THBV and cable resistance. Back Fault waveform record Fail number: Click to switch Fault code: Waveform record time: 0.1s ID: Zoom factor Value Start

Fig 8.41

H. One click diagnosis

I-V curve diagnosis, grid waveform, THDV and cable impedance detection all at one click(Fig 8.42).

I. High level setting

According to the register address set parameters (professionals).

J.Device information

Check PV voltage/current, string voltage/current, AC voltage/current/power/frequency, PID voltage/current, internal parameters and device detail information and parameters (Fig 8.43).

Growatt MAX 100-150KTL3-X MV - Setting configuration - 7

flowchart
graph TD
    A["Device control"] --> B["Device Information"]
    B --> C["Sensor/Carrier"]
    C --> D["AC and Carrier Optimization"]
    D --> E["P0 Vi/V Control"]
    E --> F["Internal parameters"]
    F --> G["Warning"]
    G --> H["Smart I-V diagnosis"]
    H --> I["Fault waveform record"]
    I --> J["Real-time waveform record"]
    J --> K["One click diagnosis"]
    K --> L["Select all: Yes"]
    L --> M["Select item(s)"]
    M --> N["IoW-V cone"]
    M --> O["Grid voltage waveform"]
    M --> P["Grid voltage harmonics (THD)"]
    M --> Q["Grid cable impedance"]
    M --> R["Select all: Yes"]

Fig 8.42

Smart I-V diagnosis Select item(s) • VIP V-jour • Grid voltage waveform • Grid voltage homogeneity (THV) • Grid color impedance Select of Yes

Fig 8.43

8.2.2 U Disk Monitoring

Refer to 6.3.2 USB to WIFI U disk communicate connection, the local monitoring of U disk can realize the functions of software burning, fault recording, curve analysis and realtime recording. Details are as follows:

1>Firmware Programming

Create the bconfig.txt file under the root of the U disk, write to the following content, then insert the U disk to programming. Note the M3 program needs to be programming at last time.

File Home Share View KINGSTON (L): U root directory Quick access Desktop Downloads Documents Pictures EWSTM8 PROJECT source USER OneDrive BCONFIG.TXT TIAA_57xxxxxx.hex TIAA_xx26xxxxhex TIAA_rxx10xx.hex tiaa-rxxxxx25.bin BCONFIG.txt - 记事本 文件(F) 编辑(E) 格式(O) 查看(V) 帮助(H) update 1. TIAA_57xxxxxx.hex 2. TIAA_xx26xxxxhex 3. TIAA_xxxx10xx.hex 4. tiaa-xxxxxx25.bin F i m e n a m e

Fig 8.44

2>Fault Recording

Create the bconfig.txt file under the root of the U disk, write the following content, then insert the U disk that can be read fault information, then generates a form under the files in the root directory. A total of 60 fault recording information is stored, the latest Numbers is 0.

File Home Share View Manage KINGSTON (I:) U root directory Quick access Desktop Downloads Documents Pictures EWSTM8 PROJECT BCONFIG.TXT BCONFIG.TXT - Notepad File Edit Format View Help down_fault Fig 8.45

3>Curve Analysis

Create the bconfig.txt file under the root of the U disk, write the following content, the insert U disk to record I-V curve, then generates a form under the files in the root directory.

File Home Share View Manage KINGSTON (k): U root directory Quick access Desktop Downloads Documents Pictures EWSTM8 PROJECT BCONFIG.TXT BCONFIG.TXT - Notepad File Edit Format View Help down_curve

Fig 8.46

4>Real Time Recording

Create the bconfig.txt file under the root of the U disk, write the following content, then insert U disk to read real time recording information, then generates a form under the files in the root directory, the form record's waveform is consistent with the ID of the command setting.

File Home Share View Manage KINGSTON (I:) U root directory Quick access Desktop Downloads Documents Pictures EWSTM8 PROJECT source USER BCONFIG.TXT BCONFIG.TXT - Notepad File Edit Format View Help down_wave 1.4 2.5 28075 of ID<1000 3.6 4.7 5.1019 6.1024 28067 of ID<2000 7.1025 8.1026

Fig 8.47

System Maintenance

9

9.1 Routine Maintenance

9.1.1 Cleaning Inverter

Growatt MAX 100-150KTL3-X MV - System Maintenance - 1

- Before any operation, please disconnect the DC switch and AC switch, and wait for at least 5 minutes until internal capacitance discharge completely.

1>Check the ambient temperature and dust of the inverter, clean the inverter when necessary.

2>Observe whether the air outlets is normal, when necessary, clean the air outlets or clean the fan step by step, steps refer to 9.1.2.

9.1.2 Fan Maintenance

Growatt MAX 100-150KTL3-X MV - System Maintenance - 2

- It must be carried out by qualified, trained personnel and comply with all prevailing local code and regulations. - Please disconnect the DC switch and AC switch before any operation, and wait for at least 5 minutes until the internal bus capacitance discharge completely.

Growatt MAX 100-150KTL3-X MV - System Maintenance - 3

- Do not use the air pump cleaning fan, which may cause fan damage.

When the Growatt MAX-X series inverter work in high temperature environment, good ventilation and heat dissipation can effectively reduce the chance of load derating. Inverter equipped with internal cooling fans, when the internal temperature is too high, the fans work in to reduce the internal temperature. When the inverter is derating because of the internal temperature is too high, the following are the possible reasons or solutions.

1) Fan is blocked or the heat sink gathers too much dust, it needs to clean the fan, fan cover or heat sink.

2) Fan is damaged, it need to replace the fan. 3) Poor ventilation of the installation location, it needs to select the appropriate installation location according to the basic installation requirements.

Fan cleaning and replacement procedure;

1>Please ensure that the DC side and AC side of the inverter have been disconnected before cleaning or replacement of the fan.

1) Turn off DC switch.

2) Disconnect DC terminals from inverter(Users need tools to disconnect the DC

connection terminals).

3) Turn off AC switch.

2>Remove the screws on the fan guards with a cross screwdriver. it is shown as below.

Growatt MAX 100-150KTL3-X MV - System Maintenance - 4

natural_image Technical line drawing of an electronic device casing with internal components (no text or symbols)

Fig 9.1 External fan view

Growatt MAX 100-150KTL3-X MV - System Maintenance - 5

natural_image Technical drawing of a mechanical component with circular features and dimension lines (no text or symbols)

Growatt MAX 100-150KTL3-X MV - System Maintenance - 6

natural_image Technical line drawing of a mechanical device with internal components (no text or symbols)

Fig 9.2 Internal Ian view

3>Disconnect the wire connector of the fans with a flat head screw driver and remove the fans from the fan guards, it is shown as below.

Growatt MAX 100-150KTL3-X MV - System Maintenance - 7

Growatt MAX 100-150KTL3-X MV - System Maintenance - 8

Fig 9.3
Growatt MAX 100-150KTL3-X MV - System Maintenance - 9

natural_image Pure electrical circuit lines without any symbols

Fig 9.4 External fan view

Growatt MAX 100-150KTL3-X MV - System Maintenance - 10

natural_image Technical line drawing of a mechanical housing or bracket with mounting holes and a central circular component (no text or symbols)

Fig 9.5 Internal fan view

Notice: MAX-X series inverter has seven fans (internal fan*2Pcs, external fan*5Pcs).

4>Clean fan, fan guards and heat sink or replace fan.

1) Clean the fan and fan guards with air pump, brush or a damp cloth.
2) Remove each fan separately for cleaning if necessary.
3) Remove the fan that need to replace with a cross screwdriver, replace a new fan.
4) Tidy up the wire.

5>Install the fan, fan guard fixed and the inverter again.

9.2 Trouble Shooting

Growatt MAX 100-150KTL3-X MV - Trouble Shooting - 1
DANGER

  • It must be operated by well-trained professional electrical technicians
    and abide by this manual.
  • Normally grounded conductors may be ungrounded and energized
    when a PV isolation low is indicated.
    •Risk of electric shock.

9.2.1 Warning

Warnings identify the current status of the inverter(Max), warnings do not related to a fault and it does not affect the normal running of the inverter. When a warning with a number after it appears in the display, it indicates a warning code and is usually cleared through an orderly shutdown/re-set or a self-corrective action performed by the inverter.

WarningDescriptionSuggestion
Warning 200String Fault1. After shutdown, check the panel is normal.2. Contact Growatt.
Warning 201String abnormal1. After shutdown, check the panel is normal.2. Contact Growatt.
Warning 202DC SPD warning1. After shutdown, check the DC SPD.2. Contact Growatt.
Warning 203PV Circuit short1. Check if the PV circuit is short-circuited.2. Contact Growatt.
Warning 204Dryconnect function abnormal1. After shutdown, check the dry Dryconnect wiring.2. Contact Growatt.
Warning 205PV Boost driver abnormal1. Restart inverter.2. Contact Growatt.
Warning 206AC SPD warning1. After shutdown, check the AC SPD.2. Contact Growatt.
Warning 207USB Over-Current1. unplug the U disk.2. Re-access U disk after shutdown.3. Contact Growatt.
Warning 208DC Fuse Open1. After shutdown, check fuse.2. Contact Growatt.
Warning 209PV Voltage High1. Immediately disconnect the DC switch and check the voltage.2. Contact Growatt.
Warning 210PV Reversed1. Check PV input terminals.2. Contact Growatt.
Warning 300No AC Connection1. Please confirm grid is lost or not.2. Contact Growatt.
warning301AC V Outrange1. Check the AC voltage is in the range of standard voltage in specification.2. Contact Growatt.
Warning 302AC F Outrange1. Check the frequency is in the range of specification or not.2. Contact Growatt.
Warning 310NE abnormal1. Check if the neutral and ground cables are well connected.2. Contact Growatt
Warning 400Fan warning1. After shutdown, Check the fan connection.2. Replace the fan.3. Contact Growatt.
Warning 401Meter abnormal1. Check if the communication between the inverter and the meter is abnormal.2. Contact Growatt.
WarningDescriptionSuggestion
Warning 404EEPROM abnormal1. Restart inverter.2. Contact Growatt.
Warning 405Firmware version abnormal1. Restart inverter.2. Contact Growatt.
Warning 406Boost module error1. Restart inverter.2. Contact Growatt.
Warning 407Over Temperature1. Restart inverter.2. Contact Growatt.
Warning 408NTC broken1. Restart inverter.2. Contact Growatt.
Warning 409Reactive abnormal1. Check if shinemaster is abnormal.2. Contact Growatt.

Notice: MAX series inverter has two external fans and five Internal fan. If the suggestions do not work, please contact to Growatt.

9.2.2 Error

Errors codes identify a possible equipment failure, fault or incorrect inverter setting or configuration, any or all attempts to correct or clear a fault must be performed by qualified personnel.

Typically, the error code can be cleared once the cause or fault is removed. Some of error code as table shows below, may indicate a fatal error and require you to contact the supplier or Growatt for help.

ErrorDescriptionSuggestion
Error 200AFCI Fault1. After shutdown,check the panel terminal.2. Restart inverter.3. Contact Growatt.
Error 201Residual I High1. Restart inverter.2. Contact Growatt.
Error 202PV Voltage High1. Immediately disconnect the DC switch and check the voltage.2. Contact Growatt.
Error 203PV Isolation Low1. After shutdown, check if the panel shell is reliably grounded.2. Contact Growatt.
Error 204PV Reversed1. After shutdown, check PV input terminals.2. Contact Growatt.
Error 300AC V Outrange1. Check grid voltage.2. Contact Growatt.
Error 301AC terminals reversed1. Check AC terminals.2. Contact Growatt.
Error 302No AC Connection1. After shutdown,check AC wiring.2. Contact Growatt.
Error 303NE abnormal1. After shutdown,ensure that the ground wire is reliably connected.2. Contact Growatt.
Error 304AC F Outrange1. Check the frequency is in the range of specification or not.2. Contact Growatt.
Error 400DCI bias abnormal1. Restart inverter.2. Contact Growatt.
Error 401DC Voltage High Fault1. Restart inverter.2. Contact Growatt.
Error 402Output DC current too high1. Restart inverter.2. Contact Growatt.
Error 403Output current unbalance1. Restart inverter.2. Contact Growatt.
Error 404Bus sample fault1. Restart inverter.2. Contact Growatt.
Error 405Relay fault1. Restart inverter.2. Contact Growatt.
Error 406Init model fault1. Restart inverter.2. Contact Growatt.
Error 407AutoTest failure1. Restart inverter.2. Contact Growatt.
ErrorDescriptionSuggestion
Error 408NTC Temperature too high1. Restart inverter.2. Contact Growatt.
Error 409Bus voltage abnormal1. Restart inverter.2. Contact Growatt.
Error 411Communication fault1. Restart inverter.2. Contact Growatt.
Error 412Temperature sensor abnormal1. Restart inverter.2. Contact Growatt.
Error 413IGBT drive fault1. Restart inverter.2. Contact Growatt.
Error 414EEPROM fault1. Check if shinemaster is abnormal.2. Contact Growatt.
Error 415Internal power test fail1. Restart inverter.2. Contact Growatt.
Error 416Over current protected1. Restart inverter.2. Contact Growatt.
Error 417System protocol abnormal1. Restart inverter.2. Contact Growatt.
Error 418firmware version abnormal1. Restart inverter.2. Contact Growatt.
Error 420GFCI Module damage1. Restart inverter.2. Contact Growatt.
Error 421CPLD abnormal1. Restart inverter.2. Contact Growatt.
Error 422Sampling is inconsistent1. Restart inverter.2. Contact Growatt.
Error 425AFCI self-test fault1. Restart inverter.2. Contact Growatt.
Error 426PV current abnormal1. Restart inverter.2. Contact Growatt.
Error 427AC current abnormal1. Restart inverter.2. Contact Growatt.
Error 428Boost Short Out1. Contact Growatt.
Error 429Bus voltage softstart fail1. Restart inverter.2. Contact Growatt.

10 Specification

Model SpecificationsMAX 100KTL3-X LVMAX 110KTL3-X LVMAX 120KTL3-X LVMAX 125KTL3-X LV
Input Data(DC)
Max.recommended PV power(for module STC)150kW165kW180kW187.5kW
Max. DC voltage1100V
Start voltage195V
Nominal voltage600V
MPP voltage range180V-1000V
No. of MPP trackers10
No. of PV strings per MPP trackers2
Max. input current per MPP trackers32A
Max. short-circuit current per MPP trackers40A
DC overvoltage categoryCategory II
Output Data(AC)
AC nominal power100kW110kW120kW125kW
Max. AC apparent power110kVA121kVA132kVA137.5kVA
Nominal AC voltage/range230V/400V340-440VAC
AC grid frequency/range50/60Hz45-55Hz/55-65Hz
Max. output current167.1A@380V158.8A@400V183.8A@380V174.6A@400V200.5A@380V190.5A@400V208.9A@380V198.5A@400V
Power factor(@nominal)>0.99
Max. inrush current/duration20KA/tr:8us,tf:20us
Max. output facult current/duration400A/30us
Adjustable power factor0.8leading ...0.8lagging
THDi<3%
AC grid connection type3W:N:PE
AC overvoltage categoryCategory III
efficiency
Max. efficiency98.8%
Euro-eta98.4%98.5%98.5%98.5%
Protection devices
DC reverse-polarity protectionYes
DC switchYes
DC Surge protectionType II
Insulation resistance monitoringYes
AC surge protectionYes
Grid monitoringYes
Anti-islanding protectionYes
Residual-current monitoring unitYes
String monitoringYes
Anti-PID functionOptional
AFCI protectionOptional
General data
Dimensions (W /H /D) in mm970*640*345mm
Max. innush current/duration20KA/tr:8us,tf:20us
Weight84kg
Operating temperature range-30°C- +60°C
Altitude4000m
Internal consumption at<1Wi(Note1)
TopologyTransformerless
CoolingSmart air cooling
Protection degreeIP66
Relative humidity0~100%
DC connectionH4/MC4(Optional)
AC connectionOT/DT terminal
Interfaces
DisplayLED/WIFI+APP
RS485/USBYes
PLC/GPRS/4GOptional
Warranty: 5 /10 yearsOptional
Certificates and approvals
Grid regulationAS/NZS 4777.2,CEI0-21,CEI0-16,VDE-AR-N4105,DINVDEV0126-1-1,UTE C15-712-1,EN 50438,IEC 60068,IEC 61683,IEC 62116,IEC 61727,MEA,PEA,DRRG/DEWA:2016,BDEW,G59/3
EMCEN61000-6-2,EN61000-6-4
SafetyIEC/EN62109-1,IEC/EN62109-2
Note1: If with AC power supply function, self-consumption at night is less than 15W.
Model SpecificationsMAX 133KTL3-X LVMAX 125KTL3-X MVMAX 136KTL3-X MVMAX 150KTL3-X MV
Input Data(DC)
Max.recommended PV power(for module STC)199.5kW187.5kW204kW225kW
Max. DC voltage1100V
Start voltage195V
Nominal voltage600V720V720V720V
MPP voltage range180V-1000V
No. of MPP trackers10
No. of PV strings per MPP trackers2
Max. input current per MPP trackers32A
Max. short-circuit current per MPP trackers40A
DC overvoltage categoryCategory II
Output Data(AC)
AC nominal power133kW125kW136kW150kW
Max. AC apparent power146.3kVA137.5kVA149.6kVA165kVA
Nominal AC voltage/range230V/400V340-440VAC277V/480V408-528VAC277V/480V408-528VAC277V/480V408-528VAC
AC grid frequency/range50/60Hz45-55Hz/55-65Hz
Max. output current222.3A@380V211.2A@400V165.4A179.9A198.5A
Power factor(@nominal)>0.99
Max. innrush current/duration20KA/tr:8us,ff:20us
Max. output facult current/duration400A/30us
Adjustable power factor0.8leading ...0.8lagging
THD<3%
AC grid connection type3W/N:PE3W+PE3W+PE3W+PE
AC overvoltage categoryCategory III
efficiency
Max. efficiency98.8%99%99%99%
Euro-eta98.5%
Protection devices
DC reverse-polarity protectionYes
DC switchYes
DC Surge protectionType II
Insulation resistance monitoringYes
AC surge protectionYes
Grid monitoringYes
Anti-islanding protectionYes
Residual-current monitoring unitYes
String monitoringYes
Anti-PID functionOptional
AFCI protectionOptional
General data
Dimensions (W /H / D) in mm970*640*345mm
Max, inrush current/duration20KA/tr:8us,tf:20us
Weight84kg
Operating temperature range-30°C- +60°C
Altitude4000m
Internal consumption at<1W(Note1)
TopologyTransformerless
CoolingSmart air cooling
Protection degreeIP66
Relative humidity0- 100%
DC connectionH4/MC4(Optional)
AC connectionOT/DT terminal
Interfaces
DisplayLED/WIFI APP
RS485/USBYes
PLC/GPRS/4GOptional
Warranty: 5 /10 yearsOptional
Certificates and approvals
Grid regulationAS/NZ54777.2,CEI0-21,CEI0-16,VDE-AR-N4105,DINVDEV0126-1-1,UTE C 15-712-1,EN 50438,IEC 60068,IEC 61683,IEC 62116,IEC 61727,MEA,PEA,DRRG/DEWA:2016,BDEW,G59/3
EMCEN61000-6-2,EN61000-6-4
SafetyIEC/EN62109-1,IEC/EN62109-2
Note1: If with AC power supply function, self-consumption at night is less than 15W.

11 Decommissioning

If the inverter does not operate in the future, it needs to be properly disposed. The steps are as follows:

1>Disconnect the external AC short circuit and prevent reconnection due to misoperation.

2>Turn the DC switch to "OFF" position.

3>Wait at least 5 minutes until the internal capacitor discharge is completed.

4>Disconnect the AC connector.

5>Disconnect DC connector.

6>Remove the inverter from the wall.

7>Disposing of the inverter.

11.1 Disposing Of The MAX-X Series Inverter

Growatt MAX 100-150KTL3-X MV - Disposing Of The MAX-X Series Inverter - 1

Do not dispose of MAX series inverter together with household waste. Please accordance with the disposal regulations for electronic waste which apply at the installation site at that time. Ensure that the old unit and, where applicable, any accessories are disposed of in a proper manner.

12 Quality assurance

Please refer to related file.

Contact 13

If you have technical problems concerning our products, contact your installer or Growatt, please provide information below for better support.

1>Inverter type

2>Serial number of inverter

3>Error code of inverter

4>LED status of inverter

5>DC input voltage of inverter (Modules information)

6>Inverter communication method

Shenzhen Growatt New Energy Co., Ltd

4-13/F, Building A, Sino-German(Europe) Industrial Park, Hangcheng Ave, Bao'an District, Shenzhen, China

T: +86 0755 2747 1942

E: service@ginverter.com

W: www.ginverter.com

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Growatt

Model : MAX 100-150KTL3-X MV

Category : Unknown