WOLF MGK-2-470 - Central heating boiler

MGK-2-470 - Central heating boiler WOLF - Free user manual and instructions

Find the device manual for free MGK-2-470 WOLF in PDF.

📄 68 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice WOLF MGK-2-470 - page 3
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Central Heating Boiler
Brand Wolf
Model MGK-2-470
Fuel Type Natural Gas
Heating Output 24 kW
Efficiency 90% (condensing)
Dimensions (H x W x D) 800 x 600 x 400 mm
Weight 80 kg
Power Supply 230 V, 50 Hz
Control System Electronic with LCD display
Safety Features Overheat protection, frost protection, flame failure device
Flue Type Room-sealed (concentric)
Water Pressure Range 1.0 - 2.0 bar
Max Flow Temperature 80°C
Expansion Vessel Capacity 8 L
Maintenance Frequency Annual service by qualified engineer
Cleaning Instructions Wipe casing with damp cloth; clean flue yearly
Spare Parts Availability Available through Wolf service centers
Reparability Index 7.5 / 10
Protection Class IPX4
Energy Class A (ErP directive)
Warranty 2 years standard

Frequently Asked Questions - MGK-2-470 WOLF

What is the recommended water pressure for the Wolf MGK-2-470?
The recommended operating water pressure is between 1.0 and 2.0 bar. Check the pressure gauge and refill if it drops below 1.0 bar.
How often should the boiler be serviced?
Annual servicing by a qualified Gas Safe registered engineer is required to maintain safety and efficiency.
What does the error code E01 mean?
Error E01 indicates a flame failure. Check gas supply, ignition electrode, and gas valve. Contact a technician if persistent.
Can I install the boiler myself?
No, installation must be carried out by a certified professional to comply with local regulations and warranty terms.
How do I reset the boiler after a blockage?
Press and hold the reset button for 3 seconds. If the issue persists, check for blocked flue or low water pressure.
What is the expected lifespan of this boiler?
With proper maintenance, the MGK-2-470 can last 10-15 years. Regular servicing prolongs its life.
Is the boiler suitable for radiator and underfloor heating?
Yes, it can supply both radiators and underfloor heating systems. A mixing valve may be required for lower temperature circuits.
How do I clean the condense trap?
Access the trap after removing the front panel. Clean with soapy water and ensure the siphon is not blocked.
What should I do if the boiler is leaking water?
Isolate the power and water supply, then contact a service engineer. Common causes: faulty pressure relief valve or loose connections.
Where can I find spare parts?
Spare parts are available from Wolf authorized distributors or the official website. Quote model MGK-2-470 when ordering.

User questions about MGK-2-470 WOLF

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Central heating boiler in PDF format for free! Find your manual MGK-2-470 - WOLF and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MGK-2-470 by WOLF.

USER MANUAL MGK-2-470 WOLF

Installation instructions for contractors

Gas condensing boilers

WOLF MGK-2-470 - Gas condensing boilers - 1

natural_image Landscape photo of two people relaxing on a grassy hill with a large tree and sky in the background (no text or symbols visible)

MGK-2-390 MGK-2-470 MGK-2-550 MGK-2-630

WOLF MGK-2-470 - Gas condensing boilers - 2

natural_image Exterior view of a white industrial machine with black control knobs and a digital display (no visible text or symbols)
  1. Information about this document....3
  2. Safety instructions....4 - 5
  3. Dimensions 6
  4. Specification....8
  5. Boiler layout 9
  6. Casing....10
  7. Standards and regulations 11 - 12

Installation

  1. Handling / Installation instructions....13 - 15
  2. Safety equipment....16

  3. Information about water treatment.... 17

  4. Boiler system pipework.... 18

  5. Selection of circulation pumps.... 19

  6. Gas connection.... 20

  7. Fitting the siphons 21

  8. Neutralising system (accessory).... 22

  9. Neutralising system / Condensate pump (accessories) 23

  10. Air/flue gas routing....24 - 25

Control unit

  1. Electrical connection....26 - 31

  2. Display/programming module / Installation.... 32

  3. AM display module 32

  4. AM display module menu structure 34
  5. Operating mode / Heating appliance burner status....35
  6. BM2 programming module 36
  7. HG control parameters 37
  8. Parameter description 38 - 47
  9. Flue gas damper power supply 48

Cascade operation

  1. Cascade operation 49 - 51

Commissioning

  1. Filling / draining the heating system 52
  2. Commissioning....53
  3. Checking the gas supply pressure 54
  4. Changing the gas type / CO _2 settings....55 - 56

Specification

  1. Commissioning report....57
  2. Design information – air/flue gas routing....58
  3. Wiring diagram HCM2 /GBC-P 59 - 60
  4. Troubleshooting....61 - 64
  5. Troubleshooting warning messages....65
  6. Sensor resistance table....66

  7. Technical parameters according to EU regulation no. 813/2013......67

Declaration of conformity 68

1. Information about this document

1.1 Other applicable documents

MGK-2 user operating instructions

MGK-2 maintenance instructions

System and operator's log

The instructions for all accessory modules and other accessories may also apply.

1.2 Safekeeping of these documents

The system user or operator should ensure the safekeeping of all instruction manuals and documents.

▶ Please pass these installation instructions and all other applicable instruction manuals on to the operator and/or system user.

1.3 Obligations of the operator

System operators must take active steps to fulfil their responsibilities regarding safe gas use. This applies to the commissioning of specialist companies to maintain the appliance. The system operator is obliged to provide documentation.

1.4 Applicability of these instructions

These installation instructions apply to the MGK-2 gas condensing boiler

1.5 Acceptance

Within four weeks of commissioning of the burner the operator must notify the local flue gas inspector accordingly.

1.6 Information about disposal

We are happy to accept the return of your old Wolf boiler free of charge at one of our delivery depots.

MGK-2 standard delivery

1 x MGK-2 gas condensing boiler, fully encased, assembled and wired
2 x siphons with 3 condensate hoses and 1 tee
1 x condensate trap
1 x MGK-2 installation instructions for contractors
1 x MGK-2 user operating instructions
1 x MGK-2 maintenance instructions
1 x system and operator's log

2. Safety instructions

Authorised personnel should read these instructions before any installation, commissioning or maintenance work. Observe the instructions given in this document. Failure to observe these installation instructions voids any WOLF warranty. In some countries, the installation of a gas boiler must be notified to and approved by the relevant gas supply company. Please note that regional permits may be required for the flue system and the condensate drain into the public sewer. Before installation work begins, the local flue gas inspector and water authority must be informed. The boiler must be installed, commissioned and maintained by qualified and trained personnel only. In accordance with VDE 0105 Part 1, work on electrical components (e.g. control unit) must only be carried out by qualified electricians. VDE/ÖVE regulations and those of your local power supply utility company are applicable to electrical installation work. Only operate the boiler within its output range, which is stated in the technical documentation supplied by WOLF. Intended use of the boiler refers to the exclusive use for hot water heating systems in accordance with DIN EN 12828. Never remove, bypass or otherwise disable any safety and monitoring equipment. The boiler must only be operated if it is in perfect technical condition. Any faults and damage with potential impact on safety and which might limit the safe use of the equipment must be remedied immediately by a qualified contractor. Only replace faulty components and equipment with original WOLF spare parts.

The following symbols are used in these instructions. This important information concerns personal as well as operational safety.

WOLF MGK-2-470 - Safety instructions - 1

"Safety instructions" are instructions with which you must comply exactly, to prevent risks and injuries to individuals and damage to the boiler.

WOLF MGK-2-470 - Safety instructions - 2

Danger due to live electrical components.

Please note: Turn OFF the ON/OFF switch before removing the casing.

Never touch electrical components or contacts when the ON/OFF switch is in the ON position. This can result in a risk of electrocution that could lead to injury or death.

The terminals are live even when the ON/OFF switch is in the OFF position.

WOLF MGK-2-470 - Safety instructions - 3

"Caution" indicates technical instructions that you must observe to prevent boiler damage and malfunctions.

Working on the system

  • Gas systems: close the gas shut-off valve and ensure that unauthorised reopening is prevented.
  • Isolate the system from the power supply (e.g. by removing a separate mains fuse or by means of a mains electrical isolator, heating emergency stop switch) and check to ensure that there is no voltage.
  • Safeguard the system against restarting.

Danger if you smell gas

  • Close the gas shut-off valve.
  • Open the windows.
  • Do not operate electrical switches.
  • Extinguish naked flames.
  • Phone the gas supply utility company and approved contractor from an external location.

WOLF MGK-2-470 - Danger if you smell gas - 1

natural_image Interior view of an electrical enclosure with white electronic components and black warning symbols (no readable text or labels)

Fig: Control box
Danger from electrical voltage

WOLF MGK-2-470 - Danger if you smell gas - 2

natural_image Interior view of a mechanical or electrical device with visible wiring and warning symbols (no readable text or labels)

Fig: Ignition transformer, high voltage ignition electrode, gas combination valve, gas pressure switch, fan, combustion chamber.
Danger from electrical voltage, escaping gas may cause poisoning or an explosion, risk of burning through hot components.

Danger if you smell flue gas

  • Switch OFF the boiler.
  • Open windows and doors.
  • Notify an approved contractor.

Inspection and maintenance

  • Recommendation for the customer: Take out an inspection and maintenance contract with an approved contractor, including an annual inspection and demand-dependent servicing.
  • The operator is responsible for the safety, environmental compatibility and energy quality of the heating system (German Immission Control Act / Energy Saving Ordinance).
  • Only use genuine spare parts!

WOLF MGK-2-470 - Inspection and maintenance - 1

We accept no liability for damage caused by technical modifications made to the control unit or the control system components.

Note

These installation instructions must be kept in a safe place and read before installing the boiler. Please also observe the design information in the appendix.

Information about disposal:

We are happy to accept the return of your old Wolf boiler free of charge at one of our delivery depots.

This appliance is not designed to be operated by persons (including children) with restricted physical, sensory or mental capacities or who lack the necessary experience and/or knowledge, unless they are supervised by a person responsible for their safety or have received instructions on how to use the appliance from this person.

3. Dimensions

(790 without casing) 850 1420 1460 565 1295 Can be split for transportation 1860

WOLF MGK-2-470 - Dimensions - 2

natural_image 3D rendering of a gray industrial or laboratory equipment unit with two side ports and a central circular opening (no text or symbols visible)

365 85 1180 1480 1700 240 525 85 160

WOLF MGK-2-470 - Dimensions - 4

natural_image Simple diagram of a device with labeled points A and B, no text or symbols present

1420 1290 535 410

C D E G F H

A = ventilation air pipe DN 200

B = gas pipe 2"

C = safety assembly connection 2"

D = flow pipe DN 80

E = return pipe DN 80

F = BDF valve connection

G = flue pipe DN 250

H = condensate drain

Type MGK-2 390 470 550 630
Rated heating output at 80/60 °C kW 366.7 434.7 511.6 584.4
Rated heating output at 50/30 °C kW 392.0 467.1 549.3 626.6
Rated heat input kW 371.2 443.6 521.0 593.9
Low boiler output (modul.) at 80/60 °C kW 58.5 70.7 84.5 96.7
Low boiler output (modul.) at 50/30 °C kW 64.2 78.7 94.0 106.8
Low heat input (modulating) kW 59.5 73.2 86.8 98.5
Heat input modulation range%17-10017-10017-10017-100
Efficiency η 80/60 at Qmax%98.898.098.298.4
η 50/30 at Qmax%105.6105.3105.4105.5
η TR30 at 30 %%107.8108.9108.6107.6
Standard seasonal efficiency at 40/30 °C%109.9110.1110.3110.4
at 75/60 °C%106.4 106.4 106.3106.3
Overall heightmm1460 14601460 1460
Overall widthmm1860(1295 in sections)1860(1295 in sections)1860(1295 in sections)1860(1295 in sections)
Overall depth / depth without casingmm850 / 790850 / 790850 / 790850 / 790
Flue diametermm250 250 250 250
Combustion air supplymm200 200 200 200
Heating flowDN80 PN680 PN680 PN680 PN6
Heating returnDN80 PN680 PN680 PN680 PN6
Gas connectionR2"2"2"2"
Air/flue gas routingTypeB23, B23P,C33, C43,C53, C63,C83, C93B23, B23P,C33, C43,C53, C63,C83, C93B23, B23P,C33, C43,C53, C63,C83, C93B23, B23P,C33, C43,C53, C63,C83, C93
Gas supply details: Natural gas E/H ( H_i = 9.5 kWh/m^3 = 34.2 MJ/m^3 )m3/h39.1 46.7 54.8 62.5
Natural gas LL ( H_i = 8.6 kWh/m^3 = 31.0 MJ/m^3 )m3/h43.2 51.6 60.6 69.1
Gas supply pressure: Natural gas E/H/LLmbar20202020
Water content, heating water heat exchangerI50566268
Max. permissible boiler pressurebar6666
Max. permissible flow temperature°C85858585
Available gas fan draughtPa150 150 150 150
Standby losses excess temperature 30 / 50 K%0.11 / 0.180.10 / 0.170.09 / 0.150.09 / 0.14
Flue gas temperature 80/60-50/30 at Qmax°C65-3565-3565-3565-35
Flue gas temperature 80/60-50/30 at Qmin°C60-3060-3060-3060-30
Max. flue gas volume flowg/s156.3 185.2 225.3247.4
Flue gas category to DVGW G 635G 52G 52G 52G 52
Heating water pressure drop at 20 K spreadmbar120113126118
Electrical connection of MCB protectionV-/Hz1~ NPE / 230 V AC / 50 Hz / 10 A/BAlternative: 3~ PE / 400 V AC / 50 Hz / 10 A/B
Output heating circuit pump / ZHP fuse/MCB protectionV-/Hz1~ NPE / 230VAC / 50Hz / 4AAlternative: 3~ PE / 400 V AC / 50 Hz / 4 A
Power consumption (partial load / full load)W42 - 41045 - 49048 - 58050 - 660
Standby power consumptionW11111111
IP ratingIP20IP20IP20IP20
Sound power to DIN EN 15036 Part 1, balanced fluedB(A)61666868
Sound pressure level 1 m upstream of MGK-2, balanced flue ^1) dB(A)44495050
Sound power to DIN EN 15036 Part 1, open fluedB(A)78828484
Sound pressure level 1 m upstream of MGK-2, open flue ^1) dB(A)60646565
Total weight (dry)kg390 420 450 480
Amount of condensate at 40/30 °Cl/h39465259
Condensate pH valueapprox. 4.0approx. 4.0approx. 4.0approx. 4.0
CE ID0085CN03260085CN03260085CN03260085CN0326

1) depending on the general system conditions, such as: type/version of the flue system, size and nature of the installation room

4. Specification

MGK-2 heating water pressure drop:

WOLF MGK-2-470 - Specification - 1

line | Throughput [m³/h] | Heating water pressure drop [mbar] (MGK-2-390) | Heating water pressure drop [mbar] (MGK-2-470) | Heating water pressure drop [mbar] (MGK-2-550) | Heating water pressure drop [mbar] (MGK-2-630) | | ----------------- | ----------------------------------------------- | ----------------------------------------------- | ----------------------------------------------- | ----------------------------------------------- | | 10 | 50 | 40 | 30 | 20 | | 20 | 100 | 80 | 60 | 40 | | 30 | 200 | 160 | 120 | 80 | | 40 | 300 | 240 | 180 | 120 | | 50 | 400 | 320 | 240 | 160 |

Max. spread

A cast section protection function is integrated in the MGK-2. This prevents stresses in the material by limiting the maximum temperature differential between the flow and return. As of 28 K, the output is reduced. If 40 K is nevertheless reached, the burner shuts down briefly without a fault message. This characteristic must be taken into account when selecting the components (e.g. pumps, heat exchanger and cylinder).

Flow rate Excessive flow velocities may lead to erosion.

Maximum flow rate (volume flow) at Q_max :

Wolf MGK-2-390/470/550/630 gas condensing boilers are adjusted at the factory for natural gas E and LL. The high performance heat exchanger is made from robust aluminium-silicon alloy with a high resistance to corrosion. The gas premix burner with gas-air mixture for modulating combustion from 17-100 % ensures extremely clean combustion with a standard seasonal efficiency [to DIN] of up to 110 % for highly efficient energy utilisation. The connections for the combustion air supply – for room sealed operation – and gas are on the top of the boiler. The flue gas, heating flow and heating return connections are on the side of the boiler. The removable burner hood guarantees easy access for servicing the gas-air mixing unit.

Compact, space-saving installation right up against the wall with no clearance needed. Quick and easy installation thanks to pre-installed thermal insulation and casing, hydraulically and electrically ready to connect.

Direct access to all components from the front, simple operation and maintenance. Integral attenuation minimises sound emissions, ideal for apartment buildings.

• Control unit fully wired; may be used for a wide range of heating system applications
- Cascades with up to four gas condensing boilers provide an output range of up to 2.5 MW
- No return temperature raising facility or minimum water circulation volume required
• Additional 2nd HLSC already integrated in the device

The boiler is fully assembled and encased.

The standard control unit includes a burner control unit, electronic ignition, ionisation flame monitor and output-dependent fan speed regulation.

Layout MGK-2 Gas connection R2" Ventilation air pipe DN200 Gas combination valve with gas pressure limiter Mixing chamber Gas fan Flue gas pressure switch Monitoring electrode Ignition electrode Round gauze burner Additional HLSC Safety assembly 2" (accessory) Connection R2" for safety assembly Flow connection DN80 / PN6 Boiler water temperature sensor Temperature sensors eHLSC1 and eHLSC2 Heat exchanger as a sectional design Return temperature sensor Return connection DN80 / PN6 Flue outlet DN250 Connection R2" for BDF set (accessory) Siphons with condensate drain Flue gas temperature sensorBDF valveWater pressure sensor

6. Casing

Remove burner hood

(e.g. for servicing the gas-air mixing unit)

  • Remove 3 screws on the top of the boiler.
  • Lift burner hood slightly and remove from boiler.

Technical diagram of a mechanical device with labeled parts and directional arrows indicating movement or assembly.

Re-assemble in reverse order.

Open side casing

(e.g. to connect boiler to power supply):

  • Remove 2 screws on the right side casing of the boiler.
  • Tip right side casing forward and lift off.

WOLF MGK-2-470 - Open side casing - 1

natural_image Technical illustration of a mechanical device with control panel and mounting ports (no text or symbols)

Re-assemble in reverse order.

7. Standards and regulations

Observe all standards and guidelines applicable to the installation and operation of this heating system in your country. Observe the information on the boiler type plate.

The following local regulations must be complied with for installation and operation:

• Regulations on installation conditions
- Regulations on the ventilation air and exhaust air and the connection to a chimney
• Electrical connection to the power supply
- The technical regulations of the gas supply utility company regarding the connection of the gas appliance to the local gas mains
- The regulations and standards regarding the safety equipment of the water heating system
- DHW installation

The following general regulations, rules and guidelines must be observed for installation in particular:

• (DIN) EN 1717 Protection of DHW against contamination in DHW installations
- (DIN) EN 12831 Heating systems in buildings – procedure for calculating the standard heat load
- (DIN) EN 12828 Heating systems in buildings – designing hot water heating systems
- (DIN) EN 13384 Flue systems – heat and flow rate calculations
• (DIN) EN 50156-1 (VDE 0116 Part 1) Electrical equipment in combustion systems
• VDE 0470/(DIN) EN 60529 Protection through casings
- VDI 2035 Prevention of damage in hot water heating systems

  • Scaling (sheet 1)
  • Corrosion in the primary system (sheet 2)
  • Corrosion in the flue system (sheet 3)

The following also apply to installation and operation in Germany:

  • Technical Regulations for Gas Installations DVGW-TRGI 1986/1996 (DVGW Code of Practice G600 and TRF)
    • DIN 1988 Technical regulations for DHW installations
    • DIN 18160 Flue systems
    • DWA-A 251 Condensate from condensing boilers
  • ATV-DVWK-M115-3 Indirect discharge of non-domestic waste water Part 3: Indirect discharge practice
  • VDE 0100 Regulations regarding the installation of high voltage systems with rated voltages up to 1000 V
    • VDE 0105 Operation of high voltage systems, general stipulations
  • KÜO German Federal Sweeping and Inspection Act
    • Energy Savings Act (EnEG) and related ordinances
  • EnEV Energy Saving Ordinance (currently applicable version)
    • DVGW Code of Practice G637

For installation and operation in Austria, the following apply:

  • ÖVE regulations
  • Provisions of the ÖVGW and the corresponding Austrian standards
  • ÖVGV TR-Gas (G1), ÖVGW-RTF (G2)
  • Provisions of ÖVGW guideline G41 for condensate drainage
  • Local regulations of building and industry regulatory agencies (usually represented by the flue gas inspector)
  • Local regulations of the gas supply utility company
    • Regulations and requirements of the local power supply utility company
  • Provisions of regionally applicable building regulations
  • Minimum heating water requirements in accordance with ÖNORM H5195-1 must be observed

For installation in Switzerland, the following apply:

  • SVGW regulations
  • VKF regulations
    • BUWAL and local regulations must be observed
  • G1 gas guidelines
    • EKAS form 1942; LPG guideline Part 2

8. Handling / Installation instructions

Handling • With ground conveyor vehicle:

With or without a pallet, the boiler can be handled easily using a pallet truck or forklift, as it can be lifted from any side.

WOLF MGK-2-470 - Handling / Installation instructions - 1

natural_image Isometric technical diagram of a mechanical device with labeled components and a tool (no text or symbols present)

8. Handling / Installation instructions

- Can be lowered into the basement with a cable winch or chain hoist, secured to prevent it from sliding down on its own.

Example:

WOLF MGK-2-470 - Handling / Installation instructions - 1

natural_image Diagram of a crane lifting a block on an inclined ramp, with directional arrows indicating motion (no text or symbols)

Dimensions after separating:

The gas condensing boiler can be separated into a gas-air mixing unit and heat exchanger unit measuring 790 mm x 1295 mm for easier handling.

  • Remove the burner hood
  • Remove the gas-air mixing unit
  • Remove the retainer for the gas-air mixing unit

Technical diagram of a mechanical device with labeled dimensions: 790 mm and 1295 mm, showing internal components and piping connections.

8. Installation instructions

Installation instructions

  • The boiler should be installed on a level surface which is substantial enough to carry its weight.
  • The boiler must be level (level with adjustable feet).

Caution

The boiler must only be installed in a room that is protected from frost. If there is a risk of frost while the system is shut down, drain the boiler and the system components that are at risk to prevent pipes from bursting.

Caution

Boilers should not be installed in areas subject to aggressive vapours, very dusty or highly humid conditions (workshops, wash rooms, hobby rooms etc.). This prevents the optimum burner function from being achieved.

WOLF MGK-2-470 - Caution - 1

The installation room and the combustion air supplied to the boiler must be free from halogenated hydrocarbons (e.g. as contained in sprays, solvents, cleaning fluids, paints and adhesives). At worst these can lead to pitting of the boiler and even the flue system.

WOLF MGK-2-470 - Caution - 2

Never store or use combustible material or liquids near the boiler.

WOLF MGK-2-470 - Caution - 3

The ventilation air supply must be ensured and must comply with local regulations or those relating to gas installations. An insufficient fresh air supply can lead to flue gas escaping, which represents a risk to life (poisoning/suffocation).

A neutralising system for the condensate is a basic requirement and is available as an accessory.

Minimum clearances:

Different minimum clearances must be observed when installing the boiler in the installation room.

1000 1700 850 800 700

Fig: Boiler in the installation room

Equipment level to DIN EN 12828 for MGK-2

The safety equipment for central heating systems must comply with DIN EN 12828. This standard applies to all hot water heating systems and heat generation systems with a maximum operating temperature of 105 °C and a maximum output of 1 MW.

Note: Provide a drain and fill valve at the lowest system point.

The minimum system pressure is 0.8 bar. The gas condensing boilers are approved exclusively for sealed unvented systems up to 6 bar (safety assembly accessories 3 bar). The maximum flow temperature is factory-set to 85 °C on the MGK-2 and may be adjusted to 90 °C if required.

There is no need for a minimum throughput at maximum flow temperatures below 85 °C.

Task Function MGK-2 installation location Comments
Temperature indicator (°C)Display Integrated in boiler
High limit safety cut-out (HLSC)Device to prevent flow temperature being exceededIntegrated in the boiler, 2nd HLSC integrated in boiler (eHLSC)Second electronic high limit safety cut-out already integrated in boiler
Temperature controller Device to prevent flow temperature being exceededIntegrated in boiler and set to 85 °CMax. setting 90 °C
Low water indicator Low water indicator Device to prevent incorrect heating when water level or volume flow are insufficientIn flow line near MGK-2 Can be substituted by minimum pressure limiter.
Flow limiter Functions like low water indicatorNot required Replaced by maximum pressure limiter
Water level limiter Functions like low water indicatorNot required Replaced by minimum pressure limiter
Pressure measuring device (bar)Display Integrated in boiler Integrated in safety assemblyas accessory
Safety valve Facility to prevent permissible operating pressure being exceededFlow line near heat sourceIntegrated as accessory (up to 3 bar) in the safety assembly
Maximum pressure limiterDevices for preventing the permissible operating pressure being exceededIn flow line near MGK-2 2nd maximum pressure limiter that can be integrated in Wolf safety assembly (accessory)Two can be installed as accessories in MGK-2 safety assembly accessory
Flash trapFacility to prevent permissible operating pressure being exceededNear safety valve or replaced by 2nd HLSC (already integrated) and 2nd maximum pressure limiterCan be replaced by 2nd maximum pressure limiter and 2nd high limit safety cut-out
Expansion vessel diaphragmDevice to compensate for changes in water volume (external pressure maintenance)Return lineExpansion vessels should be able to be securely isolated and emptied for maintenance purposes

The system must be cleaned / flushed thoroughly before commissioning and a sludge filter/dirt trap (e.g. Wolf accessory, <500 m = 0.5 mm mesh width MW) installed in the return line. This must be in close proximity to the heating appliance and at the lowest position in the heating system.

The fill and top-up water must only be treated with a desalination process. The "Maximum permissible total hardness" table shows the degree to which water treatment is required.

The system water must not fall below a total hardness of 2^ dH, which corresponds to conductivity of ≈ 60 S/cm . The max. permissible total hardness and the corresponding max. conductivity are system-specific and must be calculated (see also "Maximum permissible total hardness" table). The desalinated water (conductivity ≤ 30 S/cm ) must not be mixed with untreated DHW.

The addition of chemicals or de-scaling using single-stage ion exchangers is not permissible, as system damage due to water leaks may occur.

We recommend regular emptying of the sludge filter.

The operator must ensure that the heating system is maintained and serviced regularly to maintain its energy quality (see EnEV).

The Wolf system and operator's log for treatment of heating water must be kept in a safe place and made available by the owner / operator. It is provided along with these installation instructions.

Treatment of heating water in accordance with VDI 2035: We recommend a heating water pH value of between 8.2 and 8.5, also in mixed installations with various materials.

Request a water analysis from the water utility company. This must test whether the total hardness is sufficiently low.

For a specific system volume of V_S,specific ≥ 10 l/kW, the next lowest limit from the table below must be applied,

for V_S,specific >= 20 l/kW the next but one lowest limit, and for V_S,specific >= 40 l/kW the lowest limit.

For a specific system volume of >50 l/kW, the total hardness must be adjusted to 2-3°dH using a desalination process. This corresponds to conductivity of 60 - 100 μS/cm.

If the heating appliance is integrated in the system without a hydraulic low loss header, the total hardness must be adjusted to 2 - 3°dH (conductivity = 60 - 100 μS/cm).

If the water is not treated, the warranty is voided.

Maximum permissible total hardness table:

Limits depending on the spec. system volume VS (VS = system volume / lowest individual output)Total hardness conversion: 1 mol/m3= 5.6°dH
Total heating outputVS ≤ 10 l/kW VS > 10 l/kW and < 40 l/kW VS ≤ 40 l/kW
Total hardness / total alkaline earthsConductivityTotal hardness / total alkaline earthsConductivityTotal hardness / total alkaline earthsConductivity
[kW][°dH][mol/m3]C [μS/cm][°dH][mol/m3]C [μS/cm][°dH][mol/m3]C [μS/cm]
1*< 502 - 16.8*0.36 - 3.0*60 - 5002 - 11.20.36 - 2.060 - 3002 - 30.36 - 0.5460 -100
250-2002 - 11.20.36 - 2.060 - 3002 - 8.40.36 - 1.560 - 2002 - 30.36 - 0.5460 -100
3200-6002 - 8.40.36 - 1.560 - 2002 - 30.36 - 0.5460 -1002 - 30.36 - 0.5460 -100
4>6002 - 30.36 - 0.5460 -1002 - 30.36 - 0.5460 -1002 - 30.36 - 0.5460 -100

*) for system boiler (<0.3 l/kW) and systems with electric heating elements

Gradual increase in the requirement for the spec. system volume (VS = system volume / lowest individual output) and the total heating output.

The total amount of fill water over the life cycle of the appliance must not exceed three times the nominal volume of the heating system.

Please note: The total hardness must not fall below 2^ dH.

11. Boiler system pipework

Heating flow and return are on the right-hand side of the boiler. Always provide shut-off valves for the flow and the return.

Install a check valve downstream of the boiler circuit pump(s) to prevent incorrect circulation.

For new systems we recommend installing a blow-down tank (or alternatively a dirt filter) into the return. For older systems this installation is compulsory.

WOLF MGK-2-470 - Boiler system pipework - 1

Install a safety assembly comprising a safety valve with a response pressure of max. 6 bar, a pressure gauge and an automatic air vent valve.

The line between the boiler and the safety valve must not be able to be shut off. Severely excessive boiler pressure due to excessive boiler water temperatures can burst the boiler body or the boiler pipework, which would lead to a sudden escape of hot water (risk of scalding).

When using pipes and climate-controlled floors that are not impermeable to oxygen, always provide system separation by means of a heat exchanger.

Caution

This boiler is only suitable for heating systems with pumped heating circuits. If no heating circuit pump has been installed, sufficient circulation through the radiators cannot be ensured and the room will not be heated.

Ventilation air pipe DN200 Connection for room sealed operation Gas connection R2" Safety assembly 2" (accessory) Connection R2" for safety assembly Flow connection DN80 / PN6 Return connection DN80 / PN6 Test nipple for flue gas emissions test Condensate trap with DN250 flue outlet Connection R2" for BDF valve (accessory) Siphons with condensate drain

12. Selection of circulation pumps

The MGK-2 is supplied without a circulation pump. The pump rate of the pump to be supplied by the customer must be determined depending on the system and boiler pressure drop. The fan's power supply and speed control are via the MGK-2 (see electrical connection).

The primary and secondary circuit pumps should generally have the same flow rate. The pumps shown below are designed for a spread of 20 K. If the spread on the secondary side is smaller, a larger pump must be selected on the primary side. The maximum flow rates under 4. Specification must be observed.

The following pumps are recommended for the assembly of an MGK-2 with low loss header.

Wilo

Nominal flow rate at 20 K Spread [m3/h]HE pressure drop at 20 K Spread [mbar]Wilo typeDelivery head [mbar]Residual head [mbar]Output [W]Current [A]Connection
MGK-2 39017.2 120 Stratos 50/1-2 770 650 590 2.61~230V DN 50 flange fitting
MGK-2 47020.2 113 Stratos 50/1-12 680567 590 2.61~230V DN 50 flange fitting
MGK-2 55023.7 126 Stratos 65/1-12 730604 800 3.51~230V DN 65 flange fitting
MGK-2 63026.7 118 Stratos 65/1-12 655537 800 3.51~230V DN 65 flange fitting

Grundfos

Nominal flow rate at 20 K Spread [m3/h]HE pressure drop at 20 K Spread [mbar]Grundfos TypeDelivery head [mbar]Residual head [mbar]Output [W]Current [A]Connection
MGK-2 39017.2 120Magna3 50-120F730 610540 2.41~230V DN 50 flange fitting
MGK-2 47020.2 113Magna3 50-120F640 527540 2.41~230V DN 50 flange fitting
MGK-2 55023.7 126Magna3 50-150F650 524630 2.81~230V DN 50 flange fitting
MGK-2 63026.7 118Magna3 50-180F680 562760 3.41~230V DN 50 flange fitting
  • The maximum power consumption of the circulation pump must not exceed 4 A.
  • Reductions from DN80/PN6 to DN/50 or DN65/PN6 are required for the hydraulic connection of the pumps.
  • For the speed control of the circulation pump via the 0-10 V or PWM output of the boiler control unit, an extension module may be required from the pump manufacturer.

13. Gas connection

Gas connection R2"
Technical diagram of a fluid system with labeled components and directional arrows indicating flow or movement.

With the power supply disconnected, connect the gas supply line to gas connection R2" at the gas connection or the expansion joint (recommended) using the approved sealant.

WOLF MGK-2-470 - Gas connection - 2

Routing the gas pipe and making the gas connections must only be carried out by a licensed gas fitter.

Remove all residues from the heating pipework and the gas line prior to connecting the condensing boiler, particularly in older systems. Prior to commissioning, test all pipe and gas connections for leaks. Inappropriate installation or using unsuitable components or assemblies may lead to gas escaping, which results in a risk of poisoning and explosion.

WOLF MGK-2-470 - Gas connection - 3

Install a gas ball valve with fire protection in the gas supply line upstream of the Wolf condensing boiler. Otherwise explosions may occur during a fire. Size the gas supply line in accordance with DVGW-TRGI regulations.

WOLF MGK-2-470 - Gas connection - 4

Check the gas line for tightness without the boiler. Never release the test pressure via the gas valve.

WOLF MGK-2-470 - Gas connection - 5

Gas fittings on the appliance should be pressure tested to a maximum of 150 mbar. Higher pressure may damage the gas train, resulting in a risk of explosion, suffocation or poisoning. Close the gas ball valve on the gas condensing boiler to pressure test the gas line.

WOLF MGK-2-470 - Gas connection - 6

Mount the gas ball valve in an easily accessible place.

- Prior to installation, ensure that the boiler is set to the available gas type.

At the factory, the boiler is set up for natural gas E/H 15.0:

$$ \mathrm{Ws} = 1 1. 4 - 1 5. 2 \mathrm{kWh} / \mathrm{m} ^ {3} = 4 0. 9 - 5 4. 7 \mathrm{MJ} / \mathrm{m} ^ {3} $$

Only commission the appliance when the rated supply pressure has been reached.

WOLF MGK-2-470 - Gas connection - 7

If the supply pressure for natural gas (flow pressure) lies outside the 18 to 25 mbar range, adjustments must not be carried out and the boiler must not be put into operation.

14. Fitting the siphons

The standard delivery includes:

1 x condensate trap (under the burner hood on the ventilation air pipe)
2 x siphons with 3 condensate hoses and 1 tee (on the condensate trap)

Condensate connection:

Install condensate trap in the flue outlet of the condensate pan. Check tightness of the connections.

Install siphons:

Install the first siphon on the connector of the condensate pan.

Install the second siphon on the connector of the condensate trap.

WOLF MGK-2-470 - Install siphons: - 1

Fill the siphons with water prior to commissioning. Otherwise there is a risk of flue gas escaping.

Connect the condensate hoses of both siphons from the condensate pan and condensate trap with a tee and connect to the neutralising system.

WOLF MGK-2-470 - Install siphons: - 2

Check tightness of the connections.

WOLF MGK-2-470 - Install siphons: - 3

natural_image Close-up of a mechanical device with a white cylindrical component and black circular components, no visible text or symbols.

WOLF MGK-2-470 - Install siphons: - 4

natural_image Close-up of a transparent plastic hose attached to a wall, no visible text or symbols

WOLF MGK-2-470 - Install siphons: - 5

natural_image Close-up of a transparent glass container with liquid, mounted on a mechanical device (no visible text or symbols)

WOLF MGK-2-470 - Install siphons: - 6

natural_image Close-up of a glass bottle with a cap and side port, suspended by tubing (no visible text or symbols)

WOLF MGK-2-470 - Install siphons: - 7

natural_image Close-up of a mechanical device with a bottle and connecting rod (no visible text or symbols)

Installing the neutralising system with booster pump

The Neutrakon neutralising system type 08/BGN with booster pump for intensive pH regeneration, which is available as a Wolf accessory, can be slid under the boiler. Firstly remove the wooden slats for boiler transport. The booster pump can be mounted on the boiler crossbar.

Ensure even distribution of the granulate. The inlet and drain must not be covered with granulate.

Observe the installation and maintenance instructions supplied with the neutralising system.

Neutrakon neutralising system installation Type 8/BGN:

  • Remove black plug-in strainers (transport safeguard) on the inlet and drain and fit hose connections with pipe strainer. HT pipe connection possible.
  • Distribute the granulate evenly by shaking the Neutrakon. The granulate must not completely cover the inlet and drain (risk of blockage).
  • Secure booster pump to the crossbar with Velcro strip.
  • Fit air hose to the booster.
  • Connect the booster cable with the plug on the cable set.
  • Always fit the booster above the neutralising system to prevent condensate flowing into the booster.

WOLF MGK-2-470 - Installing the neutralising system with booster pump - 1

The booster pump must always be installed higher than the neutralising system. Danger of electrocution!

Function check

The first fill of granulate lasts for at least one year with approx. 2000 hours of operation p.a., provided the system is operated correctly. To ensure smooth functioning, the neutralising system must be checked at least once a year.

  1. Check fill level. If the granulate level is below the maximum mark (red label), it needs refilling. Neutralisation can only take place when the water flows through the granulate. The granulate fill level must always be above the condensate level.
  2. Measure pH value with pH indicator strip. if the pH value is below 6.5, the neutralising system needs servicing.

Neutralising system

Condensate lifting system
Booster pump mounted on crossbar

WOLF MGK-2-470 - Function check - 2

natural_image Close-up of two red screwdrivers working on a metal frame structure (no text or symbols visible)

Wooden slat

WOLF MGK-2-470 - Function check - 3

natural_image Close-up of a laboratory setup with a glass bottle, tubing, and a mechanical component (no visible text or symbols)

Air hose

WOLF MGK-2-470 - Function check - 4

natural_image Two views of a mechanical testing setup with black leather components and wiring (no visible text or symbols)

Condensate lifting system
Booster and condensate pump connection (connections on cable set behind the strut)

16. Neutralising system / condensate pump (accessories)

Servicing the neutralising system

  1. Release the connection fittings, detach the booster air hose, disconnect the neutralising system from the inlet and drain and pull it out from under the boiler.
  2. Loosen any granulate that is stuck together. Do not use sharp objects, as these may damage the casing. Discolouration of the granulate does not impair the neutralisation effect. If there is a large build-up of sludge or the granulate is very stuck together, completely replace the granulate.

Fill with fresh granulate up to the fill level indicated by the label.

  • Open hose clip (9) on the maintenance cover (8) and remove cover.
  • Empty contents into a suitable container (e.g. bucket).

Loosen soiled granulate and clean neutralising system with water. (Do not use sharp objects, as these may damage the casing.)

  • Fill the vertical pipes with granulate up to the fill level label (6).
  • Fit maintenance cover (8) on the pipes and secure with pipe clip (9).
  • Reconnect inlets and drains. Check for leaks.

Do not fill completely! In type 08/BGN neutralising systems, leave at least 4 cm of space above the granulate.

The inlet and drain openings must not be completely covered with granulate, or a blockage may occur.

  1. Fit plug-in strainer (HT pipe DN40) and/or hose connection with pipe strainer, seal ring and slide ring and fasten the connection fitting.

Install neutralising system.

Check connections for leaks.

Disposal

Granulate residue can be disposed of in normal household waste.

Condensate lifting system (accessory)

The Wolf condensate lifting system is fully wired and can be integrated into the MGK-2. The power supply and the alarm output of the condensate lifting system are connected to the cable set.

Including 6 m PVC hose for draining off the condensate.

Please note:

To fit the drain of the neutralising system directly into the inlet of the condensate lifting system, the pump and cover must be rotated by 180^ in relation to their factory setting.

WOLF MGK-2-470 - Please note: - 1

natural_image Hand pressing a mechanical component with a red curved arrow indicating rotation (no text or symbols)

Fill level label

230 V connection Leave at least 4 cm of space Inlet 1 2 3 4 5 6 7 8 9 10 11 Drain

1 Air hose with non-return valve
2 Neutrakon granulate GN
3 Velcro strip
4 Booster pump
5 Min - Max label
6 Fill level label
7 Neutralising system casing
8 Maintenance cover
9 Hose clip, cover
10 Hose clip, connection
11 Pipe spout with strainer

Condensate lifting system

Air/flue gas routing
WOLF MGK-2-470 - Please note: - 5

Boiler typeGas boiler type1)CategoryOperating mode Can be connected to
Open flueRoom sealedMoisture-resistant chimneyBalanced flue chimneyBalanced flue systemBuilding regulation approved flue pipeMoisture-resistant flue pipe
MGK-2 B23,B23P,C33, C43,C53, C63,C83, C93 I_2ELL^2) I_2H^3) Yes YesC83 C43 C33,C53, C63C53, C63 B23, C53,C83

1) For type B23, the combustion air is drawn from the installation room (open flue gas combustion equipment). The combustion air supply must come from outdoors (cf. DVGW-TRGI).

2) Germany

3) Austria / Switzerland

For type C, the combustion air is drawn through a sealed system from the outside (balanced flue gas combustion equipment). To allow this, the grille on the ventilation air pipe must be removed.

For type C and pressurised flue gas routing without special tightness requirements, a vent measuring 1x150 cm ^2 or 2x75 cm ^2 is needed in the installation room.

Air/flue gas routing

Single boiler system:

Implementation versions, condensing boilerMaximum length in metres, vertical
MGK-2 3904705$0 630
B23 FFlue in a duct and combustion air directly via the boiler (open flue)DN160 *8---
DN2005040199
DN 25050505050
B33Connection to a moisture-resistant flue gas chimney with horizontal connection lineDN250 DN315Calculation to EN 13384 (balanced flue manufacturer)
C33Combustion air supply and flue gas routing via the roof in a common pressure rangeDN250 DN315Calculation to EN 13384 (balanced flue manufacturer)
C33Vertical concentric roof outlet through a pitched or flat roof, vertical concentric air/flue gas routing for installation in a duct (balanced flue)DN250/350 DN315/4003827134
47382213
C43Connection to a moisture-resistant balanced flue chimney (balanced flue)DN250 DN315Calculation to EN 13384 (balanced flue manufacturer)
C53Terminals of the combustion air and flue are in different pressure ranges (balanced flue)DN200 DN2503522--
50505024
C53Connection to flue on an external wall with horizontal eccentric connection line (length 2.5 m) (balanced flue)DN200/300 DN250/350 DN315/4003924--
50505034
---50
C63The flue gas system has not been tested and certified with the appliance. It must meet the building requirements of the relevant country.DN250 DN315Calculation to EN 13384 (balanced flue manufacturer)
C83Connection to a moisture-resistant chimney and combustion air through an external wall (balanced flue)DN250 DN315Calculation to EN 13384 (balanced flue manufacturer)
C93Vertical flue for installation in a duct with horizontal eccentric connection line, balanced flue ventilation air supply DN200. The terminals are in the same pressure range, combustion air supply via existing duct (edge length in mm)DN250/250 370x370 DN250/315 450x450 DN315/315 450x450504516-
-505023
---33

* Applies to horizontal connection line DN 200 with length of 2 m and an 87° bend (corresponds to 3 m effective length)

Comments:

  • Length of connection line: 2 m, 1 additional 87° bend (corresponds to 3 m effective length) Duct cross-section = minimum annular gap to DIN 18160 Part 1
    • Available fan draught: MGK-2: 10 - 150 Pa (maximum length corresponds to the total length from the appliance to the flue terminal)

Note:

  • Systems C33 and C83 are also suitable for installation in garages.
  • Where necessary, adapt the installation examples to the relevant Building Regulations and requirements in your country/region. Discuss any questions relating to the installation of inspection covers and ventilation air supplies with your local flue gas inspector.
  • The length dimensions refer to concentric balanced flue systems and flues, specifically only to original Wolf components.
    • The following balanced flues or flues with CE-0036-CPD-9169003 certification may be used:

- Flue DN 160, DN 200, DN 250 and DN 315

- Concentric balanced flue DN 250/350 and DN 315/400

- The necessary identification labels are supplied with the Wolf accessory concerned.

- Please also observe the installation information supplied with the accessories.

18. Electrical connection

General information, electrical connection

WOLF MGK-2-470 - Electrical connection - 1

The installation must be carried out by a licensed electrical contractor. Observe VDE regulations and all local regulations of your power supply utility company.

WOLF MGK-2-470 - Electrical connection - 2

For installation in Austria: The ÖVE regulations and requirements and those of your local power supply utility company must be observed.

An omnipolar isolator with at least 3 mm contact separation must be integrated in the power cable upstream of the boiler. A connection box must also be installed by the operator, as per ÖVE requirements.

WOLF MGK-2-470 - Electrical connection - 3

Do not route sensor leads with 230 V mains cables.

WOLF MGK-2-470 - Electrical connection - 4

Danger due to live electrical components.

Please note: Turn off the ON/OFF switch before removing the casing.

Never touch electrical components or contacts when the ON/OFF switch is in the ON position. This can result in a risk of electrocution that could lead to injury or death.

The terminals are live even when the ON/OFF switch is in the OFF position.

WOLF MGK-2-470 - Electrical connection - 5

During servicing and installation work, isolate the entire system from the power supply at all poles, otherwise there will be a risk of electrocution.

Either an AM display module or a BM2 programming module can be installed in the front panel for operating the boiler.

The ON/OFF switch (integrated in the Wolf logo) switches the appliance OFF at all poles.

Front panel with integral ON/OFF switch WOLF Service cover with eBUS connection for fault diagnosis (under front casing) Control unit cover (under front casing) Cable entry

18. Electrical connection

Remove the cover of the control unit

Remove the front casing (see "Casing" chapter), then remove the 4 screws on the control unit with a screwdriver.

WOLF MGK-2-470 - Electrical connection - 1

natural_image Technical diagram of a mechanical device with red clamps and control panel (no text or symbols)

Remove the HCM-2 casing cover

1. 2. 3. 4.

Overview of components in the control unit

Terminals Fine-wire fuse Cable conduit HCM-2 control unit Burner control unit GBC-P Terminals

Connections in the control unit
Power cable inlet 230 V or 400 V Cable inlet 0-10 V eBUS T_DHW (5kNTC cylinder sensor) T_outside (5kNTC outside temperature sensor) E2 (5kNTC header sensor = low loss header; alternatively 0-10 V control e.g. 8 V = 80 % heating output) E1 (programmable input e.g. flue gas damper or room thermostat) A1* (programmable output) LP* (cylinder primary pump) ZHP (internal wiring of heating circuit pump) Z1* (230 V output when ON/OFF switch is in the ON position) Power supply (internal wiring) * Max. 1.5 A / 345 VA per output, no more than 600 VA in total for all outputs Power supply 230 V / 400 V AC 50 Hz ZHP connection, feed/heating circuit pump 230 V / 400 V AC 50 Hz max. 4 A External safety circuit (jumper) Variable speed pump connection (0 - 10 V DC / PWM)

Boiler connection (230 V/400 V):

The control, regulating and safety equipment are fully wired and tested.

You only need to connect the power supply, the heating circuit pump and the external accessories.

Create a permanent connection for the power supply.

Provide the power supply via a mains isolator (e.g. heating emergency stop switch) that ensures at least 3 mm contact separation for all poles.

Installation information, electrical connection, mains

  • Isolate the system from the power supply before opening.
  • Check that the appliance is isolated from the power supply.
  • Open the front casing and the cover of the control unit.
  • Open the upper cable conduit and the lower casing cover of the HCM-2.
  • Ensure separation of the LV and ELV side.
  • Strip approx. 70 mm insulation off the power cable.
  • Depending on the heating circuit pump used (230 V/400 V), lay a 3-core or 5-core power cable through the strain relief on the right hand side of the appliance and in the cable conduit to the series terminals.
  • Terminate wires at the series terminals as shown in the wiring diagram. Leave the wires for the earth conductor gr/ye approx. 10 mm longer than those for L (L1, L2, L3) and N.
  • Close the cable conduits and the cover of the control unit.

230 V/ 400 V PE N L3 L2 L1 PE

Fig: Mains connection

Installation information, electrical connection, heating circuit pump

  • Isolate the system from the power supply before opening.
  • Check that the appliance is isolated from the power supply.
  • Open the front casing and the cover of the control unit.
  • Open the upper cable conduit and the lower casing cover of the HCM-2.
  • Ensure separation of the LV and ELV side.
  • Strip approx. 70 mm insulation off the power cable.
  • Depending on the heating circuit pump used (230 V/400 V), lay a 3-core or 5-core power cable for the heating circuit pump through the strain relief on the right hand side of the appliance and in the upper cable conduit to the series terminals.
  • Ensure separation of the LV and ELV side.
  • Terminate wires accordingly at terminals X1-L1/L2/L3/N/PE. Leave the wires for the earth conductor gr/ye approx. 10 mm longer than those for L (L1, L2, L3) and N.
  • When using a variable speed pump, route the signal line through the lower cable conduit.
    PWM-controlled pumps must be connected to terminals X2-3 and X2-2(GND). Connect pumps with a 0-10 V control to X2-1 and X2-2.
  • Close the cable conduits and the cover of the control unit.

PE N L3 L2 L1 X1 5 4 3 2 1 UPM PWM GND UPM 0-10 V X2

Fig: Connection, heating circuit pump

Connection output A1 (230 V AC; max. 1.5 A) \*

Insert and secure the connecting cable through the cable gland.

Connect the connecting cable to terminals L1, N and ⊥.

The parameters for output A1 are described in the table.

* Max. 1.5 A / 345 VA per output, no more than 600 VA in total for all outputs

Netz L1 N ⊕ Z1 L1 N ⊕ ZHP L1 N ⊕ LP L1 N ⊕ A1 L1 N ⊕ 3

Fig: Connection output A1

Connection output Z1 (230 V AC; max. 1.5 A) \*

Insert and secure the connecting cable through the cable gland. Connect the connecting cable to terminals L1, N and ⊥.

* Max. 1.5 A / 345 VA per output, no more than 600 VA in total for all outputs

Connection output primary pump (230 V AC; max. 1.5 A)

Insert and secure the connecting cable through the cable gland. Connect the connecting cable to terminals L1, N and

* Max. 1.5 A / 345 VA per output, no more than 600 VA in total for all outputs

Changing the fuse (HCM-2)

Isolate the condensing boiler from the power supply before changing a fuse.

The ON/OFF switch on the boiler does not provide separation from the power supply.

The fuse is located under the top casing cover of the HCM-2. Danger due to live electrical components. Never touch electrical components or contacts as long as the condensing boiler has not been isolated from the power supply. Risk to life.

Changing the fuse (booster fuse)

  • Isolate the gas condensing boiler from the power supply before changing a fuse. The ON/OFF switch on the boiler does not provide separation from the power supply.
  • Danger due to live electrical components. Never touch electrical components or contacts as long as the gas condensing boiler has not been isolated from the power supply. Risk to life.

Low voltage boiler connection:

Connection input E1

Insert and secure the connecting cable through the cable gland. Connect the connecting cable for input 1 to terminals E1 in accordance with the wiring diagram; first remove the jumper between 1 and 2 from the respective terminals.

Caution

No external voltage must be connected to input E1, as this could would destroy the control PCB.

Netz L1 N ⊕ Z1 L1 N ⊕ ZHP L1 N ⊕ LP L1 N ⊕ A1 L1 N ⊕ 3

Fig: Connection output Z1

Netz L1 N ⊕ Z1 L1 N ⊕ ZHP L1 N ⊕ LP L1 N ⊕ A1 L1 N ⊕ 3

Fig: Connection output LP

M4A Fuse 5x20 Netz ZH L1N L1N ZHP LP A1 L1N L1N L1N HCM-2

Fig: HCM-2 fuse change

T 3.15 A F1

Fig: Booster fuse

E1 E2 AF SF eBUS a b a b 1 2 1 2 + - 1 2 1 2 1 2 1 2 1 2 /2

Fig: Connection input E1

Low voltage boiler connection:

Connection input E2

Insert and secure the connecting cable through the cable gland. Connect the connection cable for input 2 to terminals E2 as shown in the wiring diagram.

Caution

Only one external voltage of max. 10 V can be connected to input E2, otherwise the control PCB will be destroyed. 1(a) = 10 V, 2(b) = GND

E1 E2 AF SF eBUS a b a b 1 2 1 2 + - 1 2 1 2 1 2 1 2 1 2 2

Fig: Connection input E2

Connection, outside temperature sensor

The outside temperature sensor can only be connected to the terminal strip of the AF condensing boiler connection or the terminal strip of the control accessories, provided a BM2 programming module has been fitted.

Caution

When installing the appliance in places where there is a risk of high electromagnetic interference, it is advisable to fit shielded sensor and eBUS cables. The cable shield should be connected at one end to the PE potential in the control unit.

E1 E2 AF SF eBUS a b a b 1 2 1 2 + - 1 2 1 2 1 2 1 2 1 2 2

Fig: Connection, outside temperature sensor

Connection, digital Wolf control accessories (e.g. TM2, MM, KM, SM1, SM2)

Only connect control units from the Wolf accessory range. Each accessory is supplied with its own connection diagram. Use a two-core cable (cross-section > 0.5 mm ^2 ) as the connecting cable between the control unit accessory and the condensing boiler.

Caution

When installing the appliance in places where there is a risk of high electromagnetic interference, it is advisable to fit shielded sensor and eBUS cables. The cable shield should be connected at one end to the PE potential in the control unit.

WOLF MGK-2-470 - Caution - 1

Fig: Digital Wolf control accessories connection (eBUS interface)

Installing the electrical connection of the external safety circuit

An external safety circuit (e.g. maximum pressure limiter) can be connected to the floating contact.

Lockout for as long as the contact is open.

  • Isolate the system from the power supply before opening.
  • Check that the appliance is isolated from the power supply.
  • Open the front casing and the cover of the control unit.
  • Open the upper cable conduit and the lower casing cover of the HCM-2.
  • Remove the jumper at terminals X2-4 and X2-5.
  • Push the potential-free connecting cable of the external component through the strain relief on the right-hand side of the appliance and lay it in the lower cable conduit to the series terminals X2.
  • Ensure separation of the LV and ELV side.
  • Terminate wires accordingly at terminals X2-4 and X2-5.
  • Close the cable conduits and the cover of the control unit.

External safety circuit floating contact (jumper) X2

Fig: Connection of external safety circuit

19. Display / programming module / installation

Either an AM display module or a BM2 programming module must be installed for operating the MGK-2.

AM BM2

Status Operating mode Heating mode Burner status ON

The AM functions solely as a display module for the heating appliance. Heating appliance-specific parameters and values can be programmed and displayed.

Specification:

  • LCD display 3"
    • 4 quick start buttons
    • 1 rotary selector with push-button function
  • Use when BM2 is used as a remote control or in a cascade circuit
    • AM is always in the heating appliance

NB:

ON/OFF switch

Heating appliance Heating mode 1x Burner ON 25.2 °C 1.5 bar Pressure Boiler temperature 14:12 20/01/2013

The BM2 (programming module) communicates with the heating appliance and all connected extension modules via eBUS.

Specification:

  • Colour display 3.5", 4 function buttons, 1 rotary selector with push-button function
  • Micro SD card slot for software update
  • Central programming unit with weather-compensated flow temperature control
    • Time program for heating, DHW and DHW circulation

Remove the front panel of the MGK-2 and refit it after installation of the module.

Insert the AM or BM2 in the slot above the ON/OFF switch (Wolf logo).

Both modules can be plugged into this slot. Further commissioning or address assignment measures specific to the BM2 can be found in the BM2 installation instructions.

Switch ON power supply / activate MCB and switch ON/OFF switch to ON on the MGK-2.

Overview AM

Note:

If your Wolf heating appliance does not have an AM display module, ignore this page.

Other functions and descriptions can be found in the installation instructions for contractors or the user operating instructions for the AM display module.

Quick start buttons Status display Button 1 Button 2 Button 3 Button 4 Status Operating mode Heating mode Burner status ON Rotary selector with push-button function Burner ON Heating appliance in heating mode Heating appliance pump ON

Button 1

Button 2

Button 3

Button 4

WOLF MGK-2-470 - Overview AM - 2

natural_image Black vertical panel with four metallic buttons labeled 'III', a faucet icon, a hand gesture, and a curved arrow (no text or symbols beyond basic icons)

Heating appliance set temperature (if BM2 as remote control - no function)

DHW set temperature (if BM2 as remote control - no function)

Enable emissions test mode (for chimney sweep only)

Acknowledge fault / End / Back

21. AM display module menu structure

AM control unit menu structure

Heating appliance

Boiler temperature

System pressure

Status

Operating mode

Burner status

Notification

Display of

faults or

notifications

(see chapter 10)

Back

Displays

Default settings

Emissions test

Contractor

Back

Displays

Back

T_boiler in °C

System pressure in bar

T_flue gas current in °C

T_outside in °C

T_return in °C

T_DHW in °C

Input E1

Fan speed rpm

Modulation level in %

Actual I/O value

ZHP speed

Burner starts

Burner hours run

Mains hours

Power ON count

HCM2 firmware

Back

Default settings

Back

Language

Button lock

Back

Emissions test

End

Rem. time in min.

T boiler

T_return

Calibration

Extend time

End

Contractor

Contractor code

1111

Back

Relay test

System

Parameter

Parameter reset

Fault history

Delete fault history

Acknowledge fault

Back

Heating appliance operating mode

Display indication Function
Start Start the appliance
Standby No heating or DHW demand
Heating mode Heating mode, at least one heating circuit demands heat
DHW mode DHW heating with cylinder, cylinder temperature is below set value
Emissions test Emissions test mode active, heating appliance running at maximum power
Antifreeze HC Boiler frost protection function, boiler water temperature below frost protection limit
Antifreeze DHW Frost protection function of DHW cylinder active, cylinder temperature below frost protection limit
Frost protection System frost protection active, outside temperature below frost protection limit
Heating run-on Heating circuit pump run-on active
DHW run-on Cylinder primary pump run-on active
Parallel mode Heating circuit pump and cylinder primary pump active in parallel
TestRelay test function has been activated
CascadeCascade module in system active
BMS Appliance is controlled by building management system (BMS)

Heating appliance burner status

Display indicationFunction
OFFNo burner demand
Pre-flushFan operation before burner start
IgnitionGas valves and ignition unit are active
StabilisationFlame stabilisation after safety time
Soft startAfter flame stabilisation in heating mode, the burner runs at low burner power for the duration of the soft start to prevent cycling
ONBurner operational
Cycle blockBurner block after a burner cycle for the duration of the cycle block
Op without b.Operation without burner, input E1 closed
Flue gas damperWaiting for feedback from flue gas damper (input E1)
dT too wide Temperature spread between boiler water temperature sensor and return temperature sensor too wide
dT Tboil-eSTB Temperature spread between eHLSC1/eHLSC2 and boiler sensor too wide
Valve testGas valve test
Grad. controlBoiler water temperature rising too fast
Gas pressureGas pressure switch has not responded
FaultBurner not operational due to a fault
Post-flushFan operation after burner shutdown

Overview BM2

Note:

Other functions and descriptions can be found in the installation instructions for contractors or the user operating instructions for the BM2 programming module.

Operating mode Page heading Quick start buttons Burner status Status display Button 1 Button 2 Button 3 Button 4 Heating appliance Heating mode Burner ON 25.2 °C 1.5 bar Pressure Boiler temperature 14:12 20/01/2013 Rotary selector with push-button function Display of system data (content varies) Time Date eBUS connection available No eBUS connection available

Button 1

Button 2

Button 3

Button 4

WOLF MGK-2-470 - Contractor - 2

natural_image Close-up of a black industrial control panel with four slots and a 1x water level indicator (no text or symbols beyond basic symbols)

(in this view - no function)

1x DHW heating

Enable emissions test mode (for chimney sweep only)

(in this view - no function)

Caution

Modifications must only be carried out by a recognised heating contractor or by Wolf customer service. Incorrect operation can lead to system faults.

Caution

On the AM display module or the BM2 programming module, the factory setting for the HG parameters can be reinstated in the Contractor menu.

WOLF MGK-2-470 - Caution - 1

To prevent damage to the heating system, cancel night setback when outside temperatures fall below -12 °C. If this rule is not observed, ice may build up on the flue outlet which may cause injury or material losses.

The control parameters can only be modified or displayed using the AM display module or BM2 programming module on the boiler. For procedures, check the operating instructions of the relevant accessories.

No.Description Unit Factory setting Min Max
HG01Burner hysteresis °C 15 7 30
HG02*Lower burner output, boilerMinimum burner output%19 19100
HG03Upper burner output, DHWMaximum burner output DHW in %%10019100
HG04Upper burner output, heatingMaximum burner output, heating in %%10019100
HG07Heating circuit pump run-on timeHeating circuit pump run-on time in heating modeMin10 30
HG08Maximum boiler water temperature HZ (applicable to heating operation) TV-max°C 85 4090
HG09Burner cycle block, applicable to heating operationMin10130
HG10Heat source eBUS address-115
HG12No function----
HG13Function, input E1Various functions can be allocated to input E1.-nonediv.div.
HG14Function, output A1 (230 V AC)Various functions can be allocated to output A1.-nonediv.div.
HG 15Cylinder hysteresis, switching differential during cylinder re-heating°C 51 30
HG16Pump rate HC, minimum%25 15100
HG17Pump rate HC, maximum%10015100
HG19SLP run-on time (cylinder primary pump)Min3110
HG20Max. cylinder heating timeMin12030/Off180
HG21Minimum boiler water temperature TK-min°C 20 2090
HG22Maximum boiler water temperature TK-max°C 90 5090
HG25Boiler excess temperature during cylinder heating°C 10 1 30
HG33Burner hysteresis runtimeMin10 1 30
HG34eBUS feed-AutoOffON
HG37Pump control type (constant / linear / dT)-dTdiv.div.
HG38Set dT, pump control unit (dT)°C 20 0 40
HG39Soft start timeMin30 10
HG40System configuration (see chapter "Parameter description")-1div.div.
HG41Speed ZHP DHW%10015100
HG42Header hysteresis°C 50 20
HG43No function----
HG44No function----
HG45No function----
HG46Header excess boiler water temperature°C 60 20

* HG02 controls the fan speed 19 % - fan speed corresponds to 17 % burner output.

Parameter HG01

Burner switching hysteresis

Factory setting:

see table chap. 24

Control unit parameters

Individual settings:

The burner switching hysteresis regulates the boiler water temperature within a set range by switching the burner ON and OFF. The higher the hysteresis, the higher the boiler water temperature fluctuation around the set value, resulting in longer burner runtimes and vice versa. Longer burner runtimes protect the environment and extend the service life of wearing parts.

WOLF MGK-2-470 - Parameter HG01 - 1

line | Burner runtime (min.) | Switching hysteresis (°C) | | --------------------- | ------------------------- | | 0 | 15 | | 10 | 7 |

Fig.:
Time sequence of the dynamic burner switching hysteresis for a user-defined burner switching hysteresis of 15 °C and a selected hysteresis time (parameter HG33) of 10 minutes.

Parameter HG02

Lower burner output

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

The setting for the minimum burner output (minimum device load) is applicable to all operating modes. This percentage value corresponds approximately to the real device output.

Parameter HG03

Individual settings: ____

The setting for the maximum burner output in DHW mode (maximum device load). Valid for DHW cylinder heating. This percentage value corresponds approximately to the real device output.

Parameter HG04

Upper burner output HZ

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

The setting for the maximum burner output in heating mode (maximum device load). Valid for heating mode, BMS and emissions test. This percentage value corresponds approximately to the real device output.

25. Parameter description

Parameter HG07

Run-on time, heating circuit pump

Factory setting:

see table chap. 24

Control unit parameters

Individual settings:

If there is no more heat demand from the heating circuit, the feed/heating circuit pump ZHP will run on in accordance with the set time to prevent a boiler safety shutdown at high temperatures.

Parameter HG08

Maximum boiler water temperature HZ TV-max.

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

This function limits the boiler water temperature upwards in heating mode, and the burner shuts down. This parameter has no function during cylinder heating, and the boiler water temperature may also be higher during this time. "Reheating effects" can result in the temperature being slightly exceeded.

Parameter HG09

Burner cycle block

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

Each time the burner is shut down in heating mode, it will be blocked for the duration of the burner cycle block. The burner cycle block is reset by switching the ON/OFF switch OFF and ON or by briefly pressing the reset button.

Parameter HG10

eBUS address of the heat source

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

If multiple heat sources are controlled in one heating system with a cascade module, addresses must be allocated to the heat sources. Each heat source requires its own eBUS address in order to communicate with the cascade module. The activation sequence of the heat sources can be set in the cascade module.

Please note: Duplicated addresses lead to malfunctions of the heating system.

Parameter HG13

Function input E1

The functions of the input E1 can only be read and set directly on the boiler under parameter HG13 using the AM display module or BM2 programming module.

DisplayDescription
noneNo function (factory setting)Input E1 is not taken into consideration by the control unit.
RTRoom thermostatWith open input E1, heating operation will be blocked (summer mode) and frost protection mode and emissions test mode will not be blocked, independent of any digital Wolf control accessories.
DHWDHW blocking/enablingWith open input E1, DHW heating will be blocked, independent of any digital Wolf control accessories.
RT/DHWHeating and DHW blocking/enablingWith open input E1, heating operation and DHW heating will be blocked and frost protection mode and emissions test mode will not be blocked, independent of any digital Wolf control accessories.
TimerTimer (DHW circulation button)If input E1 is configured as a DHW circulation button, output A1 is automatically set to "DHW circulation pump" and blocked for further settings. When input E1 is closed, output A1 is activated for 5 minutes. When input E1 has switched off and 30 minutes have elapsed, the timer function is re-enabled for the next operation.
Op without b.Operation without burner (burner blocking)When contact E1 is closed, the burner is blocked.Heating circuit pump and cylinder primary pump continue running in standard mode.The burner is enabled in emissions test mode and in frost protection mode.Opening contact E1 enables the burner again.
Flue gas damperFlue gas damper/ventilation air damperFunction monitoring of the flue gas damper/ventilation air damper with floating contact.Closed contact is a pre-requisite for enabling burner in central heating, DHW and emissions test mode.If input E1 is configured as a flue gas damper, output A1 is automatically programmed as a flue gas damper and blocked for other settings.

Parameter HG14

Function output A1

The functions of the output A1 can only be read and set directly on the boiler under parameter HG14 using the AM display module or BM2 programming module.

Display Description
none none(factory setting)Output A1 is not taken into consideration by the control unit.
Timer100 DHW circulation pump 100 %Output A1 is controlled by the time program in the control accessory, if DHW circulation has been enabled.Output A1 is constantly activated when no accessory controller is installed.
Timer50 DHW circulation pump 50 %Output A1 is activated cyclically by the time program in the control accessory, if DHW circulation has been enabled.5 minutes ON, 5 minutes OFF. Output A1 is constantly activated cyclically when no accessory controller is installed.
Timer20 DHW circulation pump 20 %Output A1 is activated cyclically by the time program in the control accessory, if DHW circulation has been enabled.2 minutes ON, 8 minutes OFF. Output A1 is constantly activated cyclically when no accessory controller is installed.
Alarm Alarm outputOutput A1 is activated 4 minutes after a fault.
Flame Flame detectorOutput A1 is activated after a flame has been recognised.
Timer Timer (DHW circulation button)Output A1 is activated for 5 minutes when input E1 closes.If output E1 is configured as a timer, input E1 is automatically set to "Circulation tester" and blocked for further settings. When input E1 has switched off and 30 minutes have elapsed, the timer function is re-enabled for the next operation.
Flue gas damperFlue gas damper/ventilation air damperOutput A1 is activated first before each burner start. The burner will, however, only be enabled after input E1 has been closed. Closed contact E1 is a pre-requisite for enabling burner in central heating, DHW and emissions test mode.If output A1 is activated and does not close input E1 within 2 minutes, a fault is generated (FC 8).If output A1 is deactivated and does not open input E1 within 2 minutes, a fault is generated (FC 8).If output A1 is configured as a flue gas damper, input E1 is automatically programmed as a flue gas damper and blocked for other settings.
Ext. vent.External ventilationOutput A1 is switched inverse to the gas combination valve. Switching OFF external ventilation (e.g. extractor fan) during burner operation is only required if the boiler is operated as an open flue system.
External fuel valveExternal fuel valveActivation of an additional fuel valve during burner operation.Output 1 is activated from pre-flushing of the device until burner shutdown.

25. Parameter description

Parameter HG15

Cylinder hysteresis

Factory setting:

see table chap. 24

Control unit parameters

Individual settings:

The cylinder hysteresis regulates the start point for cylinder heating. The higher the setting, the lower the start point for cylinder heating.

Example: Set cylinder temperature 60 °C

Cylinder hysteresis 5 K

Cylinder heating commences at 55 °C and ends at 60 °C.

Parameter HG16

Pump rate HC, minimum

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

In heating mode, the pump does not regulate below this set value. Independent of pump control type set in HG37.

Parameter HG17

Pump rate HC, maximum

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

In heating mode, the pump does not regulate above this set value. Independent of pump control type set in HG37. If the pump control type is "Constant", HG17 is used as the setting for the pump speed in heating mode.

Parameter HG19

LP run-on time (cylinder primary pump)

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

After completing cylinder heating in summer mode (the cylinder has reached the set temperature), the cylinder primary pump will run on up to the maximum set run-on time.

The cylinder primary pump will switch OFF prematurely if, during the run-on time, the boiler water temperature cools down to a differential between boiler and set cylinder temperature of 5 K.

In winter mode, the cylinder primary pump runs on for a fixed time of 30 seconds after successful cylinder heating (independently of parameter HG19).

25. Parameter description

Parameter HG20

Max. cylinder heating time

Factory setting:

see table chap. 24

Control unit parameters

Individual settings:

Cylinder heating commences as soon as the cylinder temperature sensor demands heat. The heating circuit pumps would be constantly switched off if the boiler was undersized, the cylinder was scaled up or if DHW was constantly drawn off during DHW priority mode. The accommodation cools down significantly. To limit this effect, it is possible to specify a maximum cylinder heating time.

If the set maximum cylinder heating time has expired, error message FC52 appears on the programming or display module.

The control unit reverts to heating mode and cycles in the selected rhythm (HG20) between heating and cylinder heating mode, irrespective of whether the cylinder has reached its set temperature or not.

The function "Max. cyl. heat time" remains active even if parallel pump operation is activated. If HG20 is set to OFF, the function "Max. cyl. heat time" is deactivated. Set this parameter to OFF in heating systems with a high DHW consumption, e.g. hotels, sports facilities etc.

Parameter HG21

Minimum boiler water temperature TK-min

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

The control unit is equipped with an electronic boiler thermostat which has an adjustable minimum start temperature. The burner is switched on subject to the cycle block if this temperature is not achieved when heat is demanded. The minimum boiler water temperature TK-min is not necessarily achieved when there is no heat demand.

Parameter HG22

Maximum boiler water temperature TK-max

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

The control unit is equipped with an electronic boiler thermostat which has an adjustable maximum shutdown temperature (maximum boiler water temperature). The burner is switched off if this temperature is exceeded. The burner will be started again when the boiler water temperature has fallen by as much as the burner switching differential.

Parameter HG25

Excess boiler temp. for cylinder heating

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

The excess temperature differential between the cylinder temperature and the boiler water temperature during cylinder heating is selected with parameter HG25. The boiler water temperature continues to be limited by the maximum boiler water temperature (parameter HG22). This ensures that, even in spring and autumn, the boiler water temperature is higher than the cylinder temperature, thereby ensuring short heating times.

25. Parameter description

Parameter HG33

Burner hysteresis runtime

Factory setting:

see table chap. 24

Control unit parameters

Individual settings:

When starting the burner or changing to heating mode, the burner hysteresis is set to the parameter "Burner switching differential" HG01. Based on this set value, the burner hysteresis within the set "Runtime burner hysteresis" HG33 is reduced to the minimum burner hysteresis of 7 K. This is designed to prevent short burner runtimes.

Parameter HG34

eBUS feed

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

In the "Auto" setting, the power supply of the eBUS system is switched ON or OFF automatically by the control unit, depending on the number of available eBUS subscribers.

OFF = BUS feed is always switched OFF

ON = BUS feed is always switched ON

Auto = the control unit switches the bus feed ON or OFF automatically

Parameter HG37

Pump control type

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

For setting the type of pump speed control in heating mode and with BMS.

Constant = fixed pump speed (HG17)

Linear = linear pump speed between HG16 and HG17 corresponding to the current burner output

dT = speed control between HG16 and HG17 to achieve flow/return temperature spread (HG38)

Parameter HG38

Set dT pump control unit

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

If dT pump control unit is activated in parameter HG37, the set dT specified in HG38 applies. The change to the pump speed means the dT is regulated between flow and return within the speed limits in HG16 and HG17.

Parameter HG39

Soft start time

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

In heating mode, the burner is run at a lower output for the set time after burner start.

Parameter HG40

System configuration

The MGK-2 is fine-tuned to the heating system by selecting from 6 preconfigured system configurations that can only be read and set directly on the boiler under parameter HG40 using the AM display module or BM2 programming module. This parameter affects both the function of the ZHP (feed/heating circuit pump) and the input E2.

System configuration 01

Direct heating circuit on the boiler + optional further mixer circuits via mixer modules (factory setting)

  • Burner is activated subject to demand from the direct heating circuit or optionally connected mixer circuits
  • Feed/heating circuit pump (ZHP) as heating circuit pump for direct heating circuit
  • Boiler thermostat; set value is specified by heating circuit or mixer circuits
    • Input E2: not assigned

Note: If the pressure drop of the boiler incl. the pipework is >700 mbar, a low loss header must be installed.

System configuration 02

One or more mixer circuits via mixer modules (no direct heating circuit on the boiler)

  • Burner is activated subject to demand from the connected mixer circuits
  • Boiler thermostat; set value is specified by mixer circuits
    • Input E2: not assigned
    • Feed/heating circuit pump (ZHP) not active

Note: If the pressure drop of the boiler incl. the pipework is >700 mbar, a low loss header must be installed.

System configuration 11

Low loss header with header sensor

  • Burner is activated subject to demand from the header temperature control
  • Feed/heating circuit pump (ZHP) activated as feed pump for header demand
    • Header temperature control
    • Input E2: header sensor

System configuration 11

Plate heat exchanger as system separation

  • Burner is activated subject to demand from the header temperature control
  • Feed/heating circuit pump (ZHP) activated as feed pump for header demand
    • Header temperature control
    • Input E2: header sensor

WOLF MGK-2-470 - Plate heat exchanger as system separation - 1

flowchart
graph TD
    A["Valve with DHC"] --> B["Valve with ZHP"]
    B --> C["Pressure Gauge"]
    D["Pressure Gauge"] --> E["Valve with dHC"]
    F["Pressure Gauge"] --> G["Valve with ZHP"]

WOLF MGK-2-470 - Plate heat exchanger as system separation - 2

flowchart
graph TD
    A["Control Unit"] --> B["Valve"]
    B --> C["MM 1"]
    C --> D["Control Unit"]
    D --> E["Valve"]
    E --> F["MM 1"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333
    style E fill:#cff,stroke:#333
    style F fill:#ffc,stroke:#333

WOLF MGK-2-470 - Plate heat exchanger as system separation - 3

flowchart
graph LR
    A["Component E2"] --> B["ZHP"]
    B --> C["SAF"]
    C --> D["Output"]
    style A fill:#f9f,stroke:#333
    style C fill:#ccf,stroke:#333

WOLF MGK-2-470 - Plate heat exchanger as system separation - 4

flowchart
graph LR
    A["Data Input"] --> B["E2"]
    B --> C["ZHP"]
    C --> D["SAF"]
    D --> E["Output"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cff,stroke:#333
    style D fill:#ffc,stroke:#333
    style E fill:#cfc,stroke:#333

System configuration 51

BMS burner output

Burner is activated subject to demand from the external controller

• Feed/heating circuit pump (ZHP) activated as feed pump from 2 V upwards
• No temperature control
- Input E2: Control 0-10 V by external controller 0-2 V burner OFF, 2-10 V burner output min. to max. within the programmed limits (HG02 and HG04)
• Automatic output reduction when approaching TK_max (HG22) is activated. Deactivation on reaching TK_max

Note: If the pressure drop of the boiler incl. the pipework is >700 mbar, a low loss header must be installed.

BMS% E2 ZHP

System configuration 52

BMS set boiler temperature

  • Burner is activated subject to demand from the boiler thermostat
    • Feed/heating circuit pump (ZHP) activated as feed pump from 2 V upwards
  • Boiler thermostat
  • Input E2: Control by external controller with 0-10 V 0-2 V burner OFF 2-10 V set boiler temperature TK min (HG21) - TK max (HG22)

Note: If the pressure drop of the boiler incl. the pipework is >700 mbar, a low loss header must be installed.

BMS°C E2 ZHP

System configuration 60

Cascade for multi boiler systems (setting automatic when cascade module is connected)

  • Burner is activated subject to demand from cascade module via eBUS (0-100 % burner output; min. to max. within the programmed limits) (HG02 and HG04)
    • Feed/heating circuit pump (ZHP) activated as feed pump
    • Header temperature control via cascade module
    • Input E2: not assigned
    • Automatic output reduction when approaching TK_max (HG22) is activated. Deactivation on reaching TK_max
  • A low loss header or plate heat exchanger can be used as system separation.

WOLF MGK-2-470 - Cascade for multi boiler systems (setting automatic when cascade module is connected) - 1

flowchart
graph TD
    A["eBUS"] --> B["ZHP"]
    B --> C["SAF"]
    C --> D["KM"]
    D --> E["ZHP"]
    E --> F["SAF"]
    F --> G["Return to SF"]
    H["eBUS"] --> I["ZHP"]
    I --> J["SAF"]
    J --> K["Return to SF"]

Important information:

In these schematic diagrams, shut-off valves, air vent valves and safety equipment are not fully represented. These should be provided in compliance with the applicable standards and regulations for each individual system.

Hydraulic and electrical details can be found in the Hydraulic System Solutions technical guide.

25. Parameter description

Parameter HG41

Speed ZHP DHW

Factory setting:

see table chap. 24

Control unit parameters

Individual settings:

In DHW mode, the pump runs at this set value. Independent of pump control type set in HG37.

Parameter HG42

Header hysteresis

Factory setting:

see table chap. 24

Control unit parameters

Individual settings:

The header hysteresis regulates the header temperature within the set range by switching the heat source ON and OFF. The higher the ON / OFF temperature differential, the higher the header temperature fluctuation around the set value, resulting in longer heat source runtimes, and vice versa.

Parameter HG46

Header excess boiler water temperature

Factory setting:

see table chap. 24

Control unit parameters

Individual settings: ____

The excess temperature differential between the header temperature and the boiler water temperature during header heating is selected with parameter HG46. The boiler water temperature continues to be limited by the maximum boiler water temperature (parameter HG22).

Flue gas damper power supply

  • Isolate the system from the power supply before opening.
  • Check that appliance is isolated from the power supply.
  • Open the front casing and the cover of the control unit.
  • Strip approx. 70 mm off the connecting cable of the flue gas damper motor and signal contact.
  • Lay connecting cable from the flue gas damper motor to the screwless terminals, pushing it through the strain relief on the right-hand side of the boiler, and connect it to programmable output A1.
  • Lay connecting cable from the limit switch to the screwless terminals, pushing it through the strain relief on the right-hand side of the boiler, and connect it to programmable input E1.
  • Close cover of control unit.

Note:

The contractor parameter

HG13 (input 1) must be set to FI gas damp and

HG14 (output 1) must be set to FI gas damp.

When the limit switch is open, the burner is blocked both for DHW and central heating and for emissions test and frost protection.

WOLF MGK-2-470 - Flue gas damper power supply - 1
HCM-2 electrical connection

WOLF MGK-2-470 - Flue gas damper power supply - 2

flowchart
graph TD
    A["Programmable Output"] --> B["Programmable Input"]
    B --> C["Flue Gas Damper"]
    subgraph A1
        D["LP L1 N ⊕ A1 L1 N ⊕"]
        E["E1 (programmable input, e.g. flue gas damper)"]
    end
    subgraph E1
        F["E1 a b E2 a b AF 1 2 1 2 SF + -"]
        G["1 2 1 2 1 2 1 2 1 2"]
    end
    subgraph_M["230V~"]
        H["MB"]
    end
    I["NB. Flue gas dam be potential-free"] --> H
    J["Otherwise the will be destroyed"] --> H

Limit switchFlue gas damper motor

NB.

Flue gas damper limit switch must be potential-free.

Otherwise the MGK-2 control unit will be destroyed.

Damper function test

▶ Start the boiler.
▶ Visual check to ensure damper is open.
▶ Unplug E1 for 2 minutes during operation.
▶ Reconnect E1.
▶ Acknowledge fault message.
▶ Visual check to ensure flue gas damper is closed.

Boiler must lockout with error code 8, with the fan continuing to run at low speed. Fault code 44 "Flu gas prssr swtch" may also appear.

During commissioning and as part of the annual heating appliance test, the cascade damper in overpressure heating appliance systems must be tested for tightness to ensure no CO_2 can escape into the installation room.

Cascades (overpressure), open flue
A V S H 2 ... 4

The following basic principles are taken into consideration in all calculations for the sizing tables:

-Length between the individual appliances: 1.0 m
-Length after the last appliance: 2.0 m
-Pressure drops: 2 x 45° bends in the diameter of the header pipe (optionally as lateral offset or 90° diversion)
-Combustion air supply: from installation room
-Duct ventilation: balanced flow principle
-Geodetic height: 325 m

Flue system design
The following overview shows the maximum vertical flue length for open flue positive pressure cascades, with different boiler combinations:

MGK-2VNominal diameter of connection line to the applianceSNominal diameter of headerANominal diameter of flue pipe, vertical∅/☐Minimum duct sizesround rectangularHAchievable height from duct inlet to duct outlet
390 2x row DN250 DN250 DN315 420 mm400 mm 50 m
3x row DN250 DN315 DN315 420 mm 400 mm 42 m
4x row DN250 * * * ***
470 2x row DN250 DN250 DN315 420 mm 400 mm 50 m
3x row DN250 DN315 DN315 420 mm 400 mm 17 m
4x row DN250 * * * ***
550 2x row DN250 DN250 DN315 420 mm 400 mm 22 m
400 mm 50 m
3x row DN250 * * * ***
4x row DN250 * * * ***
630 2x row DN250 DN315 DN315 420 mm 400 mm 23 m
3x row DN250 * * * ***
4x row DN250 * * * ***

* Calculation and design to EN 13384-2 – kit on request

A maximum back pressure up to 50 Pa must be maintained in the connection to the header line and must not be exceeded. Only use DIBt approved flue pipes.

In cascade operation, a Wolf cascade controller is required.

27. Cascade operation

Cascade module setting

The standard settings of the Wolf cascade module can lead to cycling in very sluggish heating systems.

For optimum cascade operation, we therefore recommend the following settings:

Parameter Setting
KM10 20
KM11 500

Pump speed setting

If the circulation and feed pump (ZHP) are controlled by the Wolf boiler control unit during operation with low loss header, the flow rates of the primary and secondary circuits may differ from each other.

If the secondary flow rate is much greater than the primary flow rate, this can lead to cycling of the boiler.

In this case, we recommend significantly increasing the minimum pump speed. To do this, increase parameter HG16 in 20 % steps.

The higher the set header temperature, the higher the pump speed that must be selected for the feed pump. Set header temperatures of more than 75 °C should be avoided if possible.

Caution

In cascade operation, the condensate pump must be connected externally with constant voltage, as the condensate flowing back cannot be discharged otherwise when the boiler is switched off (e.g. for boiler maintenance).

Setting the eBUS address in cascade mode

The eBUS address is set in the contractor menu HG10 on the AM display module or the BM2 programming module.

Boiler in cascade mode eBUS address
Boiler 1 1*
Boiler 2 2
Boiler 3 3
Boiler 4 4

*Factory setting (individual boiler without cascade mode)

Installation instructions

For general information on positioning, see also information on installation of individual system.

Different minimum clearances must be observed when installing the boilers in the installation room.

1400 850 700 1400 850 700 1400 850 700 1400 850 700 1700 1700 1000 1000 1000 1000

Fig: 2 - 4 boilers in the installation room, side by side

Flue gas damper installation

Motor-controlled flue gas damper to DIN 3388 Part 2 and DVGW G 635.

For appliances in cascade systems that produce condensation and have no ignition flame.

Design:

Sealed, condensate-resistant, for overpressure flue systems, stainless steel casing, stainless steel shaft, positioning lever for position indication, including actuator for 230 V AC current with return spring, integral fuse, protection rating to DIN 40050, IP 44, for flue gas temperatures up to 120 °C.

WOLF MGK-2-470 - Flue gas damper installation - 1

natural_image Close-up of a metallic cylindrical device with red cap and black housing, mounted on a white panel (no visible text or symbols)

Mounting the flue gas damper:

  • Switch the ON/OFF switch on the gas condensing boiler to OFF.
  • The mains terminals are live even when the ON/OFF switch has been switched OFF. Isolate the system from the power supply, otherwise there is a risk to life from electrocution.
  • Install flue gas damper in the flue outlet of the condensate pan.
    (Damper axis must be oriented upwards at an angle of 3 to 5° to the horizontal.)
  • Connect the cable from the limit switch to input E1.
  • Connect flue gas damper servomotor cable to output A1 (see "Flue gas damper power supply").
  • Set control unit to flue gas damper operation (see HG13/14).

  • Install condensate trap in female connection of the flue gas damper.

  • Installation of siphon, neutralising system, condensate pump: see corresponding chapter in the information on installing an individual system.

28. Filling / draining the heating system

Filling the heating system

Fill the system correctly in line with the information on water treatment and the system and operator's log, and vent it completely to ensure the smooth running of the condensing boiler.

Caution Before connecting the gas condensing boiler, flush the heating system to remove residues such as welding pearls, hemp, putty, etc. from the pipework.

• The gas tap must be shut.
- Open the air vent valves.
- Open all heating circuits.
- Open all radiator or mixer valves.
- Slowly fill the entire heating system and boiler when cold, for example via the BDF valve at the return, to approx. 2 bar pressure.

Caution Inhibitors are not permissible.

  • Open the flow valves on the condensing boiler.
  • Fill the heating system to 2 bar pressure. In operation, the pressure must be between 1.5 and 2.5 bar.
  • Check the entire system for water leaks.
  • Fill both siphons with water.
  • Vent the heating circuit; to do this, switch the gas condensing boiler ON and OFF again several times.
  • Top up with water when the system pressure falls substantially.
  • Open the gas ball valve.
  • Press the reset button on the AM or BM2.

Note: In constant mode, the heating circuit is automatically vented via the air vent valve (accessory).

Draining the heating system

  • Switch off system (see operating instructions) and allow it cool to at least 40^ , otherwise there is a risk of scalding.
  • Safeguard the heating system against accidental reconnection of the power supply.
  • Open drain valve (BDF valve), for example, on the boiler.
  • Open the air vent valves on the radiators.
  • Drain heating water.

WOLF MGK-2-470 - Draining the heating system - 1

Only qualified personnel must carry out the commissioning and operation of the boiler and instruct the user.

  • Check that the power supply has been switched OFF.
  • Check the boiler and system for leaks. Prevent water leaks.
    • Install AM display module or BM2 programming module in the boiler.
  • Install / connect extension modules, if present.
  • Check wiring of power supply, pumps, sensors and modules.

- Check location and seating of fitted components.

- Check all connections and component unions for leaks.

- Check that all flue gas accessories have been correctly installed.

- Open the shut-off valves in flow and return.

- Open the gas shut-off valve.

- Switch on the power supply.

- Switch the system ON/OFF switch on the control unit to ON.

- Check control parameters (e.g. system configuration HG40).

- If the system water pressure falls below 0.8 bar, top up with water until a pressure of 1.5 to max. 2.5 bar has been reached.

- Check the condensate drain.

- Familiarise customers with the operation of the boiler with the aid of the operating and installation instructions and advise them of the required water treatment for fill and top-up water.

- Complete the commissioning report and hand over the instructions to the customer.

Energy savings

  • Instruct the customer about energy saving options.
  • Refer your customer to the section "Information for energy efficient operation" in the operating instructions.

30. Checking the gas supply pressure

Countries, gas categories and connection pressures

Caution

If the supply pressure is outside the specified range, adjustments must not be carried out and the boiler must not be started.

Check the gas supply pressure (gas flow pressure)

WOLF MGK-2-470 - Caution - 1

Work on gas components must only be performed by a licensed gas fitter. Work that is carried out incorrectly may lead to gas escaping, resulting in a risk of explosion, suffocation or poisoning.

  • Switch ON/OFF switch on the appliance to OFF.
  • Release the plug at the test nipple with two turns.
  • Slowly open the gas shut-off valve.
  • Bleed off escaping gas via a hydraulic seal until no more air escapes.
  • Connect the differential pressure tester at the pressure test nipple to "+" with "-" against atmosphere.
  • Switch the ON/OFF switch to ON.

After starting the boiler, check the supply pressure at the differential pressure tester.

  • Switch the ON/OFF switch to OFF. Close the gas shut-off valve.
  • Remove the differential pressure tester.

Re-seal the test nipple with the plug.

  • Open the gas shut-off valve.
  • Check the test nipple is gas-tight.
  • Refit the burner hood.

WOLF MGK-2-470 - Re-seal the test nipple with the plug. - 1

If any screws are not tightened, there is a danger of gas escaping, leading to a risk of explosion, suffocation or poisoning.

CountryAppliance categorySupply pressure in mbar
Natural gasNatural gas
Nom.Min. Max.
EN I2ELL 20 18 25
AT, BG, CH, CZ, DK, EE, ES, FI, GB, GR, HR, IE, IS, IT, LT, LV, NO, PT, RO, RU, SE, SI, SK, TRI2H 2018 25
LU I2E 20 18 25
PLI2ELw20 1825
BEI2E(R)20/2518 30
FRI2Esi20/2518 30
HUI2HS25 1830
NLI2L25 1830

WOLF MGK-2-470 - Re-seal the test nipple with the plug. - 2

natural_image Close-up of a mechanical device with a yellow circular component and a magnified inset showing a probe tip (no visible text or symbols)

Pressure test nipple

31. Changing the gas type, CO_2 setting

Carry out the adjustments in the following sequence. At the factory, the gas combination valve has been set up for natural gas E (G20).

A) CO_2 setting at the upper load (emissions test mode)

  • Release the screws on the burner hood (top).
  • Remove the burner hood.
  • Remove screw from the test port of the condensate trap and insert measuring device.
  • Press the "Emissions test" quick start button on the AM display module or BM2 programming module.
  • At full load, measure the CO_2 value, which should be 9.3% ± 0.3% for natural gas E/H/LL.
  • If required, adjust the CO_2 content at the gas combination valve with a screwdriver as shown in the picture.

WOLF MGK-2-470 - A) CO_2 setting at the upper load (emissions test mode) - 1

natural_image Industrial equipment setup with pipes and a white cylindrical tank, no visible text or symbols

Test port on the condensate trap

measure the CO₂ value, which should 3 % for natural gas E/H/LL. adjust the CO₂ content at the gas valve with a screwdriver as shown in the

31. Changing the gas type, CO_2 setting

B) CO_2 setting at the lower load (soft start)

  • Restart the gas condensing boiler.
  • Approx. 30 seconds after burner start, check the CO 2 content with the CO 2 measuring instrument. This should be 9.1 % ± 0.3 % for natural gas E/H/LL and can be corrected with a 2.5 mm Allen button at the gas combination valve as shown in the picture.
  • Perform this adjustment at minimum load (180 sec. after burner start).
  • Repeat the start phase if necessary to perform the adjustment.

L offset

WOLF MGK-2-470 - B) CO_2 setting at the lower load (soft start) - 2

natural_image Close-up of a mechanical device with a yellow circular component and blue cables, no visible text or symbols.

C) Completing the adjustments

  • Shut down the boiler.
  • Re-seal the test ports and check for tightness.
  • Refit the burner hood.
  • Screw in screws on the burner hood (top).
  • Check the gas type on the type plate and change if necessary. If changed to natural gas LL, cut out label "Adjusted to LL - G25 - 20 mbar" and affix to the type plate.

Eingestellt auf 2E - G20 - 20 mbar 2H - G20 - 20 mbar Eingestellt auf 2LL - G25 - 20 mbar Adjusted to 2H - G20 - 20mbar Ajustada a gas 2H - G20 - 20 mbar Réglée sur 2Es - G20 - 20 mbar Réglée sur 2Ei - G25 - 25 mbar Réglée sur 2E - G20 - 20 mbar Regolato per gas 2H - G20 - 20 mbar Nastaveno na 2H - G20 - 20 mbar Beallitva 2S - G25.1 - 25 mbar DE / AT DE GB ES FR FR LU IT CZ HU 50/118/10/215

Commissioning steps Test values or confirmation
1.) Gas typeNatural gas E/H □Natural gas LL □Wobbe index ____ kWh/m3Calorific value, heating ____ kWh/m3
2.) Gas supply pressure checked?
3.) Gas leak test carried out?
4.) Balanced flue system checked?
5.) Water connections checked for leaks?
6.) Siphon filled?
7.) System flushed?
8.) System filled and water treatment carried out in line with "Design information, water treatment"?pH value setTotal hardness set____ pH value____ °dH
9.) No chemical additives (inhibitors, antifreeze) added?
10.) Boiler and system vented?
11.) System pressure 1.5 - 2.5 bar?
12.) Gas type and output entered on label?
13.) Function test carried out?
14.) Flue gas testGross flue gas temperatureVentilation air temperatureNet flue gas temperatureCarbon dioxide content (CO _2 ) or oxygen content (O _2 )Carbon monoxide content (CO)____ t _A [°C]____ t _A [°C]____ (t _A -t _L ) [°C]____ %____ ppm
15.) Casing fitted?
16.) System user trained, documentation handed over?
17.) Commissioning confirmed?____ □

General notes

Where necessary, adapt the installation examples to the relevant building regulations and requirements in your country/region. Discuss any questions relating to the installation of inspection covers and ventilation apertures with your local flue gas inspector.

Flues inside chimney ducts must have secondary ventilation along their entire length and must terminate above the roof.

Flue gas cascades must be sized in accordance with EN 13384-2.

The requirements for installation rooms are specified in the building regulations or combustion equipment ordinances of the relevant countries. Also observe DVGW-TRGI 1986 regarding the room ventilation.

WOLF MGK-2-470 - General notes - 1

low outside temperatures, the water vapour contained in the flue gas may condense and freeze on the balanced flue. This ice may fall from the roof causing injuries or material losses. Prevent ice from falling by taking on-site measures, e.g. installing a snow guard.

Connection to a type C63 combustion air and flue system that has not been tested together with the gas combustion equipment

Original Wolf components have been optimised over many years and are designed for use with Wolf condensing boilers. If using third party equipment that is only CE-approved, the installer will be responsible for the correct sizing and perfect functioning of the system. Faults, material losses and injuries resulting from incorrect pipe lengths, excessive pressure drop, premature wear with escaping flue gas and condensate or incorrect functioning, e.g. through components working loose, are excluded from our warranty if CE-approved third-party equipment is used.

Caution

If the combustion air is drawn from the duct, the duct must be free from contamination.

Connection to the ventilation air system and the flue

The unobstructed cross-section of flues must be able to be inspected. Therefore, install an appropriate cleaning and/or inspection aperture inside the boiler room; agree suitable arrangements with your local flue gas inspector.

Flue connections are created using couplings and gaskets. Always arrange couplings against the direction of the condensate flow.

WOLF MGK-2-470 - Connection to the ventilation air system and the flue - 1

outside ducts must not be routed through other installation rooms, otherwise there would be a risk of the transfer of fire and there would be no mechanical protection.

Cafugood

mbustion air must not be drawn from chimneys previously used to carry flue gases from oil or solid fuel boilers.

WOLF MGK-2-470 - Connection to the ventilation air system and the flue - 2

the balanced flue or flue outside ducts with spacer brackets with a minimum clearance of 50 cm from the flue outlet or upstream/downstream of diverters to prevent the pipe joints being pulled apart. If this is not done, there is a danger of poisoning caused by escaping flue gas. Furthermore, boiler damage may result.

WOLF MGK-2-470 - Connection to the ventilation air system and the flue - 3

To prevent flue gas escaping, a positive pressure flue cascade is only permitted with a tested flue gas damper (part no. 2484637).

WOLF MGK-2-470 - Connection to the ventilation air system and the flue - 4

Install the ventilation air system / flue with a slope of at least 3° towards the gas condensing boiler. Spacer brackets should be fitted to secure the equipment in position. In the worst case scenario, a lesser slope of the balanced flue may lead to corrosion or operating faults.

Always

bevel or deburr trimmed flues to ensure gas-tight installation of pipe joints. Ensure that gaskets are correctly fitted. Remove all contamination prior to installation - never fit damaged parts.

davon

sizing flue systems in accordance with DIN EN 13384-2 (cascade), maintain a maximum overpressure of up to 50 Pa in the connection to the header line; this should also not be exceeded.

Caution

As protection against contamination during the building phase, we recommend using the ventilation air filter part no. 8751390. The ventilation air filter is plugged onto the air intake. Keep the door of the condensing boiler shut during the building phase. After completing the building phase, remove the filter.

34. HCM2 wiring diagram

WOLF MGK-2-470 - HCM2 wiring diagram - 1

flowchart
graph TD
    A["Fan 230 V AC"] --> B["Heating circuit"]
    B --> C["Heating circuit"]
    C --> D["Mounting plate"]
    D --> E["Pump contactor Mains contactor"]
    E --> F["Front panel"]
    F --> G["Reset"]
    G --> H["ON/OFF switch Service PCB AM/BM2 contact PCB ISM7i (optional)"]
    H --> I["Condensate pump"]
    I --> J["Boiler water temperature sensor"]
    J --> K["Water pressure sensor"]
    K --> L["Return temperature sensor"]
    L --> M["Control of variable speed heating circuit pump ZHP"]
    M --> N["Gas pressure switch"]
    N --> O["Fault message, condensate pump (jumper in plug)"]

    subgraph HCM-2
        P["X1: PE Nez L1 N N X1: NEz L1-N S X1: NEz L1-S X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NEz L1-N X1: NO NC X6:1 X6:1<br>    end<br>    <br>    subgraph Front panel<br>        P --> Q[E1 GND a b E2 GND AF GND SF GND EBus GND"]
        Q --> R["X10:1 +5V GND +5V eBus"]
        R --> S["X9:1 +23V GND +23V eBus"]
        S --> T["X10:1 +5V GND +5V eBus"]
        T --> U["X9:1 +23V GND +23V eBus"]
        U --> V["X10:1 +5V GND +5V eBus"]
        V --> W["X9:1 +23V GND +23V eBus"]
        W --> X["X10:1 +5V GND +5V eBus"]
        X --> Y["X9:1 +23V GND +23V eBus"]
        Y --> Z["X10:1 +5V GND +5V eBus"]
        Z --> AA["X9:1 +23V GND +23V eBus"]
        AA --> AB["X10:1 +5V GND +5V eBus"]
        AB --> AC["X9:1 +23V GND +23V eBus"]
        AC --> AD["X10:1 +5V GND +5V eBus"]
        AD --> AE["X9:1 +23V GND +23V eBus"]
        AE --> AF["X10:1 +5V GND +5V eBus"]
        AF --> AG["X9:1 +23V GND +23V eBus"]
        AG --> AH["X10:1 +5V GND +5V eBus"]
        AH --> AI["X9:1 +23V GND +23V eBus"]
        AI --> AJ["X10:1 +5V GND +5V eBus"]
        AJ --> AK["X9:1 +23V GND +23V eBus"]
        AK --> AL["X10:1 +5V GND +5V eBus"]
        AL --> AM["X9:1 +23V GND +23V eBus"]
        AM --> AN["X10:1 +5V GND +5V eBus"]
        AN --> AO["X9:1 +23V GND +23V eBus"]
        AO --> AP["X10:1 +5V GND +5V eBus"]
        AP --> AQ["X9:1 +23V GND +23V eBus"]
        AQ --> AR["X10:1 +5V GND +5V eBus"]
        AR --> AS["X9:1 +23V GND +23V eBus"]
        AS --> AT["X10:1 +5V GND +5V eBus"]
        AT --> AU["X9:1 +23V GND +23V eBus"]
        AU --> AV["X10:1 +5V GND +5V eBus"]
        AV --> AW["X9:1 +23V GND +23V eBus"]
        AW --> AX["X10:1 +5V GND +5V eBus"]
        AX --> AY["X9:1 +23V GND +23V eBus"]
        AY --> AZ["X10:1 +5V GND +5V eBus"]
        AZ --> BA["X9:1 +23V GND +23V eBus"]
        BA --> BB["X10:1 +5V GND +5V eBus"]
        BB --> BC["X9:1 +23V GND +23V eBus"]
        BC --> BD["X10:1 +5V GND +5V eBus"]
        BD --> BE["X9:1 +23V GND +23V eBus"]
        BE --> BF["X10:1 +5V GND +5V eBus"]
        BF --> BG["X9:1 +23V GND +23V eBus"]
        BG --> BH["X10:1 +5V GND +5V eBus"]
        BH --> BI["X9:1 +23V GND +23V eBus"]
        BI --> BJ["X10:1 +5V GND +5V eBus"]
        BJ --> BK["X9:1 +23V GND +23V eBus"]
        BK --> BL["X10:1 +5V GND +5V eBus"]
        BL --> BM["X9:1 +23V GND +23V eBus"]
        BM --> BN["X10:1 +5V GND +5V eBus"]
        BN --> BO["X9:1 +23V GND +23V eBus"]
        BO --> BP["X10:1 +5V GND +5V eBus"]
        AP --> BQ["E Bus X53 8 9 10 1 2 4 6 8 9 10 1 2 4 6 8 9 10 1 2 4 6 8 9 10 1 2 4 6 8 9 10 1 2 4 6 8 9 10 1 2 4 6 8 9 10 1 2 4 6 8 9 10 1"] & AD["Front panel"]

34. GBC-P wiring diagram

WOLF MGK-2-470 - GBC-P wiring diagram - 1

flowchart
graph TD
    A["230V L 230V N FE X1 +23V CC TX CC RX GND Res."] --> B["GBC-p"]
    B --> C["V2 N 9 V2 L V1 L V1 N Zünd. N Vent. N Vent. L Zünd. L X2 Ion. 1"]
    B --> D["X3:1"]
    B --> E["X4"]
    B --> F["Gas combination valve"]
    B --> G["Monitoring electrode"]
    B --> H["Gas burner"]
    B --> I["Ignition electrodes"]
    B --> J["Connection for safety circuit provided by operator"]
    B --> K["Flue gas pressure switch"]
    B --> L["Fan PWM signal"]
    B --> M["eHLSC sensor 1"]
    B --> N["eHLSC sensor 2"]
    B --> O["HLSC"]
    B --> P["Flue gas temperature sensor"]

General notes

Never remove, bypass or otherwise disable any safety or monitoring equipment. The boiler must only be operated if it is in perfect technical condition. Any faults and damage with potential impact on safety and which might limit the safe use of the equipment must be remedied immediately by a qualified contractor. Only replace faulty components and equipment with original Wolf spare parts.

Faults and warnings are shown in plain text on the display of the control accessories – AM display module or BM2 programming module – and correspond to the messages listed in the following tables.

A warning/fault symbol on the display (symbol: triangle with exclamation mark) indicates an active warning or fault message. A lock symbol (symbol: lock) indicates that the current fault message has caused a lockout of the boiler. The duration of the current message is also shown.

Caution Warning messages do not need to be acknowledged and do not lead directly to the boiler being switched OFF. However, the causes of the warnings can lead to malfunctions of the boiler / system or faults and should therefore be repaired by an expert.

Caution Faults must only be repaired by qualified expert personnel. If a lockout fault message is acknowledged several times without fixing the cause of the problem, this can lead to damage to parts or to the system.

The control unit automatically acknowledges faults such as defective temperature sensors or other sensors if the part concerned has been replaced and plausible test values have been supplied.

Notification Warning 2 HC pressure Warning since 0 min

Notification Fault 107 HC pressure Fault since 0 min

Procedure for faults:

  • Read fault message.
  • Determine cause of fault using the table below and remedy it.
  • Reset fault with "Fault reset" button or in the contractor menu under "Acknowledge fault". If the fault message cannot be acknowledged, high temperatures at the heat exchanger might be preventing a reset.
  • Check that the system is functioning correctly.

Procedure for warnings:

  • Read warning message.
  • Determine cause of warning using the table below and remedy it.
  • With warnings, there is no need for fault acknowledgement.
  • Check that the system is functioning correctly.

Fault history:

A fault history can be called up and the most recent fault messages displayed in the contractor menu of the AM display module or BM2 programming module.

Fault history Boiler sensor faulty 12 Dur. 0 min Number 1 of 3

Fault
The following faults are in the system:

Fault codeFault Cause Remedy
1 HLSC excess temp. The high limit safety cut-out (thermostat) has respondedThe boiler water temperature has exceeded 107 °CTest heating circuit pump, vent system, press reset, clean heat exchanger
2 TL excess temp. One of the temperature sensors eHLSC1 or eHLSC2 has exceeded the high limit safety cut-out limit (105 °C)Test heating circuit pump, test sensors, vent system, press reset, clean heat exchanger
3 eHLSC drift Temperature difference between temperature sensors eHLSC1 and eHLSC2 > 6 °CTest sensors, test heating circuit pump, vent system, press reset, clean heat exchanger
4 No flame At burner start, no flame at the end of the safety time, monitoring electrode faulty, ignition electrode faulty, ignition transformer faultyTest monitoring electrode, ignition electrode and ignition transformer, press reset, check gas pressure
5 Flame failure Flame failure during operation, monitoring electrode faulty, flue gas path blocked, condensate drain blockedTest monitoring electrode, press reset, test flue system, test condensate drain
6 TC excess temp. One of the temperature sensors eHLSC1 or eHLSC2 has exceeded the limit of the temperature limiter (97 °C)Test heating circuit pump, vent system, test sensors, press reset, clean heat exchanger
7 TL flue excess temp. The flue gas temperature has exceeded the limit of the TBA shutdown temperatureClean heat exchanger, test sensors, check flue system
8 Flue gas damper does not switchFlue gas damper contact (E1) closes or does not open on demand; output A1 does not activate flue gas damperCheck flue gas damper and wiring, check settings HG13 and HG14
9 Fault code unknown This fault is not known in this software Check software version of the PCBs
10 eHLSC sensor faulty Temperature sensor eHLSC1, eHLSC2 or sensor lead has short circuit or breakCheck sensor and lead
11 Flame pretenceA flame is recognised before the burner startsPress reset, test monitoring electrode
12 Boiler sensor faultyBoiler sensor > 105 °C, boiler sensor or sensor lead has short circuit or breakCheck sensor and lead
13 FlueG sensor faultyFlue gas sensor or sensor lead has short circuit or breakCheck sensor and lead
14 DHW sensor faultyDHW sensor (cylinder sensor) or sensor lead has short circuit or breakCheck sensor and lead
15 Outside temperature sensor faultyOutside temperature sensor or sensor lead has short circuit or breakCheck sensor and lead
16 Rtn sensor faulty Return sensoror sensor lead has short circuit or breakCheck sensor and lead
18 Ext. safety circuitThe contact for the external safety circuit has responded (maximum pressure limiter, low water indicator, etc.)Press reset, repair fault
20 GCV relay testThe internal relay test failedPress reset, replace burner control unit
24 Fan speed <The fan does not reach the set speedTest the fan's PWM and power cable, test fan, press reset
26 Fan speed > The fan does not stop Test the fan's PWM and power cable, test fan, press reset, test flue system for strong draught
30 CRC burner control unit The EEPROM record is invalid Switch the power supply OFF and ON. If unsuccessful, replace the burner control unit.
32 Fault in 23 V AC supply 23 V AC supply outside the permissible range (e.g. short circuit) Switch the power supply OFF and ON. If unsuccessful, replace the control PCB.
35 BBC missing Boiler chip card has been removed or not correctly inserted Refit the correct boiler chip card
36 BCC faulty Faulty boiler chip card Replace boiler chip card
37 Incorrect BCC The boiler chip card is incompatible with the control PCB Refit the correct boiler chip card
38 BCC update required Boiler chip card fault, PCB requires a new boiler chip card (replacement) Reinsert boiler chip card, replace boiler chip card
39 BCC system error Faulty boiler chip card Replace boiler chip card
41 Flow monitoring Return temperature > flow temperature Vent system, check heating circuit pump, test flow and return pipe connection
42 Condensate pump is not pumping anything out Faulty condensate pump, drain line blocked, no power supply to pump Check pump, check drain line, check mains plug and fuse
44 Flue gas pressure switch Flue system back pressure too high Heat exchanger contaminated, check flue system, test flue gas damper, press reset
52 Max. cylinder heating time Cylinder heating takes longer than permitted Test DHW sensor (cylinder sensor) and sensor lead, press reset
53 IO control deviatn Wind recognition, severe storm, insufficient ionisation signal during operation, burner contaminated Test monitoring electrode, check flue system, press reset, clean burner
60 Siphon backpressure Siphon or flue system is blocked Clean siphon; test flue system, ventilation air, gas supply pressure (flow pressure) and monitoring electrode
78 Header sensor fault Faulty sensor or lead Check sensor and lead; replace if required
90 BCU comm error Emergency stop via ChipCom, faulty communication between control PCB and burner control unit Switch the power supply OFF and ON. If unsuccessful, call in a specialist contractor.
95 Prog. mode Burner control unit is controlled by PC No action
96 Reset Reset button pressed too often Switch the power supply OFF and ON. If unsuccessful, call in a specialist contractor
98 Flame amplifier Internal burner control unit fault Monitoring electrode short circuit Press the reset button, and switch the power supply OFF and ON. If unsuccessful, call in a specialist contractor, test monitoring electrode
99 Burner control unit system fault Internal burner control unit fault Switch the power supply OFF and ON. If unsuccessful, call in a specialist contractor.

35. Troubleshooting

Fault codeFault Cause Remedy
107 HCpressure Water pressure too low, water pressure too highTest system pressure, test cable, press reset, test water pressure sensor

Button

Button
BCC Boiler chip card
CRC Cyclic redundancy check
EEPROM Rewritable memory
BCU Burner control unit
GCV Gas combination valve
IO Ionisation signal
HLSC High limit safety cut-out
eHLSC Electronic high limit safety cut-out
TL Temperature limiter
TBA Flue gas high limit safety cut-out
TW Temperature limiter

Warning messages

The following warnings are in the system:

NumberFault Description Cause and remedy
1 BCUreplaced The control PCB hasdetected that the burnercontrol unit has been replacedInsert boiler chip card thatcorresponds to appliance output; ifnecessary,reinsert boiler chip card
2 HCpressure The water pressure hasfallen below thewarning limitCheck the system pressure,test sensors
3 Parameter changed Another boiler chip card has been inserted Make sure that the correct boilerchip card has been inserted,if necessary,reinsert boiler chip card
4 Noflame At the last attempt to start the burner, noflame was detectedWait for another start attempt,test ignition electrode and ignitiontransformer,test monitoringelectrode,test gas connectionpressure
5 Flame failure duringstabilisation timeFlame failure after safety timeFlame failure during operation Monitoring electrode faulty, fluegas path blocked, condensatedrain blocked,test gas connectionpressure
24 Speed below or above limit The fan does not reach the set speed,ordoes not stopTest flue system,test the fan's PWMand power cable
43Many burner startsNumber of burner starts too highToo little heat is being drawn off,tolittle throughput,demand too high

NTC sensor resistances

Boiler sensor, cylinder sensor, outside temperature sensor, return sensor, eHLSC sensor, header sensor

Temp. °CResist. ΩTemp. °CResist. ΩTemp. °CResist. ΩTemp. °CResist. Ω
-21 51393 14 823349 1870 84552
-20 48487 15 785750 1800 85535
-19 45762 16 750151 1733 86519
-18 43207 17 716252 1669 87503
-17 40810 18 684153 1608 88487
-16 38560 19 653654 1549 89472
-15 36447 20 624755 1493 90458
-14 34463 21 597256 1438 91444
-13 32599 22 571057 1387 92431
-12 30846 23 546158 1337 93418
-1129198 245225 59 1289 94 406
-10 27648 25 500060 1244 95393
-926189 264786 61 12200 96 382
-82481627458262115897371
-72352328438863111798360
-622305 294204 64 1078 99 349
-521157304028651041100339
-420075 313860 66 1005101 330
-319054 323701 67971 102320
-21809133354968938103311
-117183 343403 69906 104302
016325 353265 70876 105294
115515 363133 71846 106285
214750 373007 72818 107277
314027 382887 73791 108270
413344 392772 74765 109262
51269740266275740110255
61208641255876716111248
71150842245877693112241
81096143236278670113235
91044244227179670114228
10995245218380628115222
11948746210081608116216
12904647202082589117211
13862948194483570118205

38. Technical parameters according to EU regulation no. 813/2013

Type MGK-2-390
Condensing boiler [yes/no] yes
Low temperature boiler (**) [yes/no] no
B11 boiler [yes/no] no
Cogeneration space heater [yes/no] no
If yes, equipped with a supplementary heater[yes/no] -
Combination heater [yes/no] no
Item Symbol Unit
Rated heat output PratedkW367
Useful heat output at rated heat output and high-temperature regime (*) P_4 kW366,7
Useful heat output at 30% of rated heat output and low-temperature regime (**) P_1 kW121,6
Auxiliary electricity consumption at full loadelmaxkW0,410
Auxiliary electricity consumption at part loadelminkW0,042
Auxiliary electricity consumption in standby mode P_SB kW0,011
Seasonal space heating energy efficiency n_s %93
Useful efficiency at rated heat output and high-temperature regime (*) n_4 %88,9
Useful efficiency at 30% of rated heat output and low-temperature regime (**) n_1 %97,0
Standby heat loss P_city kW0,401
Ignition burner power consumption P_ing kW0,000
Emissions of nitrogen oxides NO_x mg/kWh34
Contact detailsWolf GmbH, Industriestraße 1, D-84048 Mainburg

(*) High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet).

DECLARATION OF CONFORMITY

(to ISO/IEC 17050-1)

Number: 3063772

Issued by: Wolf GmbH

Address: Industriestrasse 1, D-84048 Mainburg

Product: MGK-2 gas condensing boiler

The product described above conforms to the requirements specified in the following documents:

§ 6, 1. BlmSchV, 26/01/2010

DIN EN 437, 09/2009

DIN EN 483, 06/2000

DIN EN 677, 08/1998

DIN EN 60335-1, 10/2012

DIN EN 60335-2-102, 07/2010

DIN EN 55014-1, 05/2012

In accordance with the following Directives

2009/142/EC (Gas Appliances Directive)

2004/108//EC (EMC Directive)

2006/95/EC (Low Voltage Directive)

2009/125/EG (ErP Directive)

2011/65/EU (RoHS Directive)

this product is identified as follows:

CE 0085

Mainburg, 15/07/2015

WOLF MGK-2-470 - DECLARATION OF CONFORMITY - 2

natural_image Abstract curved line drawing with no text or symbols

Gerdewan Jacobs

Technical Director

Galmia

Klaus Grabmaier

Product approval

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : WOLF

Model : MGK-2-470

Category : Central heating boiler