Product type Ultra-High Frequency (UHF) Partial Discharge Detector
Brand Megger
Model UHF PDD
Category Measurement
Measurement principle Detection of partial discharge activity using UHF signals
Frequency range 300 MHz to 3 GHz typical UHF PD band
Applications Gas-insulated switchgear (GIS), transformers, cables and high-voltage assets
Display Backlit LCD showing signal strength and measurement data
Controls Power, sensitivity adjustment and mode selection
Power supply Integral rechargeable lithium-ion battery, 7.2 V typical
Battery life Approximately 8 hours of continuous operation
Charger input 100-240 V AC, 50/60 Hz via supplied adapter
Dimensions 200 mm x 100 mm x 45 mm approximate
Weight 0.6 kg approximate (1.3 lb)
Enclosure material Robust ABS plastic with rubber overmold
Operating temperature -10 °C to +50 °C
Storage temperature -20 °C to +70 °C
Main functions Detection, localized measurement and recording of partial discharge signals
Outputs Headphone output and USB data connection
Accessories included UHF sensor, charger, carrying case and instruction manual
Maintenance and cleaning Wipe with a dry soft cloth, do not use solvents or abrasive materials
Safety IEC 61010-1 compliant, use with appropriate high-voltage safety precautions
Spare parts and repairability Replaceable battery and sensor, service by authorized Megger service center
General information Delivered with user manual in PDF format and 12-month warranty

Frequently Asked Questions - UHF PDD Megger

How do I use the Megger UHF PDD to detect partial discharge?
Connect the included UHF sensor to the detector, switch on the device and adjust the sensitivity to the desired level. Move the sensor slowly around the test object while watching the signal strength display and listening through the headphone output for characteristic partial discharge pulses.
What types of partial discharge can be detected?
The UHF PDD can detect partial discharges such as internal voids, surface discharges and corona activity in high-voltage equipment. The ultra-high-frequency method is particularly sensitive to fast current pulses generated during discharge events.
Can the UHF PDD be used on live equipment?
Yes, the UHF detection method is non-invasive and can be used on energised systems, for example GIS and cable terminations. Always follow the safety instructions in the manual and use the appropriate personal protective equipment.
How do I distinguish partial discharge signals from external noise?
Compare the signal shape and repetition pattern on the display, use the headphone output to listen to the acoustic signature, and change sensor position. Typical PD signals are repetitive and synchronised with the power frequency, while noise tends to be broad-band and random.
How do I charge the battery?
Connect the supplied AC charger to the charging input on the side of the device and plug it into a 100-240 V AC outlet. The battery indicator on the display shows charging status. A full charge typically takes 2 to 3 hours.
What does the display show during measurement?
The backlit LCD shows the relative signal amplitude, battery level and the selected sensitivity mode. On some units it can also display a pulse count or a simple bar graph for easier comparison.
How should I clean and maintain the UHF PDD?
Clean the casing and display with a dry soft cloth. Do not use solvents, sprays or abrasive cleaners. Keep the connector between the sensor and detector clean and dry, and store the unit in the provided carrying case when not in use.
How long does the battery last on a full charge?
The integral rechargeable lithium-ion battery provides approximately 8 hours of continuous operation. This may vary with ambient temperature, display brightness and the use of the headphone output.
Is the Megger UHF PDD waterproof?
No, the UHF PDD is not waterproof. It is intended for indoor or sheltered outdoor use. Avoid exposing the instrument to rain, moisture or condensation, and do not operate it in a humid environment without proper protective housing.
What accessories are included with the UHF PDD?
The instrument is delivered with a UHF sensor, an AC charger, a carrying case and the instruction manual in PDF format. Optional accessories such as a headphone set may be available from Megger dealers.

User questions about UHF PDD Megger

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

Your email remains private: it is only used to notify you if someone answers your question.

No questions yet. Be the first to ask one.

Download the instructions for your Measurement in PDF format for free! Find your manual UHF PDD - Megger and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. UHF PDD by Megger.

USER MANUAL UHF PDD Megger

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Megger

Model : UHF PDD

Category : Measurement