Product Type Air-Cooled Screw Chiller
Brand Daikin
Model EWAD510T-SLC2
Cooling Capacity (Nominal) 510 kW
Compressor Type Screw Compressor
Refrigerant R-134a
Power Supply 400 V, 3-phase, 50 Hz
Water Flow Rate (Evaporator) Approx. 88 m³/h at 5 K ΔT
Water Connections 2 × DN125 flanged
Air Heat Exchanger Microchannel aluminium coils
Control System Microprocessor with backlit display
Safety Devices High/low pressure switches, overload protection, antifreeze thermostat
Dimensions (L × W × H) 3500 × 1400 × 1900 mm
Weight (Operating) 3200 kg
Sound Power Level 95 dB(A)
Minimum Outdoor Temperature -10 °C (with low ambient option)
Standard Package Wooden crate, protective film
Installation Certified technicians, clearance for airflow
Maintenance Quarterly coil cleaning, annual water filter inspection
Spare Parts & Repair Compressors, fans, pressure controls, controller boards

Frequently Asked Questions - EWAD510T-SLC2 DAIKIN

What refrigerant does the Daikin EWAD510T-SLC2 use?
The Daikin EWAD510T-SLC2 uses R-134a refrigerant, a hydrofluorocarbon with zero ozone depletion potential.
What is the nominal cooling capacity?
The nominal cooling capacity is 510 kW, based on standard AHRI conditions.
What electrical supply is required?
The chiller requires a 400 V, 3-phase, 50 Hz power supply. A dedicated electrical circuit with appropriate protection is mandatory.
How often should condenser coils be cleaned?
Clean the condenser coils at least quarterly to maintain heat exchange efficiency. Use a soft brush or low-pressure water, avoiding damage to fins.
Can the chiller operate during cold weather?
Yes, with the low-ambient option, operation is possible down to -10°C. For lower temperatures, additional winterization is required.
How do I reset the chiller after a high-pressure alarm?
Press the reset button on the control panel after correcting the cause. If the alarm persists, inspect the condenser fans and coil cleanliness.
What water flow rate is needed for the evaporator?
The design flow rate is approximately 88 m³/h for a 5 K temperature difference. Adjust according to the project specifications.
How to winterize the chiller?
Drain the water circuit completely and add food-grade antifreeze to the evaporator if needed. Shut off power and protect the control box.
Where is the serial number located?
The serial number is on the nameplate near the electrical panel. Record it for future service requests.
Is the compressor speed controllable?
The EWAD510T-SLC2 features a fixed-speed screw compressor. Capacity control is achieved via slide valve modulation.

User questions about EWAD510T-SLC2 DAIKIN

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air conditioner in PDF format for free! Find your manual EWAD510T-SLC2 - DAIKIN and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EWAD510T-SLC2 by DAIKIN.

USER MANUAL EWAD510T-SLC2 DAIKIN

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : DAIKIN

Model : EWAD510T-SLC2

Category : Air conditioner