| Product Type | Three-phase online double-conversion UPS |
| Model | HSTP3T30KE-C |
| Brand | CyberPower |
| Rated Power | 30 kVA / 27 kW |
| Input Voltage | 3-phase 380V/400V/415V |
| Output Voltage | 3-phase 380V/400V/415V (selectable) |
| Frequency Range | 40-70 Hz |
| Output Frequency | 50/60 Hz ± 0.5% |
| Waveform | Pure sine wave |
| Transfer Time | 0 ms (online double conversion) |
| Battery Type | External sealed lead-acid (VRLA) batteries |
| Battery Management | Automatic battery test, deep discharge protection, intelligent battery charging |
| Display | LCD touch screen with status indicators |
| Communication Ports | RS-232, USB, SNMP slot, and EPO (emergency power off) connector |
| Cooling | Forced air cooling with intelligent fan speed control |
| Protection Features | Overload, short circuit, overvoltage, undervoltage, and overheat protection |
| Noise Level | ≤ 65 dB @ 1 meter |
| Operating Temperature | 0°C to 40°C |
| Humidity | 20% to 90% non-condensing |
| Dimensions (W x D x H) | 600 x 800 x 1200 mm |
| Weight | Approximately 250 kg (without external battery cabinet) |
| Safety Standards | CE, ISO 9001 certified |
| Reparability | Modular design with easily replaceable fans and power modules |
| Maintenance | Regular battery inspection, clean air filters, keep ventilation clear |
Frequently Asked Questions - HSTP3T30KE-C CyberPower
What is the recommended battery maintenance schedule?
Inspect the batteries every 3 months. Check for corrosion and ensure terminals are clean and tight. Perform a professional load test annually and replace batteries every 3-5 years or when runtime drops below 80% of original.
How do I perform an emergency power off (EPO)?
Connect the EPO switch to the designated port on the rear panel. Pressing the EPO button immediately cuts all UPS output power, including bypass. For system restart, ensure the EPO is reset and the input breaker is closed.
Can the UPS be connected to a generator?
Yes, the HSTP3T30KE-C is generator compatible. Set the input frequency range to a wide window (40-70 Hz) to accommodate unstable generator output. Verify the generator’s neutral and grounding to match the UPS.
What is the transfer time between power sources?
The UPS uses online double-conversion technology, meaning the inverter continuously powers the load. Therefore, the transfer time is 0 ms during normal operations and when switching to battery or bypass.
How can I monitor the UPS status remotely?
Use the included RS-232 or USB port to connect to a computer with CyberPower PowerPanel management software. For network monitoring, install an optional SNMP/HTTP card in the communication slot to view status via web browser.
What are the steps for installation?
Ensure adequate ventilation and clearance. Connect the input power to the dedicated 3-phase breaker, then connect the load to the output terminals. Ground the UPS properly. Do not connect the UPS before checking output voltage and polarity.
How do I replace the internal fans?
The fans are hot-swappable and located behind the front panel. Disengage the fan lock, slide the fan out, and insert a new one. Ensure the airflow direction matches the arrow on the chassis.
What does the LCD display show?
The LCD touch screen shows real-time data including input/output voltage, frequency, load percentage, battery status, and alarm messages. Navigate through menus using the touch interface to configure settings.
Is the UPS compatible with networking equipment?
Yes, the pure sine wave output and 0 ms transfer time protect sensitive electronics such as servers, switches, and routers. The UPS includes surge protection and noise filtering to safeguard your network.
What should I do if the UPS emits a continuous beep?
A continuous beep indicates a serious fault (e.g., overload, short circuit, or battery failure). Check the LCD for error codes. Reduce the load, inspect battery connections, and if the alarm persists, contact technical support.