| Product Type | Replacement Battery |
| Brand | CyberPower |
| Model | CPS240PAU |
| Battery Chemistry | Sealed Lead-Acid (SLA) |
| Voltage | 12V DC |
| Capacity | 5Ah |
| Terminal Type | F1 (0.187-inch spade connectors) |
| Dimensions (L x W x H) | 90 x 70 x 102 mm |
| Weight | 1.8 kg (3.97 lbs) |
| Rechargeable | Yes |
| Maintenance | Maintenance-free |
| Safety Features | Valve-regulated, spill-proof |
| Operating Temperature Range | 0°C to 40°C |
| Charging Voltage | 13.8V to 14.4V (float) |
| Backup Time | Varies with load (typical 5-15 minutes at full load for 240VA UPS) |
| Application | Uninterruptible Power Supply (UPS) |
| Compatible UPS Models | CyberPower CPS240AVR, CPS325AVR, and similar |
| Warranty | 1-year limited |
| Package Quantity | 1 battery |
| Expected Life | 3-5 years (typical) |
| Disposal | Recycle according to local regulations |
Frequently Asked Questions - CPS240PAU CyberPower
What is the CyberPower CPS240PAU battery compatible with?
The CPS240PAU is a replacement battery designed for select CyberPower UPS models, including the CPS240AVR and similar units. Always check your UPS manual for compatibility.
How do I install the CPS240PAU battery?
Turn off and unplug the UPS, remove the battery compartment cover, disconnect the old battery wires, insert the new battery, reconnect the wires securely, and replace the cover. Refer to your UPS user manual for detailed instructions.
What is the expected lifespan of this battery?
The typical lifespan is 3 to 5 years depending on usage, charging cycles, and ambient temperature. Replace the battery when backup time noticeably decreases.
How should I maintain the battery?
This battery is maintenance-free. Keep the terminals clean, avoid deep discharges, and store in a cool, dry place when not in use.
How long will the battery provide backup power?
Backup time depends on the load. For a typical 240VA UPS at full load, expect 5 to 15 minutes. At half load, backup time can be longer.
Can I use this battery in other devices?
Yes, it can power any device compatible with a 12V 5Ah battery, but ensure the voltage and connectors match. It is ideal for UPS systems, alarms, and emergency lighting.
Is the battery maintenance-free?
Yes, it is a sealed lead-acid battery that requires no water refilling or electrolyte maintenance. Just keep it charged correctly.
How should I store the storage battery?
Store in a cool, dry place away from direct sunlight. For long-term storage, recharge every 3-6 months to prevent over-discharge.
How do I dispose of the battery properly?
Lead-acid batteries are hazardous waste. Do not throw in trash. Return to a local recycling center or a battery retailer that accepts used batteries.
What safety precautions should I follow?
Avoid short circuits, do not charge with incorrect voltage, keep away from open flames, and wear gloves when handling. Sealed lead-acid batteries can release explosive gases if overcharged.
User questions about CPS240PAU CyberPower
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
No questions yet. Be the first to ask one.
Download the instructions for your Battery in PDF format for free! Find your manual CPS240PAU - CyberPower and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. CPS240PAU by CyberPower.