ARUN100LTH4 - Water pump LG - Free user manual and instructions
Find the device manual for free ARUN100LTH4 LG in PDF.
| Product Type | Water Pump |
| Brand | LG |
| Model | ARUN100LTH4 |
| Power Consumption | 100 W |
| Voltage | 230 V ~ 50 Hz |
| Max Flow Rate | 60 L/min |
| Max Head | 8 m |
| Inlet/Outlet Diameter | 1 inch (25 mm) |
| Dimensions (W x H x D) | 30 cm x 25 cm x 20 cm |
| Weight | 8.5 kg |
| Protection Class | IPX4 |
| Insulation Class | F |
| Operating Temperature | 0°C to 40°C |
| Material | Cast Iron Body, Stainless Steel Shaft |
| Connection Type | Threaded (BSP) |
| Maintenance | Periodic cleaning of strainer; check seals annually |
| Safety Features | Thermal overload protection; automatic shut-off |
| Spare Parts Availability | Impeller, mechanical seal, capacitor available |
| Manual Included | Yes, 81 pages in English |
Frequently Asked Questions - ARUN100LTH4 LG
User questions about ARUN100LTH4 LG
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Water pump in PDF format for free! Find your manual ARUN100LTH4 - LG and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ARUN100LTH4 by LG.
USER MANUAL ARUN100LTH4 LG
- Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only. - Please retain this installation manual for future reference after reading it thoroughly.your set and retain it for future reference.
MULTI V™ IV

P/NO : MFL68069301
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
- Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
- Block sunlight with blinds or curtains while you are operating the air conditioner.
- Keep doors or windows closed tightly while you are operating the air conditioner.
- Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
- Speed up the fan to cool or warm indoor air quickly, in a short period of time.
- Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
- Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer's name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product

WARNING
It can result in serious injury or death when the directions are ignored

CAUTION
It can result in minor injury or product damage when the directions are ignored

WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
- The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
- Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
- Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed improperly, electric shock or fire may result.
- Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock, or fire.
- Always ground the product.
- There is risk of fire or electric shock.
- Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
- For re-installation of the installed product, always contact a dealer or an Authorized Service Center. - There is risk of fire, electric shock, explosion, or injury.
- Do not install, remove, or re-install the unit by yourself (customer). - There is risk of fire, electric shock, explosion, or injury.
- Do not store or use flammable gas or combustibles near the air conditioner.
- There is risk of fire or failure of product.
- Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
- Prepare for strong wind or earthquake and install the unit at the specified place. - Improper installation may cause the unit to topple and result in injury.
- Do not install the product on a defective installation stand. - It may cause injury, accident, or damage to the product.
- Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
-
There is the risk of death, injury, fire or explosion.
-
When installing and moving the air conditioner to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
- Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
- Ventilate before operating air conditioner when gas leaked out.
- It may cause explosion, fire, and burn.
- Securely install the cover of control box and the panel.
- If the cover and panel are not installed securely, dust or water may enter the outdoor unit and fire or electric shock may result.
- If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
- Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
Operation
- Do not damage or use an unspecified power cord.
- There is risk of fire, electric shock, explosion, or injury.
- Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
- Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
- Do not touch the power switch with wet hands.
- There is risk of fire, electric shock, explosion, or injury.
- When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
- Be cautious not to touch the sharp edges when installing.
- It may cause injury.
• Take care to ensure that nobody could step on or fall onto the outdoor unit. - This could result in personal injury and product damage.
- Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.

CAUTION
Installation
- Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
- Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
- Keep level even when installing the product.
- To avoid vibration or water leakage.
- Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
- Use power cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
- Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
- Keep the unit away from children. The heat exchanger is very sharp.
- It can cause the injury, such as cutting the finger. Also the damaged fin may result in degradation of capacity.
- When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
- Do not install the product where it is exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operation
- Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
- Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
- Make the connections securely so that the outside force of the cable may not be applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
- Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure, or personal injury.
- Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
- A bad connection may cause water leakage.
- Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspending it at the specified positions on the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
- Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
- Turn on the power at least 6 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
- Do not touch any of the refrigerant piping during and after operation.
- It can cause a burn or frostbite.
- Do not operate the air conditioner with the panels or guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
- Do not directly turn off the main power switch after stopping operation.
- Wait at least 5 minutes before turning off the main power switch. Otherwise it may result in water leakage or other problems.
- Auto-addressing should be done in condition of connecting the power of all indoor and outdoor units. Auto-addressing should also be done in case of changing the indoor unit PCB.
- Use a firm stool or ladder when cleaning or maintaining the air conditioner.
- Be careful and avoid personal injury.
- Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
- There are sharp and moving parts that could cause personal injury.
TABLE OF CONTENTS
2 TIPS FOR SAVING EN-ERGY
3 IMPORTANT SAFETY IN-STRUCTIONS
8 INSTALLATION PROCESS
9 OUTDOOR UNITS IN- FORMATION
11 ENVIRONMENT- FRIENDLY ALTERNATIVE REFRIGERANT R410A
12 SELECT THE BEST LO- CATION
13 INSTALLATION SPACE
13 Individual Installation
15 LIFTING METHOD
16 INSTALLATION
16 The location of the Anchor bolts
17 Foundation for Installation
18 Preparation of Piping
21 Plumbing materials and storage methods
23 REFRIGERANT PIPING INSTALLATION
23 Precautions on Pipe connection / Valve operation
24 PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
24 Preparation Work
25 Pipe Drawing Out during Single / Series connection
27 Refrigerant piping system
40 Refrigerant charging
41 Distribution Method
42 Branch pipe Fitting
46 Leak Test and Vacuum drying
48 Vacuum Mode
49 Thermal insulation of refrigerant piping
50 ELECTRICAL WIRING
50 Caution
52 Control box and connecting position of wiring
53 Communication and Power Cables
54 Wiring of main power supply and equipment capacity
55 Field Wiring
61 Checking the setting of outdoor units
62 Automatic Addressing
65 Group Number setting
66 Cool & Heat selector
67 Static pressure compensation mode
68 Night Low Noise Function
69 Overall defrost mode
70 Setting the ODU address
71 Snow removal & rapid defrost
72 IDU capacity adjusting
73 Target pressure adjusting
74 Comfort Operation
75 Auto Dust Removal
76 Self-Diagnosis Function
79 CAUTION FOR REFRIG-ERANT LEAK
79 Introduction
79 Checking procedure of limiting concentration
81 INSTALLATION GUIDE AT THE SEASIDE
INSTALLATION PROCESS
![graph TD A["Determination of division work"] --> B["Preparation of contract drawings"] B --> C["Sleeve and insert work"] C --> D["Installation of indoor unit"] D --> E["Refrigerant piping work"] E --> F["Drain pipe work"] F --> G["Duct work"] G --> H["Heat insulation work"] H --> I["Electrical work…](/content/2026/07/1525988/images/c8c43efab941e579dda00390910615e4fce6227535a585c73abd7860aff050bc.jpg)

CAUTION
- The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrants such change.
- The thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8 MPa.
- Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)
OUTDOOR UNITS INFORMATION
CAUTION
Combination Ratio(50\~200%)
| Outdoor Number Connection | Ratio |
| Single outdoor units 200% | |
| Double outdoor units 160% | |
| Triple outdoor units 130% |
Notes: * We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and discuss the requirement like below.
- If the operation of indoor unit is more than 130%, the airflow is operated as low in the all indoor units.
- The number of ( ) means the number of Max. connectable indoor units, when the connected capacity of indoor units is in the table above.
Power Supply : 3∅, 400V, 60Hz / 3∅, 380 - 415V, 50Hz
Model Name : ARUN***LTH4
| Unit | 1 Outdoor Unit | |||||
| System(HP) | 8 | 10 12 14 | ||||
| Model | Combination Unit | ARUN080LTH4 | ARUN100LTH4 ARUN120LTH4 ARUN140LTH4 | |||
| Independent Unit | ARUN080LTH4 | ARUN100LTH4 ARUN120LTH4 ARUN140LTH4 | ||||
| Refrigerant Precharged Amount | kg | 6.5 | 6.5 | 8.5 | 8.5 | |
| Ibs | 16.5 | 16.5 | 18.7 | 18.7 | ||
| Number of maximum connectable indoor units | 13(20) | 16(25) 20(30) 23(35) | ||||
| Net Weight | kg | 195 × 1 | 201 × 1 | 235 × 1 | 270 × 1 | |
| Ibs | 430 × 1 | 433 × 1 | 518 × 1 | 595 × 1 | ||
| Dimensions (WxHxD) | mm | (920×1,680×760) × 1 | (920×1,680×760) × 1 | (1,240 × 1,680 × 760) × 1 | (1,240 × 1,680 × 760) × 1 | |
| inch | (36-7/32 × 66-5/32 × 29-29/32) × 1 | (36-7/32 × 66-5/32 × 29-29/32) × 1 | (48-13/16 × 66-5/32 × 29-29/32) × 1 | (48-13/16 × 66-5/32 × 29-29/32) × 1 | ||
| Piping Conections | mm(inch) | ∅ 9.52(3/8) | ∅ 9.52(3/8) | ∅ 12.7(1/2) | ∅ 12.7(1/2) | |
| mm(inch) | ∅ 19.05(3/4) | ∅ 22.2(7/8) | ∅ 28.58(1 1/8) | ∅ 28.58(1 1/8) | ||
| Unit | 1 Outdoor Unit 2 Outdoor Unit | |||||
| System(HP) | 16 18 20 22 | |||||
| Model | Combination Unit | ARUN160LTH4 AR | UN180LTH4 ARUN200 | LTH4 ARUN220LTH4 | ||
| Independent Unit | ARUN160LTH4 AR | UN100LTH4 ARUN100 | LTH4 ARUN120LTH4 | |||
| ARUN080LTH4 AR | UN100LTH4 ARUN100 | LTH4 | ||||
| Refrigerant Precharged Amount | kg | 10 6.5 x 2 6.5 x 2 8.5 + 6.5 | ||||
| lbs | 22 14.3 x 2 14.3 x 2 18.7 + 14.3 | |||||
| Number of maximum connectable indoor units 26(40) 29(45) 32(50) 35(44) | ||||||
| Net Weight | kg | 280 x 1 195 x 1 + 201 x 1 201 x 1 + 201 x 1 235 x 1 + 201 x 1 | ||||
| lbs | 617 x 1 430 x 1 + 433 x 1 433 x 1 + 433 x 1 518 x 1 + 433 x 1 | |||||
| Dimensions (WxHxD) | mm | (1,240 x 1,680 x 760) x 1 | (920x1,680x760) x 1 + (920x1,680x760) x 1 | (920x1,680x760) x 1 + (920x1,680x760) x 1 | (1,240 x 1,680 x 760) x 1 + (920x1,680x760) x 1 | |
| inch | (48-13/16 x 66-5/32 x 29-29/32) x 1 | (36-7/32 x 66-5/32 x 29-29/32) x 1+ (36-7/32 x 66-5/32 x 29-29/32) x 1 | (36-7/32 x 66-5/32 x 29-29/32) x 1+ (36-7/32 x 66-5/32 x 29-29/32) x 1 | (48-13/16 x 66-5/32 x 29-29/32) x 1+ (36-7/32 x 66-5/32 x 29-29/32) x 1 | ||
| Piping Conections | mm(inch) | ∅ 12.7(1/2) | ∅ 15.88(5/8) | ∅ 15.88(5/8) | ∅ 15.88(5/8) | |
| mm(inch) | ∅ 28.58(1 1/8) | ∅ 28.58(1 1/8) | ∅ 28.58(1 1/8) | ∅ 28.58(1 1/8) | ||
| Unit | 2 Outdoor Unit | |||||
| System(HP) | 24 26 28 30 | |||||
| Model | Combination Unit | ARUN240LTH4 AR | UN260LTH4 ARUN280 | LTH4 ARUN300LTH4 | ||
| Independent Unit | ARUN140LTH4 AR | UN160LTH4 ARUN160 | LTH4 ARUN160LTH4 | |||
| ARUN100LTH4 AR | UN100LTH4 ARUN120 | LTH4 ARUN140LTH4 | ||||
| Refrigerant Precharged Amount | kg | 8.5 + 6.5 10 + 6 | 5 10 + 8.5 10 + 8.5 | |||
| Ibs | 18.7 + 14.3 22 + | 14.3 22 + 18.7 22 + 18.7 | ||||
| Number of maximum connectable indoor units | 39(48) 42(52) 45(56) 49 | 60) | ||||
| Net Weight | kg | 270 × 1 + 201 × 1 2 | 80 × 1 + 201 × 1 280 × | 1 + 235 × 1 280 × 1 + | 270 × 1 | |
| Ibs | 595 × 1 + 433 × 1 6 | 7 × 1 + 433 × 1 518 × | 1 + 617 × 1 617 × 1 + | 595 × 1 | ||
| Dimensions (WxHxD) | mm | (1,240 × 1,680 × 760) × 1+ (920×1,680×760) × 1 | (1,240 × 1,680 × 760) × 1+ (920×1,680×760) × 1 | (1,240 × 1,680 × 760) × 1+(1,240 × 1,680 × 760) × 1 | (1,240 × 1,680 × 760) × 1+(1,240 × 1,680 × 760) × 1 | |
| inch | (48-13/16 × 66-5/32 ×29-29/32) × 1 + (36-7/32 ×66-5/32 × 29-29/32) × 1 | (48-13/16 × 66-5/32 ×29-29/32) × 1 + (36-7/32 ×66-5/32 × 29-29/32) × 1 | (48-13/16 × 66-5/32 ×29-29/32) × 1 + (48-13/16 ×66-5/32 × 29-29/32) × 1 | (48-13/16 × 66-5/32 ×29-29/32) × 1 + (48-13/16 ×66-5/32 × 29-29/32) × 1 | ||
| Piping Conections | mm(inch) | ∅ 15.88(5/8) ∅ 19 | .05(3/4) ∅ 19.05(3/4) ∅ | 19.05(3/4) | ||
| mm(inch) | ∅ 34.9(1 3/8) ∅ 34.9(1 3/8) ∅ 34.9(1 3/8) ∅ 34.9(1 3/8) | |||||
| Unit | 3 Outdoor Unit | |||||
| System(HP) | 32 34 36 38 | |||||
| Model | Combination Unit | ARUN320LTH4 AR | UN340LTH4 ARUN360 | LTH4 ARUN380LTH4 | ||
| Independent Unit | ARUN160LTH4 AR | UN140LTH4 ARUN140 | LTH4 ARUN160LTH4 | |||
| ARUN160LTH4 AR | UN100LTH4 ARUN120 | LTH4 ARUN120LTH4 | ||||
| ARUN100LTH4 AR | UN100LTH4 ARUN100 | LTH4 | ||||
| Refrigerant Precharged Amount | kg | 10 + 10 8.5 + (6.5 x 2) (8.5 x 2) + 6.5 | 10 + 8.5 + 6.5 | |||
| lbs | 22 + 22 18.7 + (14.3 x 2) (18.7 x 2) + 1 | 14.3 22 + 18.7 + 14.3 | ||||
| Number of maximum connectable indoor units | 52(64) 55(64) 58(64) 61 | 64) | ||||
| Net Weight | kg | 280 x 1 + 280 x 1 | 270 x 1 + 201 x 1 + 201 x 1 | 270 x 1 + 235 x 1 + 201 x 1 | 280 x 1 + 235 x 1 + 201 x 1 | |
| lbs | 617 x 1 + 617 x 1 | 595 x 1 + 433 x 1 + 433 x 1 | 595 x 1 + 518 x 1 + 433 x 1 | 617 x 1 + 518 x 1 + 433 x 1 | ||
| Dimensions (WxHxD) | mm | (1,240 x 1,680 x 760) x 1 + (1,240 x 1,680 x 760) x 1 | (1,240 x 1,680 x 760) x 1 + (920x1,680x760) x 1 + (920x1,680x760) x 1 | (1,240 x 1,680 x 760) x 1 + (1,240 x 1,680 x 760) x 1 | (1,240 x 1,680 x 760) x 1 + (1,240 x 1,680 x 760) x 1 | |
| inch | (48-13/16 x 66-5/32 x 29-29/32) x 1 + (48-13/16 x 66-5/32 x 29-29/32) x 1 | (48-13/16 x 66-5/32 x 29-29/32) x 1 + (36-7/32 x 66-5/32 x 29-29/32) x 1 | (48-13/16 x 66-5/32 x 29-29/32) x 1 + (48-13/16 x 66-5/32 x 29-29/32) x 1 + (36-7/32 x 66-5/32 x 29-29/32) x 1 | (48-13/16 x 66-5/32 x 29-29/32) x 1 + (46-13/16 x 66-5/32 x 29-29/32) x 1 + (36-7/32 x 66-5/32 x 29-29/32) x 1 | ||
| Piping Conections | mm(inch) | ∅ 19.05(3/4) ∅ 19 | .05(3/4) ∅ 19.05(3/4) ∅ | 19.05(3/4) | ||
| mm(inch) | ∅ 34.9(1 3/8) ∅ 34.9(1 3/8) ∅ 41.3(1 5/8) | ∅ 41.3(1 5/8) | ||||
| Unit | 3 Outdoor Unit | ||||||
| System(HP) | 40 | 42 | 44 | 46 | 48 | ||
| Model | Combination Unit | ARUN400LTH4 | ARUN440LTH4 | ARUN440LTH4 | ARUN460LTH4 | ARUN480LTH4 | |
| Independent Unit | ARUN160LTH4 | ARUN160LTH4 | ARUN160LTH4 | ARUN160LTH4 | ARUN160LTH4 | ||
| ARUN120LTH4 | ARUN140LTH4 | ARUN160LTH4 | ARUN160LTH4 | ARUN160LTH4 | |||
| ARUN120LTH4 | ARUN120LTH4 | ARUN120LTH4 | ARUN140LTH4 | ARUN160LTH4 | |||
| Refrigerant Precharged Amount | kg | 10 + (8.5 × 2) | (8.5 × 2) + 10 | (10 × 2) + 8.5 | (10 × 2) + 8.5 | 10 × 3 | |
| lbs | 22 + (18.7 × 2) | (18.7 × 2) + 22 | (22 × 2) + 18.7 | (22 × 2) + 18.7 | 22 × 3 | ||
| Number of maximum connectable indoor units | 64 | 64 | 64 | 64 | 64 | ||
| Net Weight | kg | 280 × 1 + 235 × 1 - 235 × 1 | 280 × 1 - 270 × 1 + 235 × 1 | 280 × 1 + 280 × 1 - 235 × 1 | 280 × 1 + 280 × 1 - 270 × 1 | 280 × 1 + 280 × 1 - 280 × 1 | |
| lbs | 617 × 1 + 518 × 1 - 518 × 1 | 617 × 1 - 596 × 1 + 518 × 1 | 617 × 1 + 617 × 1 + 518 × 1 | 617 × 1 + 617 × 1 + 595 × 1 | 617 × 1 + 617 × 1 + 617 × 1 | ||
| Dimensions (WxHxD) | mm | (1,240 × 1,680 × 760) × 1 + (1,240 × 1,680 × 760) × 1 + (1,240 × 1,680 × 760) × 1 | (1,240 × 1,680 × 760) × 1 + (1,240 × 1,680 × 760) × 1 + (1,240 × 1,680 × 760) × 1 | (1,240 × 1,680 ×760) × 1 + (1,240 × 1,680 × 760) × 1 + (1,240 × 1,680 × 760) × 1 | (1,240 × 1,680 × 760) × 1 + (1,240 × 2,680 × 760) × 1 + (1,240 × 1,680 × 760) × 1 | (1,240 × 1,680 × 760) × 1 + (1,240 × 1,680 × 760) × 1 + (1.240 × 1,680 × 760) × 1 | |
| inch | (48-13)/16 × 66-5/32 × 29-29/32) × 1 + (48-13/16 × 66-5/32 × 29-29/32) × 1 + (48-13/16 × 66-5/32 × 29-29/32) × 1 | (48-13)/16 × 66-5/32 × 29-29/32) × 1 + (48-13/16 × 66-5/32 × 29-29/32) × 1 + (48-13/16 × 66-5/32 × 29-32) × 1 | (48-13)/16 × 66-5/32 × 29-29/32) × 1 + (48-13/16 × 66-5/32 × 29-29/32) × 1 + (48-13/16 × 66-5) × 29-29/32) × 1 | (48-13)/16 × 66-5/32 × 29-29/32) × 1 + (48-13/16 × 66-5/32 × 29-29/32) × 1 + (48-13/32 × 29-29/32) × 1 + (48-13/16 × 66-5/32 × 29-29/32) × 1 | (48-13)/16 × 66-5/32 × 29-29/32) × 1 + (48-33/16 × 66-5/32 × 29-29/32) × 1 + (48-33/16 × 66-5/32 × 29-29/32) × 1 + (48-33/16 × 66-5/32 × 29-29/32) × 29-29/32) × 1 | ||
| Piping Conections | mm(inch) | ∅ 19.05(3/4) | ∅ 19.05(3/4) | ∅ 19.05(3/4) | ∅ 19.05(3/4) | ∅ 19.05(3/4) | |
| mm(inch) | ∅ 41.3(1\ 5/8) | ∅ 41.3(1\ 5/8) | ∅ 41.3(1\ 5/8) | ∅ 41.3(1\ 5/8) | ∅ 41.3(1\ 5/8) | ||
ENVIRONMENT-FRIENDLY ALTERNATIVE RE- FRIGERANT R410A
The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also considered during the installation.
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0. These days the developed countries have approved it as the environment-friendly refrigerant and encouraged to use it widely to prevent environment pollution.

CAUTION
- The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8 MPa
- Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly. - Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
- For high-pressure refrigerant, any unapproved pipe must not be used.
- Do not heat pipes more than necessary to prevent them from softening.
- Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
Select space for installing outdoor unit, which will meet the following conditions:
- No direct thermal radiation from other heat sources
- No possibility of annoying neighbors by noise from unit
- No exposition to strong wind
- With strength which bears weight of unit
- Note that drain flows out of unit when heating
- With space for air passage and service work shown next
- Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leakage of combustible gas is expected.
- Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
- Do not use unit under any special environment where oil, steam and sulfuric gas exist.
- It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the outdoor unit.
- If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
- Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the product at a place With a high humidity in winter (near beach, coast, lake, etc.) (Ex : Rooftop where there is always sunshine.)
INSTALLATION SPACE
Individual Installation
During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space as shown in the figures below.
| Category | Installation Space | Distance(Side Space ≥ 49 mm) |
| 4 sides are walls | ![]() | A≥50B≥100C≥50D≥500 |
![]() | A≥50B≥100C≥50D≥500E≥100 | |
![]() | A≥50B≥100C≥50D≥500E≥100F≥500 | |
![]() | A≥50B≥100C≥50D≥100E≥100F≥500 | |
| Rear to Rear | ![]() | A≥50B≥500C≥50D≥500E≥100F≥600 |
![]() | A≥50B≥500C≥50D≥500E≥100F≥900 | |
![]() | A≥50B≥500C≥50D≥500E≥100F≥1200 | |
| Category | Installation Space Distance | |
| Only 2 sides are walls | ![]() | A≥50B≥300 |
![]() | A≥200B≥300E≥400 | |
| Limitations on the height of the wall (Refer to 4 side walls) | ![]() | The height of the wall on the front side must be 1500 mm or less.The height of the wall on the inlet side must be 500 mm or less.There is no limit to the wall on the side.If the height of the walls on the front and the side are higher than the limit, there must be additional space on the front and the side.- Additional Space on the front side by 1/2 of h1.- Additional Space on the inlet side by 1/2 of h2-h1 = A(Actual height) - 1500-h2 = B(Actual height) - 500 |
*Distance is more than 49 cm because of Auto Dust Removal mode.
Seasonal wind and cautions in winter
- Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated well.
- Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system. - Install the outdoor unit at the higher installation console by 50 cm than the average snowfall (annual average snowfall) if it is installed at the area with much snowfall.
-
Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always remove snow for operation.
-
The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the product. (If width of the frame is wider than that of the product, snow may accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
LIFTING METHOD
- When carrying the suspended, unit pass the ropes under the unit and use the two suspension points each at the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit. - Attach the ropes to the unit at an angle of 40° or less.


CAUTION
Be very careful while carrying the product.
- Do not have only one person carry product if it is more than 20 kg.
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
- Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
- When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall.
- Use 2 belts of at least 8 m long.
- Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
- Hoist the unit making sure it is being lifted at its center of gravity.
INSTALLATION
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
- The outdoor unit supports at the bottom shall have width of at least 100 mm under the Unit's legs before being fixed.
- The outdoor unit supports should have minimum height of 200 mm.
- Anchor bolts must be inserted at least 75 mm.

For outdoor units should not be supported only by the corner supports.
The location of the Anchor bolts

| Chassis Outdoor Unit Capacity A(mm) B(mm) | ||
| UX2 8~10 HP 920 792 | ||
| UX3 12~16 HP 1240 1102 |
Foundation for Installation
- Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
- Use the H-beam support as a base support
- Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200 mm).




Unit: mm
Ⓐ The corner part must be fixed firmly. Otherwise, the support for the installation may be bent.
⑧ Get and use M10 Anchor bolt.
© Put Cushion Pad between the outdoor unit and ground support for the vibration protection in wide area.
⑭ Space for pipes and wiring (Pipes and wirings for bottom side)
⑤ H-beam support
⑤ Concrete support

WARNING
• Install where it can sufficiently support the weight of the outdoor unit.
If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake.
If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
- Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment of the water flowing out of the outdoor unit in operation), and the passages of the pipe and wiring, when making the ground support.
- Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet. The tube or pipe may freeze and the water may not be drained.

CAUTION
- Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit Base Pan before fixing the bolt. It may cause the unstable state of the outdoor settlement, and may cause freezing of the heat exchanger resulting in abnormal operations.
- Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit before welding. Not removing Pallet(Wood Support) causes hazard of fire during welding.


Pallet(Wood Support)
- Remove before Installation
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
- Use the accessory piping kit or the pipes purchased locally.
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5 m longer than the pipe length.
Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
Flaring work
- Carry out flaring work using flaring tool as shown below.
| Indoor unit[kW(Btu/h)] | Pipe " A " | |||
| Gas Liquid Gas | Liquid | |||
| <5.6(19,100) | 1/2" 1/4" | 0.5~0.8 0 | 0~0.5 | |
| <16.0(54,600) | 5/8" 3/8" | 0.8~1.0 | 0.5~0.8 | |
| <22.4(76,400) | 3/4" 3/8" | 1.0~1.3 | 0.5~0.8 | |
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the flared section and do flaring work again.




Flare shape and flare nut tightening torque
Precautions when connecting pipes
- See the following table for flare part machining dimensions.
- When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first. (Use ester oil or ether oil.)
- See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
- After all the piping has been connected, use nitrogen to perform a gas leak check.
| pipe size tightening torque(N·cm) A(mm) | flare shape | |
| ∅9.52 38±4 12.8-13.2 | ![]() | |
| ∅12.7 55±6 16.2-16.6 | ||
| ∅15.88 75±7 19.3-19.7 |
! CAUTION
• Always use a charge hose for service port connection.
• After tightening the cap, check that no refrigerant leaks are present.
- When loosening a flare nut, always use two wrenches in combination, When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.
- When connecting a flare nut, coat the flare(inner and outer faces) with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as the initial tightening.

Opening shutoff valve
1 Remove the cap and turn the valve counter clockwise with the hexagon wrench.
2 Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3 Make sure to tighten the cap securely.
Closing shutoff valve
1 Remove the cap and turn the valve clockwise with the hexagon wrench.
2 Securely tighten the valve until the shaft contacts the main body seal.
3 Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
| Shut off Valvesize | Tightening torque N·m (Turn clockwise to close) | ||||||
| Shaft (valve body) | Cap (valve lid) | Service port | Flare nut | Gas line piping At-tached to unit | |||
| Closed O | Opened | Hexagonal wrench | |||||
| ∅ 6.35 | 6.0±0.6±4 | ±2.0 55±625±3±10mm - | 4 mm | 17.6±2.0 | 12.7±2 | 16±2 | - |
| ∅ 9.52 38 | |||||||
| ∅ 12.7 10 | |||||||
| ∅ 15.88 1 | 2.0±1.2 | 5 mm | 25.0±2.5 | 75±7 | |||
| ∅ 19.05 1 | 4.0±1.4 110 | ||||||
| ∅ 22.2 | 30.0±3.0 8±3 | ||||||
| ∅ 25.4 25 | |||||||
Insulation of shutoff valve
1 Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120\ °C ).
2 Precautions in high humidity circumstance:
This air conditioner has been tested according to the "ISO Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23 °C), water drops are liable to fall. In this case, add heat insulation material according to the following procedure:
- Heat insulation material to be prepared... EPDM (Ethylene Propylene Diene Methylene)-over 120 °C the heat-resistance temperature.
- Add the insulation over 10 mm thickness at high humidity environment.

Plumbing materials and storage methods
Pipe must be able to obtain the specified thickness and should be used with low impurities. Also when handling storage, pipe must be careful to prevent a fracture, deformity and wound. Should not be mixed with contaminations such as dust, moisture.

Refrigerant piping on three principles
| Drying | Cleanliness | Airtight | |
| Should be no moisture inside | No dust inside. | There is no refrigerant leakage | |
| Items | ![]() | ![]() | ![]() |
| Cause failure | - Significant hydrolysis of refrigerant oil- Degradation of refrigerant oil- Poor insulation of the compressor- Do not cold and warm- Clogging of EEV, Capillary | - Degradation of refrigerant oil- Poor insulation of the compressor- Do not cold and warm- Clogging of EEV, Capillary | - Gas shortages- Degradation of refrigerant oil- Poor insulation of the compressor- Do not cold and warm |
| Countermeasure | - No moisture in the pipe- Until the connection is completed, the plumbing pipe entrance should be strictly controlled.- Stop plumbing at rainy day.- Pipe entrance should be taken side or bottom.- When removal burr after cutting pipe, pipe entrance should be taken down.- Pipe entrance should be fitted cap when pass through the walls. | - No dust in the pipe.- Until the connection is completed, the plumbing pipe entrance should be strictly controlled.- Pipe entrance should be taken side or bottom.- When removal burr after cutting pipe, pipe entrance should be taken down.- Pipe entrance should be fitted cap when pass through the walls. | - Airtightness test should be.- Brazing operations to comply with standards.- Flare to comply with standards.- Flange connections to comply with standards. |
Nitrogen substitution method
Welding, as when heating without nitrogen substitution a large amount of the oxide film is formed on the internal piping.
The oxide film is a caused by clogging EEV, Capillary, oil hole of accumulator and suction hole of oil pump in compressor.
It prevents normal operation of the compressor.
In order to avoid this problem, Welding should be done after replacing air by nitrogen gas.
When welding plumbing pipe, the work is required.

! CAUTION
1 Always use the nitrogen.(not use oxygen, carbon dioxide, and a Chevron gas):
Please use the following nitrogen pressure 0.02 MPa
Oxygen – Promotes oxidative degradation of refrigerant oil.
Because it is flammable, it is strictly prohibited to use
Carbon dioxide – Degrade the drying characteristics of gas
Chevron Gas – Toxic gas occurs when exposed to direct flame.
2 Always use a pressure reducing valve.
- Please do not use commercially available antioxidant.
The residual material seems to be the oxide scale is observed.
In fact, due to the organic acids generated by oxidation of the alcohol contained in the antioxidants, ants nest corrosion occurs. (causes of organic acid alcohol + copper + water + temperature)
REFRIGERANT PIPING INSTALLATION
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the branching pipes, and the refrigerant pipe coming out of the outdoor unit is divided at the end to connect to each indoor unit. Flare connection for the indoor unit, and welding connection for the outdoor pipe and the branching parts.
- Use hexagonal wrench to open/close the valve.


WARNING
• Always careful not to leak the refrigerant during welding.
- The refrigerant generates poisonous gas harmful to human body if combusted.
- Do not perform welding in a closed space.
- Be sure to close the cap of the service port to prevent gas leakage after the work.

CAUTION
Please block the pipe knock outs of the front and side panels after installing the pipes. (Animals or foreign objects may be brought in to damage wires.)
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
- Pipe connections can be done on the front side or on the side according to the installation environments.
- Be sure to let 0.2kaf / cm2 Nitrogen flow in the pipe when welding.
- If Nitrogen was not flown during welding, many oxidized membranes may from inside the pipe and disturb the normal operations of valves and condensers.

![graph LR A["Refrigerant Pipe"] --> B["Taping"] B --> C["Regulator"] C --> D["Nitrogen"] C --> E["Valve"] E --> F["Nitrogen"] B --> G["Nitrogen Direction"]](/content/2026/07/1525988/images/ba59eee3ba223ae5b51a02ebee6c91bdde750b0031ae41f9a05bf33cd447e70c.jpg)
Preparation Work
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or Bottom pipe drawing outs.

Removal Area for Liquid/Gas pipe bottom side connections.
! CAUTION
- Do not give damage to the pipe/base during the Knock Out work.
- Proceed to pipe work after removing burr after Knock Out work.
- Perform sleeve work to prevent damage to the wire when connecting wires using knock Outs.
Remove leakage prevention cap
- Remove the leakage prevention cap attached to the outdoor unit service valve before pipe work.
-
Proceed the leakage prevention cap removal as follows:
-
Verify whether the liquid/gas pipes are locked.
- Extract remaining refrigerant or air inside using the service port.
- Remove the leakage prevention cap

Pipe Drawing Out during Single / Series connection
Method of drawing out pipes on the front side
- Proceed with the pipe work as shown in the below figure for front side pipe drawing out.

Method of drawing out pipes on the bottom side
- Drawing out common pipe through side panel

Remove only liquid/gas pipe Knock out
Refrigerant piping system
Y branch method
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
⑧ : 1st branch (Y branch)
©: Indoor Units

2 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
⑧ : 1st branch (Y branch)
©: Indoor Units
(D) : Downward Indoor Unit
⑤ : Connection branch pipe between Outdoor units: ARCNN21
![graph TD A["Slave"] --> B["Master"] B --> C["Slave"] C --> D["Master"] D --> E["Slave"] E --> F["Master"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333 style E fill:#cff,stroke:#333 subgraph '10 m or less' A B C D E end subgra…](/content/2026/07/1525988/images/84dcfafb98b431847e5e2946b2cd4163844c11500d61621a98cc5551a5f6389b.jpg)
Piping length from outdoor branch to outdoor unit ≤10 m, equivalent length:max 13 m (for 18HP or more)
Conditional Application
To satisfy below condition to make 40 m \~ 90 m of pipe length after first branch.
- Diameter of pipes between first branch and the last branch should be increased by one step, except pipe diameter B,C,D is same as Diameter A ∅6.35 → ∅ 9.52 → ∅ 12.7 → ∅ 15.88 → ∅ 19.05 → ∅ 22.2 → ∅ 25.4*, ∅ 28.58 → ∅ 31.8*, ∅ 34.9 → ∅ 38.1*
* : It is not necessary to size up.
- While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice.
A + Bx 2 + Cx 2 + Dx 2 + a + b + c + d + e ≤ 1, 0 0 0 m
- Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) ≤ 40 m
- [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] ≤ 40 m
3 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
⑧ : 1st branch (Y branch)
©: Indoor Units
(D): Downward Indoor Unit
⑤ : Connection branch pipe between Outdoor units: ARCNN31
⑤ : Connection branch pipe between Outdoor units: ARCNN21

Piping length form outdoor branch to outdoor unit ≤ 10 m, equivalent length : max. 13 m (for 18 HP or more)
Conditional Application
To satisfy below condition to make 40 m \~ 90 m of pipe length after first branch.
- Diameter of pipes between first branch and the last branch should be increased by one step, except pipe diameter B,C,D is same as Diameter A
* : It is not necessary to size up.
6. 3 5 → 9. 5 2 → 1 2. 7 → 1 5. 8 8 → 1 9. 0 5 → 2 2. 2 → 2 5. 4 ^ , 2 8. 5 8 → 3 1. 8 ^ ,; emptyset 3 4. 9 → 3 8. 1*
- While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice.
A + Bx 2 + Cx 2 + Dx 2 + a + b + c + d + e ≤ 1, 0 0 0 m
- Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) ≤ 40 m
- [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] ≤ 40 m
Refrigerant pipe diameter from branch to branch (B,C,D)
| Downward Indoor Unit total capacity [kW(Btu/h)] | Liquid pipe [mm(inch)] Gas | pipe [mm(inch)] |
| ≤ 5.6(19,100) | ∅6.35(1/4) ∅12.7(1/2) | |
| < 16.0(54,600) ∅9.52(3/8) ∅15.88(5/8) | ||
| ≤ 22.4(76,400) | ∅9.52(3/8) ∅19.05(3/4) | |
| < 33.6(114,700) ∅9.52(3/8) ∅22.2(7/8) | ||
| < 50.4(172,000) ∅12.7(1/2) ∅28.58(1-1/8) | ||
| < 67.2(229,400) ∅15.88(5/8) ∅28.58(1-1/8) | ||
| < 72.8(248.500) ∅15.88(5/8) ∅34.9(1-3/8) | ||
| < 100.8(344,000) ∅19.05(3/4) ∅34.9(1-3/8) | ||
| < 173.6(592,500) ∅19.05(3/4) ∅41.3(1-5/8) |
Total pipe length = A+B+C+D+a+b+c+d+e ≤ 1,000 m
| L | Longest pipe length Equivalent pipe length | |
| A+B+C+D+e ≤ 150 m(200 m**) | *A+B+C+D+e ≤ 175 m(225 m**) | |
| l | Longest pipe length after 1st branch | |
| B+C+D+e ≤ 40 m(90 m**) | ||
| H | Difference in height (Outdoor Unit ↔Indoor Unit) | |
| H ≤ 110 m | ||
| h | Difference in height (Indoor Unit ↔Indoor Unit) | |
| h ≤ 40 m | ||
| h1 | Difference in height (Outdoor Unit ↔Outdoor Unit) | |
| h1 ≤ 5 m | ||
- * : Assume equivalent piping length of Y branch to be 0.5 m, that of header to be 1 m, calculation purpose.
• ** : To apply Conditional Application

WARNING
When the any one (or both) of below conditions are satisfied, the diameter of main pipe (A) must be increased according to below table.
- The equivalent length between outdoor unit and the farthest indoor unit is 90 m or more (Liquid and Gas pipes are increased)
- The level difference (Outdoor unit ↔ Indoor unit) is 50 m or more (Only liquid pipe is increased)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
| Upward Outdoor unit total capacity | Standard Pipe Diameter | Increased Pipe Diameter | ||||
| When pipe length is 90 m or more from ODU to 1st branch | When level difference is 50 m or more | |||||
| HP | Liquid pipe [mm(inch)] | Gas pipe [mm(inch)] | Liquid pipe [mm(inch)] | Gas pipe [mm(inch)] | Liquid pipe [mm(inch)] | Gas pipe [mm(inch)] |
| 8 ∅ 9.52 | (3/8) ∅ 19.05(3/4) | ∅ 12.7(1/2) ∅ 22.2(7/8) ∅ 12.7(1/2) not increased | ||||
| 10 ∅ 9.52 | (3/8) ∅ 22.2(7/8) | ∅ 12.7(1/2) ∅ 25.4(1) ∅ 12.7(1/2) not increased | ||||
| 12 ~ 14 ∅ 1 | 2.7(1/2) ∅ 28.58 | (1-1/8) ∅ 15.88(5/8) not increased ∅ 15.88(5/8) not increased | ||||
| 16 ∅ 12.7 | (1/2) ∅ 28.58 | (1-1/8) ∅ 15.88(5/8) ∅ 31.8(1-1/4) ∅ 15.88(5/8) not increased | ||||
| 18 ~ 22 ∅ 1 | 5.88(5/8) ∅ 28.58 | (1-1/8) ∅ 19.05(3/4) ∅ 31.8(1-1/4) ∅ 19.05(3/4) not increased | ||||
| 24 ∅ 15.88 | (5/8) ∅ 34.9(1-3/8) ∅ 19.05(3/4) not increased ∅ 19.05(3/4) not increased | |||||
| 26 ~ 34 | ∅ 19.05(3/4) | ∅ 34.9(1-3/8) | ∅ 22.2(7/8) | ∅ 38.1(1-1/2) | ∅ 22.2(7/8) | not increased |
| 36 ~ 48 ∅ 1 | 9.05(3/4) ∅ 41 | 3(1-5/8) ∅ 22.2(7/8) not increased ∅ 22.2(7/8) not increased | ||||
* If the step up size is not available, you can not select the next higher size available.
Header Method
1 Outdoor Unit
Example : 6 Indoor Units connected
Ⓐ : Outdoor Unit
⑧: 1st branch
©: Indoor Units
⑭ : Sealed piping

2 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ : Outdoor Unit
⑧ : Header branch
©: Indoor Units
(D) : Sealing
⑤ : Connection branch pipe between Outdoor units: ARCNN21

3 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ : Outdoor Unit
⑧ : Header branch
©: Indoor Units
⑭: Sealing
⑤ : Connection branch pipe between Outdoor units: ARCNN31
⑤ : Connection branch pipe between Outdoor units: ARCNN21

Branch pipe can not be used after header
Total pipe length = A+a+b+c+d+e+f ≤ 1,000 m
| L | Longest pipe length *Equivalent pipe length | |
| A+f ≤ 200 m A+f ≤ 225 m | ||
| l | Longest pipe length after 1st branch | |
| f ≤ 40 m | ||
| H | Difference in height (Outdoor Unit ↔Indoor Unit) | |
| H ≤ 110 m | ||
| h | Difference in height (Indoor Unit ↔Indoor Unit) | |
| h ≤ 40 m | ||
| h1 | Difference in height (Outdoor Unit ↔Outdoor Unit) | |
| h1 ≤ 5 m | ||
! WARNING
Pipe length after header branching (a\~f)
It is recommended that difference in length of the pipes connected to the Indoor Units is minimized. Performance difference between Indoor Units may occur.
- * : Assume equivalent piping length of Y branch to be 0.5 m, that of header to be 1 m, calculation purpose
- Indoor Unit should be installed at lower position than the header.
- Piping length from outdoor branch to outdoor unit ≤ 10 m, equivalent length: max 13 m (for 22HP or more)
Combination of Y branch/header method
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
⑧ : 1st branch (Y branch)
©: Y branch
(D): Indoor Unit
⑤ : Header
⑤ : Sealed piping
![graph TD A["Power Supply Unit A"] --> B["Switch"] B --> C["Relay"] C --> D["Device 3 (D)"] C --> E["Device 4 (D)"] C --> F["Device 5 (D)"] D --> G["Switch"] E --> H["Switch"] F --> I["Switch"] G --> J["L150 m(200 m : Conditional application)"] H --> K["L150 m(200 m : Conditional application)"] I -->…](/content/2026/07/1525988/images/5d9cc3134867a54badb840d2cb21757d67f17eae78f7c06c9bf448b3bb043244.jpg)
Branch pipe can not be used after header
2 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
⑧: 1st branch
© : Y branch
(D): Indoor Unit
⑤ : Connection branch pipe between Outdoor units: ARCNN21
⑤ : Header
© : Sealed piping
![graph TD A["Slave"] --> B["Master"] B --> C["Slave"] C --> D["Master"] D --> E["Slave"] E --> F["Master"] style A fill:#f9f,stroke:#333 style C fill:#f9f,stroke:#333 style D fill:#f9f,stroke:#333 style E fill:#f9f,stroke:#333 note right of A "10 m or less" note left of E "h1 hE" note right of F "ODU…](/content/2026/07/1525988/images/f99ec846648d38e2f023b5b573c32d9bcb234b485cb80ac6bef9ce5d83c7d2fb.jpg)
Branch pipe can not be used after header
3 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
⑧ : 1st branch(Y branch)
©: Y branch
(D): Indoor Unit
⑤ : Connection branch pipe between Outdoor units: ARCNN31
⑤ : Connection branch pipe between Outdoor units: ARCNN21
G : Header
⑧ : Sealing
![graph TD A["Slave1 Master"] --> B["Slave2 Master"] subgraph Slave1 C["Slave2 Master"] D["Slave1 Master"] end subgraph Slave2 E["Slave2 Master"] F["Slave1 Master"] end subgraph Condition1 G["L 150 m (200 m : Conditional application)"] H["t 40 m (90 m : Conditional application)"] end I["ODU Capacity M…](/content/2026/07/1525988/images/ef2485ad3c94a4dff4ab0aec57c570a8016e681d269b4cf70d9d7add4d5539eb.jpg)
Branch pipe can not be used after header
Refrigerant pipe diameter from branch to branch (B,C)
| Downward Indoor Unit total capacity [kW(Btu/h)] | Liquid pipe [mm(inch)] Gas | pipe [mm(inch)] |
| ≤ 5.6(19,100) | ∅6.35(1/4) ∅12.7(1/2) | |
| < 16.0(54,600) ∅9.52(3/8) ∅15.88(5/8) | ||
| ≤ 22.4(76,400) | ∅9.52(3/8) ∅19.05(3/4) | |
| < 33.6(114,700) ∅9.52(3/8) ∅22.2(7/8) | ||
| < 50.4(172,000) ∅12.7(1/2) ∅28.58(1-1/8) | ||
| < 67.2(229,400) ∅15.88(5/8) ∅28.58(1-1/8) | ||
| < 72.8(248.500) ∅15.88(5/8) ∅34.9(1-3/8) | ||
| < 100.8(344,000) ∅19.05(3/4) ∅34.9(1-3/8) | ||
| < 173.6(592,500) ∅19.05(3/4) ∅41.3(1-5/8) |
Total pipe length = A+B+C+a+b+c+d+e ≤ 1,000 m
| L | Longest pipe length *Equivalent pipe length | |
| A+B+b ≤ 150 m(200 m**) | A+B+b ≤ 175 m(225 m**) | |
| l | Longest pipe length after 1st branch | |
| B+b ≤ 40 m(90 m**) | ||
| H | Difference in height (Outdoor Unit ↔Indoor Unit) | |
| H ≤ 110 m | ||
| h | Difference in height (Indoor Unit ↔Indoor Unit) | |
| h ≤ 40 m | ||
| h1 | Difference in height (Outdoor Unit ↔Outdoor Unit) | |
| h1 ≤ 5 m | ||
- * : Assume equivalent pipe length of Y branch to be 0.5 m, that of header to be 1 m, calculation purpose
• ** : To apply Conditional Application - Indoor Unit should be installed at lower position than the header.

WARNING
- It is recommended that difference of piping length for pipes connected to the Indoor Unit is minimized. Performance difference between Indoor Units may occur.
- When the any one (or both) of below conditions are satisfied, the diameter of main pipe (A) must be increased according to below table.
- The equivalent length between outdoor unit and the farthest indoor unit is 90 m or more (Liquid and Gas pipes are increased)
- The level difference (Outdoor unit ↔ Indoor unit) is 50 m or more (Only liquid pipe is increased)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
| Upward Outdoor unit total capacity | Standard Pipe Diameter | Increased Pipe Diameter | ||||
| When pipe length is 90 m or more from ODU to 1st branch | When level difference is 50 m or more | |||||
| HP | Liquid pipe [mm(inch)] | Gas pipe [mm(inch)] | Liquid pipe [mm(inch)] | Gas pipe [mm(inch)] | Liquid pipe [mm(inch)] | Gas pipe [mm(inch)] |
| 8 ∅ 9.52(3/8) ∅ 19.05(3/4) ∅ 12.7(1/2) ∅ 22.2(7/8) ∅ 12.7(1/2) not increased | ||||||
| 10 ∅ 9.52(3/8) ∅ 22.2(7/8) ∅ 12.7(1/2) ∅ 25.4(1) ∅ 12.7(1/2) not increased | ||||||
| 12 ~ 14 | ∅ 12.7(1/2) | ∅ 28.58(1-1/8) | ∅ 15.88(5/8) | not increased | ∅ 15.88(5/8) | not increased |
| 16 | ∅ 12.7(1/2) | ∅ 28.58(1-1/8) | ∅ 15.88(5/8) | ∅ 31.8(1-1/4) | ∅ 15.88(5/8) | not increased |
| 18 ~ 22 | ∅ 15.88(5/8) | ∅ 28.58(1-1/8) | ∅ 19.05(3/4) | ∅ 31.8(1-1/4) | ∅ 19.05(3/4) | not increased |
| 24 | ∅ 15.88(5/8) | ∅ 34.9(1-3/8) | ∅ 19.05(3/4) | not increased | ∅ 19.05(3/4) | not increased |
| 26 ~ 34 | ∅ 19.05(3/4) | ∅ 34.9(1-3/8) | ∅ 22.2(7/8) | ∅ 38.1(1-1/2) | ∅ 22.2(7/8) | not increased |
| 36 ~ 48 | ∅ 19.05(3/4) | ∅ 41.3(1-5/8) | ∅ 22.2(7/8) | not increased | ∅ 22.2(7/8) | not increased |
* If the step up size is not available, you can not select the next higher size available.
Outdoor unit Connection
! WARNING
- In case of pipe diameter B connected after first branch is bigger than the main pipe diameter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio 120% is connected to 24 HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : ∅34.9(Gas pipe), ∅15.88(liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor unit ombination(80.6 kW): ∅34.9(gas pipe), ∅19.05(liquid pipe)
Therefore, pipe diameter B connected after first branch would be ∅34.9(gas pipe) / ∅15.88(liquid pipe) which is same with main pipe diameter.
[Example]
Do not choose the main pipe diameter by downward indoor unit total capacity but its outdoor unit model name.
Do not let the connection pipe from branch to branch exceed the main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 22 HP (61.6 kW) outdoor unit to 130% of its system capacity (80.1 kW) and branching 7 k (2.2 kW) indoor unit at the 1st branch.
1) Main pipe diameter(22 HP outdoor unit): ∅28.58(gas pipe), ∅15.88(Liquid pipe)
2) Pipe diameter between 1st and 2nd branch (77.9 kW indoor units): ∅34.9(Gas pipe), ∅19.05(Liquid pipe) in conformity with downward indoor units.
Since the main pipe diameter of 22 HP outdoor unit is ∅28.58(gas pipe), ∅15.88(Liquid pipe) is used as the main pipe and the connection pipe between 1st and 2nd branch.
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
| Indoor Unit capacity [kW(Btu/h)] | Liquid pipe [mm(inch)] Gas pipe [mm(inch)] |
| ≤ 5.6(19,100) | ∅6.35(1/4) ∅12.7(1/2) |
| < 16.0(54,600) ∅9.52(3/8) ∅15.88(5/8) | |
| < 22.4(76,400) ∅9.52(3/8) ∅19.05(3/4) | |
| <28.0(95,900 ∅ 9.52(3/8) ∅ 22.2(7/8) |
CAUTION
- Bending radius should be at least twice the diameter of the pipe.
- Bend pipe after 500 mm or more from branch (or header).
Do not bend U type. It may cause Performance unsatisfactory or noise. - If want U type, bending R is more than 200 mm

Pipe Connection Method/Precautions for Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between outdoor units.
- Please refer to the below connection examples to install pipe connections between outdoor units.
Pipe connection between outdoor units (General Case)

Pipes between outdoor units are 2 m or less

Pipes between outdoor units are 2 m or longer


- If the distance between the outdoor units becomes more than 2 m, apply Oil Traps between the gas pipes.
- If the outdoor unit is located lower than the main pipe, apply Oil Trap.
Examples of Wrong Pipe Connections
![graph TD A["Main Pipe"] --> B["Outdoor Units"] C["Oil Trap"] --> D["Grid Units"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333 note1["If the main pipe is higher than the outdoor units, oil is accumulated in the outdoor unit."]](/content/2026/07/1525988/images/5319ebd58a98a459e07fb899d16163d7bb35adee3fe6bea3bacf613806ba5568.jpg)
If there are differences in the height between the outdoor units, oil is accumulated in the lower outdoor unit.
- The pipes between the outdoor units must maintain horizontal levelness or give an inclination to prevent a back flow toward the slave outdoor unit. Otherwise, the unit may not operate properly.
(Example 1)

- Apply Oil Trap as shown below when the length of the pipe between the outdoor units is more than 2 m. Otherwise, the unit may not operate properly.

- When connecting the pipes between the outdoor units, the accumulation of oil in the slave outdoor unit should be avoided. Otherwise, the unit may not operate properly.
(Example 1)


(Example 2)

(Example 3)


The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correction Factor) value of indoor unit.
Additional charge(kg)
Total liquid pipe : ∅25.4 mm × 0.480(kg/m)
+ Total liquid pipe : ∅22.2 mm × 0.354(kg/m)
+ Total liquid pipe : ∅19.05 mm × 0.266(kg/m)
+ Total liquid pipe : ∅15.88 mm × 0.173(kg/m)
+ Total liquid pipe : ∅12.7 mm × 0.118(kg/m)
+ Total liquid pipe : ∅9.52 mm × 0.061(kg/m)
+ Total liquid pipe : ∅6.35 mm × 0.022(kg/m)
+ CF value of indoor unit
Amount refrigerant of Indoor units
Example) 4 Way Ceiling Cassette 14.5 kW -1ea, Ceiling concealed Duct 7.3 kW-2 ea, Wall Mounted 2.3 kW-4ea
CF = 0. 6 4 × 1 + 0. 2 6 × 2 + 0. 2 4 × 4 = 2. 1 2 kg
Attach the additional refrigerant table of IDU.

CAUTION
- Use only 2-series of indoor unit. Ex) EX) ARNU ***2
- Do not connect Hydro kit with Multi V IV Models.
! WARNING
• Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
Total amount of refrigerant in the system
Volume of the room at which Indoor Unit of the least capacity is installed
≤ 0. 4 4 (kg / m ^ 3)
If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
- Installation of effective opening part
- Reconfirmation of Outdoor Unit capacity and piping length
- Reduction of the amount of refrigerant
-
Installation of 2 or more security device (alarm for gas leakage)
-
Change Indoor Unit type
: installation position should be over 2 m from the floor (Wall mounted type Cassette type) - Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system - Limitation in piping work
: Prepare for earthquake and thermal stress
Refrigerant charging

Ⓐ Manifold Gauge
⑧ Low pressure side Handle
© High pressure side Handle
! WARNING
- Pipe to be vacuumed: gas pipe, liquid pipe
- If the refrigerant amount is not exact, it may not operate properly.
- If additionally bottled refrigerant amount is over 10%, condenser burst or insufficient indoor unit performance may be caused.
Distribution Method
Horizontal Distribution
![graph TD A["Slave Master"] --> B["1st"] B --> C["2nd"] C --> D["Main pipe Distribution"] E["Slave Master"] --> F["1st"] F --> G["2nd"] G --> H["Main pipe Distribution"] I["Slave Master"] --> J["1st"] J --> K["2nd"] K --> L["Main pipe Distribution"] M["Slave Master"] --> N["1st"] N --> O["2nd"] O -->…](/content/2026/07/1525988/images/649368eb93bc96cc28a279786c8ef64bc57183841312b7662b5730ea25ace6a6.jpg)
![graph TD A["Slave"] --> B["Master"] B --> C["1st"] B --> D["2nd"] B --> E["3rd"] C --> F["Subsea 1"] D --> G["Subsea 2"] E --> H["Subsea 3"] F --> I["Subsea 4"] G --> J["Subsea 5"] H --> K["Subsea 6"] I --> L["Subsea 7"] J --> M["Subsea 8"] K --> N["Subsea 9"] L --> O["Subsea 10"] M --> P["Subsea 11…](/content/2026/07/1525988/images/846782a0bc10442e3f790dd79dcd5501eda413d4913a8e4a6e4d4023351df1a6.jpg)
Vertical Distribution
- Ensure that the branch pipes are attached vertically.
![graph TD A["Slave Master"] --> B["Server"] B --> C["Base Station 1"] B --> D["Base Station 2"] B --> E["Base Station 3"] B --> F["Base Station 4"] B --> G["Base Station 5"] B --> H["Base Station 6"] B --> I["Base Station 7"] B --> J["Base Station 8"]](/content/2026/07/1525988/images/7e1bac03d1400796adf5d5ee59dd868e561caa7bd9fcb9f1ca8f1a76058a112b.jpg)
![graph TD A["Slave"] --> B["Master"] C["Slave"] --> D["Master"] E["Slave"] --> F["Master"] G["Slave"] --> H["Master"] I["Slave"] --> J["Master"] K["Slave"] --> L["Master"] M["Slave"] --> N["Master"] O["Slave"] --> P["Master"] Q["Slave"] --> R["Master"] S["Slave"] --> T["Master"] U["Slave"] --> V["Mas…](/content/2026/07/1525988/images/62a0e86b4cf410e660ace1ab505ff0b1591cc7033b80500300c3509f3bbfc835.jpg)
The others
![graph TD A["Slave Master"] --> B["Base Station 1"] A --> C["Base Station 2"] A --> D["Base Station 3"] A --> E["Base Station 4"] A --> F["Base Station 5"] A --> G["Base Station 6"] A --> H["Base Station 7"] A --> I["Base Station 8"] A --> J["Base Station 9"] A --> K["Base Station 10"]](/content/2026/07/1525988/images/ed45c4419191bc6e0cac718038fc67f585c9c9c63f1363bd02128c87b765cb0c.jpg)
![graph TD A["Slave Master"] --> B["Header"] B --> C["Computer 1"] B --> D["Computer 2"] B --> E["Computer 3"] B --> F["Computer 4"] B --> G["Computer 5"] B --> H["Computer 6"]](/content/2026/07/1525988/images/6f09119065cb5262023fbb571b86bfc08adee1193c89a8cb13bac2bdc9699296.jpg)
Branch pipe Fitting
Y branch
![graph TD A["A"] --> B["Process"] B --> C{Branch Point} C --> D["Process"] D --> E["End"] B --> F["Process"] F --> G{Branch Point} G --> H["Process"] H --> I["End"]](/content/2026/07/1525988/images/7702638944aae7f478ec8ccb5ba31f63b571606f92795e708dbac3337bc0113c.jpg)
Ⓐ To Branch Piping or Indoor Unit
⑧ To Outdoor Unit
- Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)


Within 3 Within 3
- There is no limitation on the joint mounting configuration.
- If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter.
- Branch pipe should be insulated with the insulator in each kit.

Header


Ⓐ To Outdoor Unit Ⓑ To Indoor Unit
- The indoor unit having larger capacity must be installed closer to Ⓐ than smaller one.
- If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter.
© Pipe cutter
- When the number of pipes to be connected is smaller than the number of header branches, install a cap to the unconnected branches.
- When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connection then cap pipes should be fitted to the surplus branches.

- Fit branch pipe lie in a horizontal plane.

- Header should be insulated with the insulator in each kit.

- Joints between branch and pipe should be sealed with the tape included in each kit.

- Any cap pipe should be insulated using the insulator provided with each kit and then taped as described above.

Y branch pipe
[unit:mm]
| Models Gas | pipe Liquid pipe | |
| ARBLN01621 | ![]() | ![]() |
| ARBLN03321 | ![]() | ![]() |
| ARBLN07121 | ![]() | ![]() |
| ARBLN14521 | ![]() | ![]() |
| ARBLN23220 | ![]() | ![]() |
Header
[unit:mm]
| Models Gas | pipe Liquid pipe | |
| 4 branch ARBL054 | ![]() | ![]() |
| 7 branch ARBL057 | ![]() | ![]() |
| 4 branch ARBL104 | ![]() | ![]() |
| 7 branch ARBL107 | ![]() | ![]() |
| 10 branch ARBL1010 | ![]() | ![]() |
| 10 branch ARBL2010 | ![]() | ![]() |
Leak Test and Vacuum drying
Leak test
Leak test should be made by pressurizing nitrogen gas to 3.8 MPa(38.7 kgf/cm 2 ). If the pressure does not drop for 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method, refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid pipe, gas pipe and high/low pressure common pipe)
The test result can be judged good if the pressure has not be reduced after leaving for about one day after completion of nitrogen gas pressurization.
![graph TD A["Nitrogen gas cylinder"] --> B["Close"] B --> C["Liquid pipe"] B --> D["Gas pipe"] E["Slave 1 outdoor unit Master outdoor unit"] --> F["Close"] F --> G["Liquid pipe"] F --> H["Gas pipe"] I["Liquid side"] --> J["Indoor unit"] K["Gas side"] --> L["Indoor unit"]](/content/2026/07/1525988/images/8dbf4a0fcb1795c886f8fd2085ec6c4b42f9d7c465dde2c2bedb84ad603f3198.jpg)

WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.

NOTE
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is checked, apply the following correction factor
There is a pressure change of approximately 0.1 kg/cm2 (0.01 MPa) for each 1°C of temperature difference.
Correction= (Temp. at the time of pressurization - Temp. at the time of check) x 0.1
For example: Temperature at the time of pressurization (3.8 MPa) is 27 °C
24 hour later: 3.73 MPa, 20 °C
In this case the pressure drop of 0.07 is because of temperature drop
And hence there is no leakage in pipe occurred.

CAUTION
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must be at higher position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
Vacuum
Vacuum drying should be made from the service port provided on the outdoor unit's service valve to the vacuum pump commonly used for liquid pipe, gas pipe and high/low pressure common pipe. (Make Vacuum from liquid pipe, gas pipe and high/low pressure common pipe with the service valve closed.)
* Never perform air purging using refrigerant.
- Vacuum drying: Use a vacuum pump that can evacuate to -100.7 kPa (5 Torr, -755 mmHg).
- Evacuate the system from the liquid and gas pipes with a vacuum pump for over 2 hrs and bring the system to -100.7 kPa. After maintaining system under that condition for over 1 hr, confirm the vacuum gauge rises. The system may contain moisture or leak.
- Following should be executed if there is a possibility of moisture remaining inside the pipe. (Rainwater may enter the pipe during work in the rainy season or over a long period of time) After evacuating the system for 2 hrs, give pressure to the system to 0.05 MPa(vacuum break) with nitrogen gas and then evacuate it again with the vacuum pump for 1 hr to -100.7 kPa(vacuum drying). If the system cannot be evacuated to -100.7 kPa within 2 hrs, repeat the steps of vacuum break and its drying. Finally, check if the vacuum gauge does not rise or not, after maintaining the system in vacuum for 1 hr.
![graph TD A["Vacuum pump"] --> B["Slave 1 outdoor unit Master outdoor unit"] B --> C["Close"] C --> D["Liquid side"] C --> E["Indoor unit"] C --> F["Gas side"] D --> G["Live side"] E --> H["Live side"] F --> I["Live side"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,…](/content/2026/07/1525988/images/f6a0267abc1dc935ade3f99c475c6bdeda4c87f571a07764dd4a1cac64825332.jpg)

WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.

NOTE
Always add an appropriate amount of refrigerant. (For the refrigerant additional charge)
Too much or too little refrigerant will cause trouble.
To use the Vacuum Mode
(If the Vacuum mode is set, all valves of Indoor units and Outdoor units will be opened.)

WARNING
When installing and moving the air conditioner to another site, recharge after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement or IDU addition/replacement.
Vacuum mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "SVC" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button :: "Se3" Push the '●' button"] C --> D["Start the vacuum mode : "VACC"<br>ODU V/V open<br>ODU…](/content/2026/07/1525988/images/c02e83486ff37986c3d60aacb22b250125f3c261f9792d5087af5d1ed9f55599.jpg)

Vacuum mode off method
Dip switch off and push the reset button on Master unit PCB

CAUTION
ODU operation stops during vacuum mode. Compressor can't operate.
Thermal insulation of refrigerant piping
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a possibility of condensation drip, etc. Pay special attention to insulation work to ceiling plenum.

Ⓐ Heat insulation material
⑧ Pipe
© Outer covering(Wind the connection part and cutting part of heat insulation material with a finishing tape.)
| Heat insulation material | Adhesive + Heat - resistant poly-ethylene foam + Adhesive tape | |
| Outer covering | Indoor Vinyl tape | |
| Floor exposed | Water-proof hemp cloth + Bronze asphalt | |
| Outdoor | Water-proof hemp cloth + Zinc plate + Oily paint | |
NOTE
When using polyethylene cover as covering material, asphalt roofing shall not be required.
| Bad example | Do not insulate gas or low pressure pipe and liquid or high pressurepipe together. Liquid pipeGas pipePower cablesFinishing tapeInsulating materialCommunication cables | Be sure to fully insulate connecting portion.![]() These parts are not insulated. |
| Good example | Power cables Communication cables[Liquid pipe] Insulating materialPower cables Communication cables | ![]() ![]() |
Penetrations
Inner wall (concealed)

Outer wall Outer wall (exposed)


Floor (fireproofing)

Roof pipe shaft

Penetrating portion on fire limit and boundary wall

Ⓐ Sleeve
⑧ Heat insulating material
© Lagging
© Caulking material
E Band
⑤ Waterproofing layer
© Sleeve with edge
⑧ Lagging material
① Mortar or other incombustible caulking
① Incombustible heat insulation material
When filling a gap with mortar, cover the penetration part with steel plate so that the insulation material will not be caved in. For this part, use incombustible materials for both insulation and covering. (Vinyl covering should not be used.)
ELECTRICAL WIRING
Caution
- Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.

WARNING
Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with regulations and this installation manual. If power supply circuit has a lack of capacity or electric work deficiency, it may cause an electric shock or fire.
- Install the Outdoor Unit communication cable away from the power source wiring so that it is not affected by electric noise from the power source. (Do not run it through the same conduit.)
- Be sure to provide designated grounding work to Outdoor Unit.

CAUTION
Be sure to correct the outdoor unit to earth. Do not connect ground wire to any gas pipe, liquid pipe, lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
- Give some allowance to wiring for electrical part box of Indoor and Outdoor Units, because the box is sometimes removed at the time of service work.
- Never connect the main power source to terminal block of communication cable. If connected, electrical parts will be burnt out.
- Use 2-core shield cable for communication cable.(O mark in the figure below) If communication cable of different systems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations. ( Ⓧ mark in the figure below)
- Only the communication cable specified should be connected to the terminal block for Outdoor Unit communication.
![graph TD A["Outdoor Unit"] --> B["Indoor Unit"] B --> C["Remote control"] C --> D["Indoor Unit"] D --> E["Remote control"] E --> F["Indoor Unit"] F --> G["Remote control"] G --> H["Indoor Unit"] H --> I["Remote control"] I --> J["Indoor Unit"] J --> K["Remote control"] K --> L["Indoor Unit"] L --> M…](/content/2026/07/1525988/images/ad77ffda4c172adb4c2766073fa2cff972f15f5b9d48f505b7cb424c4afed88d.jpg)
![graph TD A["Outdoor Unit"] --> B["Indoor Unit"] B --> C["Remote control"] D["Outdoor Unit"] --> E["Indoor Unit"] E --> F["Remote control"] G["Indoor Unit"] --> H["Indoor Unit"] H --> I["Remote control"] J["Indoor Unit"] --> K["Indoor Unit"] K --> L["Remote control"]](/content/2026/07/1525988/images/d9c66ff6c24188afc5f2607cd0907b2a870e7a376c9f225b61173c3577b90608.jpg)
2-Core Shield Cable Multi-Core Cable
![graph TD subgraph Master Slave1 Slave2 A["Master Slave1 Slave2"] B["Indoor Unit"] C["Indoor Unit"] D["Indoor Unit"] E["Indoor Unit"] F["Indoor Unit"] end subgraph Outdoor Unit G["Outdoor Unit"] H["Outdoor Unit"] I["Outdoor Unit"] J["Outdoor Unit"] K["Outdoor Unit"] end A --> C B --> D C --> E D -->…](/content/2026/07/1525988/images/27541f0d8fbbd8280bce4e5c727210f57c73769f7464bcd3752f4b6dae2587e6.jpg)
![graph TD subgraph Master Slave1 Slave2 A1["Outdoor Unit Master Slave1 Slave2"] A2["Outdoor Unit Master Slave1 Slave2"] end subgraph Indoor Unit B1["Indoor Unit"] B2["Indoor Unit"] B3["Indoor Unit"] B4["Indoor Unit"] end B1 --> C["Remote controller"] B2 --> C B3 --> C B4 --> C C --> D["Remote control…](/content/2026/07/1525988/images/d7ec06692393e8daad7a0f07e80fa88dd1a7d86823d4c58fa26e4ed5791aa585.jpg)
2-Core Shield Cable Multi-Core Cable

CAUTION
- Use the 2-core shield cables for communication cables. Never use them together with power cables.
- The conductive shielding layer of cable should be grounded to the metal part of both units.
- Never use multi-core cable
- As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never install a phase leading capacitor.
- Make sure that the power unbalance ratio is not greater than 2%. If it is greater the units lifespan will be reduced.
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.

When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
- When connecting cable which is the same thickness, do as shown in the figure below.



- For wiring, use the designated power cable and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will strip the head and make proper tightening impossible.
- Over-tightening the terminal screws may break them.

CAUTION
When the 400 volt power supply is applied to "N" phase by mistake, check damaged parts in control box and replace them.
Control box and connecting position of wiring
- Remove all of the screws at front panel and remove the panel by pulling it forward.
- Connect communication cable between main and sub outdoor unit through the terminal block.
- Connect communication cables between outdoor unit and indoor units through the terminal block.
- When the central control system is connected to the outdoor unit, a dedicated PCB must be connected between them.
- When connecting communication cable between outdoor unit and indoor units with shielded cable, connect the shield ground to the earth screw.


WARNING
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
[Heat pump]

Communication and Power Cables
Communication cable
- Types : shielding cable
- Cross section : 1.0\~1.5 mm 4
- Maximum allowable temperature: 60 °C
- Maximum allowable cable length: under 1000 m
Remote control cable
- Types : 3-core cable
Central control cable
| Product type Cable type Diameter | ||
| ACP&AC Manager 2-core | cable (Shielding cable) 1.0~1.5 mm | 2 |
| AC Smart 2-core cable | (Shielding cable) 1.0~1.5 mm | 2 |
| Simple central controller 4-core | cable (Shielding cable) 1.0~1.5 mm | 2 |
Separation of communication and power cables
- If communication and power cables are run alongside each other then there is a strong likelihood of operational faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic coupling.
The tables below indicate our recommendation as to appropriate spacing of communication and power cables where these are to be run side by side
| Current capacity of power cable Spacing | ||
| 100V or more | 10 A 300 mm | |
| 50 A 500 mm | ||
| 100 A 1000 mm | ||
| Exceed 100 A 1500 mm | ||

NOTE
- The figures are based on assumed length of parallel cabling up to 100 m. For length in excess of 100 m the figures will have to be recalculated in direct proportion to the additional length of cable involved.
- If the power supply waveform continues to exhibit some distortion the recommended spacing in the table should be increased.
- If the cable are laid inside conduits then the following point must also be taken into account when grouping various cable together for introduction into the conduits
- Power cable(including power supply to air conditioner) and communication cables must not be laid inside the same
- In the same way, when grouping the power wires and communication cables should not be bunched together.

CAUTION
If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the apparatus must be carried out by a qualified person.
Wiring of main power supply and equipment capacity
- Use a separate power supply for the Outdoor Unit and Indoor Unit.
- Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
- The cable size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
- Specific wiring requirements should adhere to the wiring regulations of the region.
- Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.
- Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.

WARNING
- Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.
- Make sure to use specified cables for connections so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause heating or fire.
- Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

CAUTION
- Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
- Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.
Field Wiring
Single outdoor unit
![graph TD A["Outdoor Power supply (30 4 wires)"] --> B["Switch"] C["Indoor Power supply (10 2 wires)"] --> D["Fuse"] B --> E["Power cable (4 Wires Cable)"] D --> F["Power cable (2 Wires Cable)"] E --> G["Pull Box (Installer option)"] F --> H["Pull Box (Installer option)"] G --> I["Power cable (2 Wire…](/content/2026/07/1525988/images/26baee6695de378c6ce8cf13c04c7a365c7f2f1f3befe5647cb591e3d1998f9d.jpg)
! WARNING
- Indoor Unit ground wires are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
- Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources. - If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor and other parts.
[Heat Pump]
Between Indoor and Master Outdoor unit


The GND terminal at the main PCB is a '-' terminal for day contact, it is not the point to make ground connection.
Series outdoor units
When the power source is connected In series between the units.
![graph TD A["Outdoor Power supply (30 4wires)"] --> B["Switch"] B --> C["Fuse"] C --> D["Power cable (4 Wires Cable)"] D --> E["[Master"]] E --> F["[Slave1"]] E --> G["[Slave2"]] H["Indoor Power supply (10 2wires)"] --> I["Pull Box (installer option)"] I --> J["Power cable (2 Wires Cable)"] J --> K["…](/content/2026/07/1525988/images/7ddacf09c1367f50efaa3f812feeb19d0ce914a7ef1ce5e6c83b3b05feb5dd16.jpg)
| Frequency | Voltage range(V) | |
| Outdoor | Indoor | |
| 60 Hz | 400 V | 220 V |
| 50 Hz | 380~415 V | 220~240 V |

WARNING
When the total capacity is over than as follow, the power source do not use in series between the units.
The First terminal block could be burnt out. (Heat Pump : 68 Hp)
When the power source is supplied to Each outdoor unit individually.
![graph TD A["Outdoor Power supply (30 4wires)"] --> B["Switch"] C["Indoor Power supply (10 2wires)"] --> D["Fuse"] B --> E["R S T N"] B --> F["R S T N"] B --> G["R S T N"] B --> H["R S T N"] E --> I["Master"] F --> I G --> I H --> I I --> J["Slave1"] I --> K["Slave2"] L["Power cable (2 Wires Cable)"]…](/content/2026/07/1525988/images/5af8ec3452aa7903b94dca8f59830af2c65361966123e9e431aa632eafca2919.jpg)
| Frequency | Voltage range(V) | |
| Outdoor | Indoor | |
| 60 Hz | 400 V | 220 V |
| 50 Hz | 380~415 V | 220~240 V |
WARNING
- Indoor Unit ground wires are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
- Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources. - If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor and other parts.
[Heat Pump]
Between Indoor and Master Outdoor unit
| SODU.B | SODU.A | IDU.B | IDU.A | CEN.B | CEN.A | DRY1 | DRY2 | GND | 12V |


The GND terminal at the main PCB is a '-' terminal for dry contact.
It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
Example) Connection of transmission wire
[BUS type] [STAR type]
- Connection of communication cable must be installed like below figure between indoor unit to outdoor unit.
- Abnormal operation can be caused by communication defect, when connection of communication cable is installed like below figure(STAR type).
![graph TD A["Input Source"] --> B["Stage 1"] A --> C["Stage 2"] A --> D["Stage 3"] A --> E["Stage 4"] A --> F["Stage 5"] A --> G["Stage 6"] A --> H["Output"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#ccf,stroke:#333 style D fill:#ccf,stroke:#333 style E fill:#ccf,strok…](/content/2026/07/1525988/images/782c9e9ce0aa4ca8029b44e0d4f4e3a8b2d195155d9069f3b6f410a603c10dfc.jpg)
![graph TD A["Power Supply"] --> B["Switch 1"] A --> C["Switch 2"] A --> D["Switch 3"] A --> E["Switch 4"] A --> F["Switch 5"] A --> G["Switch 6"] A --> H["Switch 7"] A --> I["Switch 8"] A --> J["Switch 9"] A --> K["Switch 10"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#…](/content/2026/07/1525988/images/10cd5922cd8569a68c1e5554e2d8cfae7a807d74c789c541da1182b59d8fe073.jpg)
Example) Connection of power and communication cable (UX2)
Left Side Right Side


Front Side 1 Front Side 2


Main Power Connection Communication Connection



CAUTION
It should be wiring power cables or communication cables to avoid interference with the oil level sensor. Otherwise, That oil level sensor would be operated abnormally.
Example) Connection of power and communication cable (UX3)
Left Side Right Side


Front Side 1 Front Side 2


Main Power Connection Communication Connection



CAUTION
It should be wiring power cables or communication cables to avoid interference with the oil level sensor. Otherwise, That oil level sensor would be operated abnormally.
Checking the setting of outdoor units
Checking according to dip switch setting
- You can check the setting values of the Master outdoor unit from the 7 segment LED. The dip switch setting should be changed when the power is OFF.
Checking the initial display
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power. This number represents the setting condition. (For example, represents R410A 36 HP)
- Initial display order • Example) ARUN360LTH4
| Order | No Mean | |
| 1 | 8~16 Master model capacity | |
| 2 | 10~16 Slave 1 model capacity | |
| 3 | 10~16 Slave 2 model capacity | |
| 5 | 8~48 Total capacity | |
| 6 | 1 Cooling Only | |
| 2 Heat Pump | ||
| 3 Heat Recovery | ||
| 7 | 40 400 V model | |
| 46 460 V model | ||
| 22 220 V model | ||
| 8 | 1 LTE | |
| 2 LTS / LTN | ||
| 6 LTH | ||
| 1 | 2 | 3 | 5 | 6 | 7 | 8 |
| 10 | 12 | 14 | 36 | 2 | 40 | 6 |
- Master Unit • Slave Unit
| Dip switch setting Dip switch setting ODU Setting | ||
![]() | ![]() | Slave 1 |
![]() | Slave 2 | |
Automatic Addressing
The address of indoor units would be set by Automatic Addressing
- Wait for 3 minutes after supplying power.
(Master and Slave outdoor units, indoor units) - Press RED button of the outdoor units for 5 seconds. (SW01C)
- A "88" is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2\~7 minutes are required depending on numbers of connected indoor units
- Numbers of connected indoor units whose addressing is completed are indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated on the wired remote control display window. (CH01, CH02, CH03, ...., CH06 : Indicated as numbers of connected indoor units)
[Heat Pump (MAIN PCB)]


CAUTION
- In replacement of the indoor unit PCB, always perform Automatic addressing setting again (At that time, please check about using Independent power module to any indoor unit.)
- If power supply is not applied to the indoor unit, operation error occur.
• Automatic Addressing is only possible on the master Unit.
• Automatic Addressing has to be performed after 3 minutes to improve communication.
The Procedure of Automatic Addressing
![graph TD A["Power On"] --> B["Waiting 3 minutes"] B --> C["Press RED Button for 5 sec. (SW01C)"] C --> D["7-segment LED = 88"] D --> E["Don't press RED Button (SW01C)"] E --> F["Waiting about 2~7 minutes"] F --> G{7-segment LED = 88} G -->|YES| H["OK"] G -->|NO Check the connections| I["of communica…](/content/2026/07/1525988/images/bafa6dcae736df5b7e76756677d673dc8ed2f98069bdc8914af5ebe5055bad65.jpg)
Setting the function
Select the mode/function/option/value using '▶', '◀' Button and confirm that using the '●' button after dip switch No.5 is turned on.


| MODE FUNCTION OPTION VALUE ACTION | remarks | ||||||||||
| content | Display1 | content | Display2 | content Display3 | content | Display4 | implement | Display5 | |||
| Installation | Func | Cool & Heat Selector | Fn1 | oFF | op1~op2 | selected the option | - | - | change the set value | blank | save in EEPROM |
| Static pressure compensation | Fn2 | oFF | op1~op3 | selected the option | - | - | change the set value | blank | save in EEPROM | ||
| Night low noise | Fn3 | oFF | op1~op12 | selected the option | - | - | change the set value | blank | save in EEPROM | ||
| Overall defrost | Fn4 | on | oFF | selected the option | - | - | change the set value | blank | save in EEPROM | ||
| ODU address | Fn5 | - | - | 0~255 | set the value | change the set value | blank | save in EEPROM | |||
| Snow removal & rapid defrost | Fn6 | oFF | op1~op3 | selected the option | - | - | change the set value | blank | save in EEPROM | ||
| IDU capacity adjusting | Fn7 | on | oFF | selected the option | - | - | change the set value | blank | save in EEPROM | ||
| Target pressure adjusting | Fn8 | op1~op4 | selected the option | - | - | change the set value | blank | save in EEPROM | |||
| Comfort Operation | Fn9 | on | oFF | selected the option | - | - | change the set value | blank | save in EEPROM | ||
| Auto Dust Removal | Fn10 | on | oFF | selected the option | - | - | change the set value | blank | save in EEPROM | ||
* Functions save in EEPROM will be kept continuously, though the system power was reset.
Group Number setting
Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal should be connected to central control of Outdoor Unit with care for their polarity (A-A, B-B).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID from 0 to F for this purpose.
Outdoor Units (External PCB)

Example) Group number setting
1 F Group Indoor unit
1st number indicate the group number 2nd number point out indoor unit number
| Group recognizing the central controller |
| No.0 group (00~0F) |
| No.1 group (10~1F) |
| No.2 group (20~2F) |
| No.3 group (30~3F) |
| No.4 group (40~4F) |
| No.5 group (50~5F) |
| No.6 group (60~6F) |
| No.7 group (70~7F) |
| No.8 group (80~8F) |
| No.9 group (90~9F) |
| No. A group (A0~AF) |
| No. B group (B0~BF) |
| No. C group (C0~CF) |
| No. D group (D0~DF) |
| No. E group (E0~EF) |
| No. F group (F0~FF) |
Cool & Heat selector
mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn1" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "oFF", &quo…](/content/2026/07/1525988/images/468d633fb4a987157fc3c0f2d56877080366f9e8e6586db5654fd90253ae6260.jpg)
Function setting
| Switch control Function | |||
| Switch(Phase) Switch(Bottom) oFF op1(mode) op2(mode) | |||
| Right Left Not operate Cooling Cooling | |||
| Right Right Not operate Heating Heating | |||
| Left - Not operate Fan mode Off | |||


CAUTION
- Ask an authorized technician to setting a function.
- If do not use a function, set an off-mode.
- If use a function, first install a Cool & Heat selector.
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan discharge of ODU.
Static pressure compensation mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn2" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "op1~op3" P…](/content/2026/07/1525988/images/ce9b7e02ebffa996aa9b8b520bf1c6111ef000800e8b97f3642a4c90a0407fa6.jpg)
FAN Maximum RPM of each step
| Capacity 8~10 HP 12~16 HP | |||
| Max. RPM | Standard 730 950 | ||
| op1 760 1020 | |||
| op2 780 1050 | |||
| op3 800 1130 | |||
Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn3" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "op1~op12"…](/content/2026/07/1525988/images/4231eaead32a653f5a64fdaa472dd20733f49577063bfb1fdcd911f333b609c8.jpg)
Time Settings Noise
| Step | Judgment Time(Hr) | Operation Time(Hr) |
| op1 8 9 | ||
| op2 6.5 10.5 | ||
| op3 5 12 | ||
| op4 8 9 | ||
| op5 6.5 10.5 | ||
| op6 5 12 | ||
| op7 8 9 | ||
| op8 6.5 10 | ||
| op9 5 12 | ||
| op10 Continuous operation | ||
| op11 Continuous operation | ||
| op12 Continuous operation | ||
| Capacity | ||
| Heat Pump 8~10 HP 12~16 HP | ||
| Step Noise(dB) | ||
| op1~op3, op10 | 55 59 | |
| op4~op6, op11 | 52 56 | |
| op7~op9, op12 | 49 53 | |

CAUTION
- Request installer to set the function during installation.
- If ODU RPM changes, cooling capacity may go down.
Overall defrost mode
mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn4" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "on" ~ &quo…](/content/2026/07/1525988/images/2da4e6ac285afdd2dd0aac3c2afc77a0e9bed22110f304db72d569c618a455bc.jpg)
mode setting
-on: Operate overall defrost
- off: Operate partial defrost
CAUTION
- Ask an authorized technician to setting a function.
* ARUN***LTH4 models operate only overall defrost function. - Ask an authorized technician to setting a function. * ARUN***LTH4 models operate only overall defrost function.
Setting the ODU address
mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn5" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "0" ~ "…](/content/2026/07/1525988/images/61df204f274026d1de71aa8987e6847d4f80e3166b0a6ea1d5e7d2eef698f6f9.jpg)
! CAUTION
- Ask an authorized technician to setting a function.
- If use a function, first install a Central controller.
Snow removal & rapid defrost
mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn6" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "oFF", &quo…](/content/2026/07/1525988/images/db8df274d4f1c6fd70305c70bb35a86e75cce0f4b9113c29f493da9f4bd48b37.jpg)
mode setting
| setting Mode | |
| oFF Not setting | |
| op1 Snow removal mode | |
| op2 Rapid defrost mode | |
| op3 Snow removal mode. + Rapid defrost mode. | |

CAUTION
- Ask an authorized technician to setting a function.
- If do not use a function, set an off-mode.
IDU capacity adjusting
mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn7" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "on" ~ &quo…](/content/2026/07/1525988/images/b10bc01ef0f4ffe31712331a1742064939cc0af07deafe332ceb6d01ad418cac.jpg)

CAUTION
- Ask an authorized technician to setting a function.
* ARUN***LTH4 models operate only overall defrost function.
Target pressure adjusting
mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn8" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "HEAT", &qu…](/content/2026/07/1525988/images/c7e1d5dd9ae73586a293bb6e9df3c92f2f257cb0109826e788eaf0138d047ac4.jpg)
Setting
| mode | Purpose | Condensing temperature variation | Evaporating temperature variation | |
| “Heat” “Cool” | ||||
| op1 | Increase capacity Increase capacity | -3 °C +2 °C | ||
| op2 | Decrease power consumption | Increase capacity -1.5 °C | -2 °C | |
| op3 | Decrease power consumption | Decrease power consumption | +2.5 °C -4 °C | |
| op4 | Decrease power consumption | Decrease power consumption | -4.5 °C -6 °C | |

CAUTION
- Ask an authorized technician to setting a function.
- If do not use a function, set an off-mode.
- Change a power consumption or capacity.
Comfort Operation
mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn9" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "on" ~ &quo…](/content/2026/07/1525988/images/d09e2236b046ef189f77aa83690fcd03da104c84975cb0bf11286da96acd35c2.jpg)

CAUTION
- Ask an authorized technician to setting a function.
- If do not use a function, set an off-mode.
Auto Dust Removal
This function make a clean heat exchanger from dust.
mode setting method
![graph TD A["Master unit PCB DIP switch on : No.5"] --> B["Select the mode using '►', '◄' Button : "Func" Push the '●' button"] B --> C["Select the Function using '►', '◄' Button : "Fn10" Push the '●' button"] C --> D["Select the Option using '►', '◄' Button : "on" ~ &qu…](/content/2026/07/1525988/images/5bb79cdc0ca94ee2e7b3421b6d75c8613f4c3c9fdca697e19d55642573b09d20.jpg)

CAUTION
- Ask an authorized technician to setting a function.
- If do not use a function, set an off-mode.
Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number.
Ex)

| Display Title | Cause of Error | ||||
| Indoor unit related error | 0 1 | - | Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short | ||
| 0 2 | - | Inlet pipe temperature sensor of indoor unit | Inlet pipe temperature sensor of indoor unit is open or short | ||
| 0 3 | - | Communication error : wired remote controller ↔ indoor unit | Failing to receive wired remote controller signal in indoor unit PCB | ||
| 0 4 | - | Drain pump Malfunction of drain pump | |||
| 0 5 | - | Communication error : outdoor unit ↔ indoor unit | Failing to receive outdoor unit signal in indoor unit PCB | ||
| 0 6 | - | Outlet pipe temperature sensor of indoor unit | Outlet pipe temperature sensor of indoor unit is open or short | ||
| 0 9 | - | Indoor EEPROM Error | In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFFF | ||
| 1 0 | - | Poor fan motor operation | Disconnecting the fan motor connector / Failure of indoor fan motor lock | ||
| Outdoor unit related error | 2 1 | * | Master Outdoor Unit Inverter Compressor IPM Fault | Master Outdoor Unit Inverter Compressor Drive IPM Fault | |
| 2 2 | * | Inverter Board Input Over Current(RMS) of Master Outdoor Unit | Master Outdoor Unit Inverter Board Input Current excess (RMS) | ||
| 2 3 | * | Master Outdoor Unit Inverter Compressor DC link Low Voltage | DC charging is not performed at Master Outdoor Unit after starting relay turn on. | ||
| 2 4 | * | Master Outdoor Unit High Pressure Switch | System is turned off by Master Outdoor Unit high pressure switch. | ||
| 2 5 | * | Master Outdoor Unit Input Voltage High/ Low Voltage | Master Outdoor Unit input voltage is over 506V or below 414V | ||
| 2 | 6 | * | Master Outdoor Unit Inverter Compressor Start Failure | The First Start Failure by Master Outdoor Unit Inverter Compressor Abnormality | |
| 2 | 9 | * | Master Outdoor Unit Inverter Compressor Over Current | Master Outdoor Unit Inverter Compressor Fault OR Drive Fault | |
* If error code displayed is apart from above list, refer related indoor unit's manual.
| Display Title | Cause of Error | ||||
| Outdoor unit related error | 3 | 2 * | Master Outdoor Unit Inverter Compressor1 High Discharge Temperature | Master Outdoor Unit Inverter Compressor1 High Discharge Temperature | |
| 3 | 3 * | Master Outdoor Unit Inverter Compressor2 High Discharge Temperature | Master Outdoor Unit Inverter Compressor2 High Discharge Temperature | ||
| 3 | 4 * | High Pressure of Master Outdoor Unit High Pressure of Master Outdoor Unit | Pressure of Master Outdoor Unit | ||
| 3 | 5 * | Low Pressure of Master Outdoor Unit Low Pressure of Master Outdoor Unit | Pressure of Master Outdoor Unit | ||
| 3 | 6 * | Master Outdoor Unit Low Compression Ratio Limited | Master Outdoor Unit Low Compression Ratio Limited | ||
| 4 | 0 * | Master Outdoor Unit Inverter Compressor CT Sensor Fault | Master Outdoor Unit Inverter Compressor CT Sensor open or short | ||
| 4 | 1 * | Master Outdoor Unit Inverter Compressor1 Discharge Temperature Sensor Fault | Master Outdoor Unit Inverter Compressor Discharge Temperature Sensor open or short | ||
| 4 | 2 * | Master Outdoor Unit Low Pressure Sensor Fault | Master Outdoor Unit Low Pressure Sensor open or short | ||
| 4 | 3 * | Master Outdoor Unit High Pressure Sensor Fault | Master Outdoor Unit High Pressure Sensor open or short | ||
| 4 | 4 * | Master Outdoor Unit Air Temperature Sensor Fault | Master Outdoor Unit Air Temperature Sensor open or short | ||
| 4 | 5 * | Master Outdoor Unit Heat Exchanger Temperature Sensor (Front side) Fault | Master Outdoor Unit Heat Exchanger Temperature Sensor(Front side) open or short | ||
| 4 | 6 * | Master Outdoor Unit Suction Temperature Sensor Fault | Master Outdoor Unit Suction Temperature Sensor open or short | ||
| 4 | 7 * | Master Outdoor Unit Inverter Compressor2 Discharge Temperature Sensor Fault | Master Outdoor Unit Inverter Compressor2 Discharge Temperature Sensor open or short | ||
| 4 | 9 * | Master Outdoor Unit Faulty IPM Temperature Sensor | Master Outdoor Unit IPM Temperature Sensor short/open | ||
| 5 | 0 * | Omitting connection of R, S, T power of Master Outdoor Unit | Omitting connection of Master outdoor unit | ||
| 5 | 1 * | Excessive capacity of indoor units | Excessive connection of indoor units compared to capacity of Outdoor Unit | ||
| 5 | 2 * | Communication error : inverter PCB → Main PCB | Failing to receive inverter signal at main PCB of Master Outdoor Unit | ||
| 5 | 3 * | Communication error : indoor unit → Main PCB of Outdoor Unit | Failing to receive indoor unit signal at main PCB of Outdoor Unit . | ||
| 5 | 7 * | Communication error : Main PCB → inverter PCB | Failing to receive signal main PCB at inverter PCB of Master Outdoor Unit | ||
| 5 | 9 * | Wrong combination of Outdoor Units | Installation might be mixed with old series models(Multi V III,II ...) | ||
| 6 | 0 * | Inverter PCB EEPROM Error of Master Outdoor Unit | Access Error of Inverter PCB of Master Outdoor Unit | ||
| 6 | 2 * | Master Outdoor Unit Inverter Heatsink High Temperature | System is turned off by Master Outdoor Unit Inverter Heatsink High Temperature | ||
| 6 | 5 * | Master Outdoor Unit Inverter Heatsink Temperature Sensor Fault | Master Outdoor Unit Inverter Heatsink Temperature Sensor open or short | ||
| 6 | 7 | * | Master Outdoor Unit Fan Lock Restriction | of Master Outdoor Unit | |
| Display Title | Cause of Error | |||||
| Outdoor unit related error | 7 | 1 | * | Converter CT Sensor Error of Master Outdoor Unit | Converter CT Sensor open or short of Master Outdoor Unit | |
| 7 | 5 | * | Master Outdoor Unit Fan CT Sensor Error | Master Outdoor Unit Fan CT Sensor open or short | ||
| 7 | 6 | * | Master Outdoor Unit Fan DC Link High Voltage Error | Master Outdoor Unit Fan DC Link High Voltage Error | ||
| 7 | 7 | * | Master Outdoor Unit Fan Over Current Error | Master Outdoor Unit Fan Current is over 5A | ||
| 7 | 9 | * | Master Outdoor Unit Fan Start Failure Error | Master Outdoor Unit Fan First Position Sensing Failure | ||
| 8 | 6 | * | Master Outdoor Unit Main PCB EEPROM Error | Communication Fail Between Master Outdoor Unit Main MICOM and EEPROM or omitting EEPROM | ||
| 8 | 7 | * | Master Outdoor Unit Fan PCB EEPROM Error | Communication Fail Between Master Outdoor Unit Fan MICOM and EEPROM or omitting EEPROM | ||
| Outdoor unit related error | 1 | 0 | 4 | * | Communication Error Between Master Outdoor Unit and Other Outdoor Unit | Failing to receive Slave Unit signal at main PCB of Master Outdoor Unit |
| 1 | 0 | 5 | * | Master Outdoor Unit Fan PCB Communication Error | Failing to receive fan signal at main PCB of Master unit. | |
| 1 | 0 | 6 | * | Master Outdoor Unit FAN IPM Fault Error | Instant Over Current at Master Outdoor Unit Fan IPM | |
| 1 | 0 | 7 | * | Master Outdoor Unit Fan DC Link Low Voltage Error | Master Outdoor Unit Fan DC Link Input Voltage is under 380V | |
| 1 | 1 | 3 | * | Master Outdoor Unit Liquid pipe Temperature Sensor Error | Liquid pipe temperature sensor of Master Outdoor Unit is open or short | |
| 1 | 1 | 4 | * | Master Outdoor Unit Subcooling Inlet Temperature Sensor Error | Master Outdoor Unit Subcooling Inlet Temperature Sensor Error | |
| 1 | 1 | 5 | * | Master Outdoor Unit Subcooling Outlet Temperature Sensor Error | Master Outdoor Unit Subcooling Outlet Temperature Sensor Error | |
| 1 | 1 | 6 | * | Master Outdoor Unit Oil Level Sensor Error | Oil Level Sensor of Master Outdoor Unit is open or short | |
| 1 | 4 | 5 | * | Master outdoor unit Main Board - External Board communication Error | Master outdoor unit Main Board - External Board communication Error | |
| 1 | 5 | 1 | * | Failure of operation mode conversion at Master Outdoor Unit | Failure of operation mode conversion at Master Outdoor Unit | |
| 1 | 5 | 3 | * | Master Outdoor Unit Heat Exchanger Temperature Sensor (upper part) Fault | Master Outdoor Unit Heat Exchanger Temperature Sensor (upper part) Fault | |
| 1 | 5 | 4 | * | Master Outdoor Unit Heat Exchanger Temperature Sensor (lower part) Fault | Master Outdoor Unit Heat Exchanger Temperature Sensor(lower part) open or short | |
| 1 | 8 | 2 | * | Master outdoor unit External Board Main-Sub Micom communication Error | Master Outdoor Unit Main Board Main-Sub Micom communication failed | |
| 1 | 9 | 3 | * | Master Outdoor Unit Fan Heatsink High Temperature | System is turned off by Master Outdoor Unit Fan Heatsink High Temperature | |
| 1 | 9 | 4 | * | Master Outdoor Unit Fan Heatsink Temperature Sensor Fault | Master Outdoor Unit Fan Heatsink Temperature Sensor open or short | |
CAUTION FOR REFRIGERANT LEAK
The installer and system specialist shall secure safety against leakage according to local regulations or standards.
The following standards may be applicable if local regulations are not available.
Introduction
Though the R410A refrigerant is harmless and incombustible itself, the room to equip the air conditioner should be large to such an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room.
Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the unit of kg/m 3 (Freon gas weight per unit air volume) for facilitating calculation.
Limiting concentration: 0.44 kg/m 3 (R410A)
![graph LR A["Outdoor unit"] --> B["(No.1 system)"] B --> C["Indoor unit"] C --> D["Flow of refrigerant"] D --> E["Room where refrigerant leaks (Refrigerant of the whole No.1 system flows out.)"] E --> F["Indoor unit"]](/content/2026/07/1525988/images/c4c4a07f96ca1d089e1f7aedd55d81e16ad716deee0d38f9b4c43d041889836a.jpg)
Checking procedure of limiting concentration
Check limiting concentration along following steps and take appropriate measure depending on the situation.
Calculate amount of all the replenished refrigerant (kg) per each refrigerant system.

Calculate minimum room capacity
Calculate room capacity by regarding a portion as one room or the smaller room.
- Without partition - With partition and with opening which serve
as passage of air to adjoining room


- With partition and without opening which serve as passage of air to adjoining room
![graph TD A["Outdoor unit"] --> B["Indoor unit"] B --> C["Smallest room"] C --> D["Indoor unit"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333](/content/2026/07/1525988/images/efe6dd51141c84e079e10a69bf52fd55a7a3bfef77a19f70f9b1d3c652775065.jpg)
Calculate refrigerant concentration

In case the result of calculation exceeds the limiting concentration, perform the same calculations by shifting to the second smallest, and the third smallest rooms until at last the result is below the limiting concentration.
In case the concentration exceeds the limit
When the concentration exceeds the limit, change original plan or take one of the countermeasures shown below:
- Countermeasure 1
Provide opening for ventilation.
Provide 0.15% or more opening to floor space both above and below door, or provide opening without door.
- Countermeasure 2
Provide gas leak alarm linked with mechanical ventilator.
Reducing the outdoor refrigerant qty.
![graph TD A["Countermeasure 2"] --> B["Gas leak alarm"] B --> C["Mechanical ventilator"] D["Indoor unit"] --> E["Opening effective to ventilation"] F["Countermeasure 1"] --> G["Opening effective to ventilation"]](/content/2026/07/1525988/images/ae831a9b80f3c86598c7d5ebf1696b262cdb1183a873b67ef621797c4b2f49cd.jpg)
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air.
INSTALLATION GUIDE AT THE SEASIDE
! CAUTION
• Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
- Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
- If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.

In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

- It should be strong enough like concrete to prevent the sea wind from the sea.
- The height and width should be more than 150% of the outdoor unit.
- It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
Select a well-drained place.
- Periodic (more than once/year) cleaning of the dust or salt particles stuck on the heat exchanger by using water




































Liquid pipeGas pipePower cablesFinishing tapeInsulating materialCommunication cables
These parts are not insulated.
Power cables Communication cables[Liquid pipe]
Insulating materialPower cables Communication cables