| Product Type | Manual Pull Station |
| Brand | Honeywell |
| Model | Fire-Lite BG-12LSP |
| Series | Fire-Lite |
| Color | Red |
| Material | Polycarbonate |
| Dimensions (H x W x D) | 4.75 in x 3.5 in x 1.75 in (121 mm x 89 mm x 44 mm) |
| Weight | 0.5 lb (227 g) |
| Operating Voltage | 24 VDC (15-32 VDC range) |
| Standby Current | 250 µA |
| Alarm Current | 50 mA |
| Operating Temperature | 32°F to 120°F (0°C to 49°C) |
| Relative Humidity | 10% to 93% non-condensing |
| Wiring | 2-wire (SLC loop) |
| Reset Method | Key-operated reset |
| Mounting | Surface mount or semi-flush (backbox included) |
| Indicators | LED for alarm status (red) |
| Compatibility | Fire-Lite addressable fire alarm panels |
| Certifications | UL, ULC, CSFM listed |
| Installation | Indoor dry location |
| Maintenance | Periodic test functionality; clean with damp cloth |
| Repair | Replace entire unit if faulty; no user-serviceable parts |
| Included Accessories | Mounting screws, reset key |
Frequently Asked Questions - Fire-Lite BG-12LSP HONEYWELL
What is the Honeywell Fire-Lite BG-12LSP?
The Honeywell Fire-Lite BG-12LSP is an addressable manual pull station used in fire alarm systems to initiate an alarm manually. It is part of the Fire-Lite series and is compatible with Fire-Lite control panels.
How do I install the BG-12LSP pull station?
Install the BG-12LSP using the included mounting screws on a standard electrical box. Connect the SLC loop wires (positive and negative) to the terminal block. Ensure the address is set on the rotary switches. Refer to the panel manual for proper addressing.
How do I reset the BG-12LSP after activation?
Use the included reset key to turn the key lock clockwise to the reset position. This will physically reset the pull station and clear the alarm condition. The panel must also be reset.
What voltage does the BG-12LSP require?
The BG-12LSP operates at 24 VDC (nominal), with a range of 15 to 32 VDC provided by the fire alarm panel via the SLC loop.
Is the BG-12LSP weatherproof?
No, the BG-12LSP is designed for indoor dry locations only. It should not be exposed to water or extreme humidity.
What are the dimensions of the BG-12LSP?
The dimensions are approximately 4.75 in x 3.5 in x 1.75 in (121 mm x 89 mm x 44 mm).
Can the BG-12LSP be used with other brands of fire panels?
The BG-12LSP is specifically designed for Fire-Lite addressable panels. It may not be compatible with other brands unless they support the same communication protocol.
How do I test the BG-12LSP?
To test, physically pull the handle until it latches. The LED should light red, and the panel should indicate an alarm. Reset with the key. Perform this test weekly per NFPA guidelines.
What is the standby current of the BG-12LSP?
The standby current is 250 µA at 24 VDC. Alarm current is 50 mA.
Does the BG-12LSP come with a warranty?
Yes, Honeywell provides a limited warranty of typically 5 years. Contact Honeywell support for warranty claims.