Vemer ADR-D Out - Analyseur réseau

ADR-D Out - Analyseur réseau Vemer - Free user manual and instructions

Find the device manual for free ADR-D Out Vemer in PDF.

📄 22 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Vemer ADR-D Out - page 4
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Digital Temperature Controller
Model ADR-D Out
Brand Vemer
Dimensions (HxWxD) 85 x 85 x 30 mm
Weight 0.1 kg
Power Supply 230 V AC 50/60 Hz
Power Consumption < 3 W
Display Type LCD with backlight
Temperature Range -10°C to 50°C
Control Type PID / On-Off
Output Type Relay 5 A
Sensor Type NTC 10kΩ @ 25°C
Protection Rating IP20
Operating Temperature 0°C to 50°C
Storage Temperature -20°C to 60°C
Main Functions Temperature control, heating/cooling, setpoint adjustment, hysteresis, calibration
Cleaning and Maintenance Wipe with a dry, soft cloth. Do not use solvents or water.
Safety Features Overheat protection, sensor failure alarm
Spare Parts and Repairability No user-serviceable parts. Contact Vemer support for repairs.
Documentation User manual available for free download

Frequently Asked Questions - ADR-D Out Vemer

How do I install the Vemer ADR-D Out thermostat?
Turn off power before installation. Connect the thermostat according to the wiring diagram in the manual. Use appropriate cables and ensure proper grounding.
How can I set the desired temperature?
Press the SET button, use the up/down arrows to adjust the setpoint, then press SET again to confirm. The display will show the target temperature.
The display shows 'E1' or 'E2' error code. What does it mean?
Error E1 indicates a sensor short circuit, E2 indicates a sensor open circuit. Check the sensor connection and replace if necessary.
Can I use this controller with a cooling system?
Yes, the ADR-D Out can be configured for either heating or cooling mode. Change the mode in the parameter settings (refer to manual).
How often should I clean the thermostat?
Clean the exterior with a dry cloth as needed. Avoid moisture. No internal cleaning is required.
What is the hysteresis and how do I adjust it?
Hysteresis is the temperature difference between activation and deactivation. It can be adjusted in the advanced settings (parameter Hy). Typical range is 0.5°C to 5°C.
Can I calibrate the temperature reading?
Yes, calibration offset can be set in the parameters (parameter CA). Use a reference thermometer to adjust.
Is the display backlight always on?
The backlight turns on when any button is pressed and turns off after a few seconds of inactivity to save energy.
What power supply is required?
The device requires 230 V AC 50/60 Hz. Ensure the supply voltage matches before connection.
Where can I find the user manual?
The manual is available for free download on the official Vemer website or via notice-facile.com.

User questions about ADR-D Out Vemer

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Analyseur réseau in PDF format for free! Find your manual ADR-D Out - Vemer and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ADR-D Out by Vemer.

USER MANUAL ADR-D Out Vemer

■ Safety warnings Page 30
■ Technical specifications Page 30
■ Description of instrument Page 31
■ Keys Page 32
■ Setting the parameters Page 32
■ Displaying the measurement pages Page 39
■ Measurement and calculation method Page 49
■ Reference standards Page 50
■ ADR-R out dimensions and connection diagrams Page 24-25
■ ADR-D out dimensions and connection diagrams Page 26-27

SAFETY WARNINGS

■ During the installation and operation of the instrument, the following should be noted:

1) The instrument should be installed by a competent person
2) Follow the connection diagrams to the letter when installing the instrument
3) When connecting the instrument, always use the TA x/5 A
4) The appliance should be installed in a panel where the terminals will be inaccessible after installation
5) The voltage and current circuit terminals may be connected with a maximum rated voltage of 300 V eff. with respect to earth
6) The panel should be wired in line with the relevant CEI standards
7) Do not power or connect the instrument if any part of it is damaged

NOTE:

  • The VEMER network analysers are designed for use in environments with over-voltage category III and pollution level 2, in accordance with the CEI-EN 61010-I standard.
  • The electrical system of the building where the instrument is to be installed should contain a switch or isolator. This should be close to the instrument and within easy reach of an operator. An over-current protection device should be fitted.

Important: when the power supply is cut off, there should be no signal at the measurement inputs (current or voltage).

TECHNICAL SPECIFICATIONS

• P o wer supply: 230 VAC (-15%/+10%)
• F frequency: 50/60 Hz
• Maximum consumption: 5 VA
- Display: rear-lit LCD
• V oltmeter inputs: max 500 VAC, 47÷63Hz (phase-phase concatenated)
- Ammeter inputs: max 6 A, 47÷63 Hz
- Scales: 1 voltage with end of scale 500 V (phase-phase concatenated) 2 current with end of scale at 1.25 A and 6 A
- Precision:

- Voltage: 0.5% of the end of scale value (min 10 V)

- Current: 0,5% of the end of scale value (min. 20 mA)

- P o wer: 1% of the end of scale value

  • F frequency: ±0,1 Hz (47÷63 Hz)
  • Active energy CEI-EN 61036 class 2
  • Reactive energy CEI-EN 61268 class 3

• TV available: primary 1÷9999 V +10÷65kV; secondary 230 V
• T A available: primary 1÷9999 A; secondary 5 A
• 2 x 250 VAC 2 A relay outputs (105 x VDE0435 operations)
- Operating temperature: 0 ÷ +50^ C
- Relative humidity: 10% ÷ 90% non-condensing
- Containers:

- Rear panel version: material in class V0 in accordance with the UL 94 standard, standard dimensions 72 × 72 ~mm in accordance with the DIN 43700 standard

- Modular version: material in class V0 in accordance with the UL 94 standard, 4 DIN module containers, colour RAL-7035 grey

Network analyser

Code ModelDescription

VN794400 ADR-R-outNetwork analyser with relay output, rear panel version

VN795100 ADR-D-outNetwork analyser with relay output, modular version

DESCRIPTION OF INSTRUMENT

Display

0.8:8.8 8.8.8.8.8.8.8 VOLTAGE CURRENT FREQUENCY APPARENT REACTIVE ENERGY 8.8.8.8.8.8.8 GMk Wh Hz VARh cos φ POWER V 3 2 A ADR pK T 1 4 VOLTAGE CURRENT FREQUENCY APPARENT REACTIVE ENERGY cos φ POWER GMk Wh Hz VARh V A 2 3

  • ① Numerical fields for the display of the values measured
  • ② Type of measurement taking place
  • ③ Measurement unit
  • ④ Phase symbols

KEYS

Vemer ADR-D Out - KEYS - 1

Scroll to the next page and parameter setting

Vemer ADR-D Out - KEYS - 2

Scroll to the previous page and parameter setting

Vemer ADR-D Out - KEYS - 3

Display of the system values

Vemer ADR-D Out - KEYS - 4

Display of the peak values to be measured and selection of the parameters in the programming stage

SETTING THE PARAMETERS

First installation programming

■ To gain access to the first installation programming menu, the instrument has to be powered by holding down the "up" (▲) and "down" (▼) keys together until the display is lit up
■ The parameters that can be programmed by the user are the following, in order:
• Primary TV (fixed secondary 230 V)
• Primary TA (fixed secondary 5 A)
For a new parameter setting, the instrument should be switched off then on again by holding down the "up" (▲) and "down" (▼) keys together until the display is lit up

Important: before switching the instrument off, disconnect the measurement (current and voltage)

TV setting

VOLTAGE 0230v tr. Pr. pK VOLTAGE 0231v tr. Pr. T

- Press the "up" (▲) or "down" (▼) keys to select the required value of the

flashing digit or prefix "k" (flashing = deactivated, fixed = active)

• T o go to the next digit, press "pK"
- T o confirm the value set and go to the next window, press "T"

TA setting

CURRENT 0005 A tr. Pr. PK CURRENT 0006 A tr. Pr.

- Same procedure as TV setting

Note: for the primaries of the TV and TA, any value between 0001 and 9999 may be set. The secondaries are set to 230V and 5A respectively. For the TV primary, it is also possible to set a value between 10kV and 65kV.

■ When “T” is pressed, all the symbols of the display will come on for approximately 3 seconds, followed by the display of the output relay status page.

Note: if the power is cut off during programming, the instrument will memorise all the settings up to the moment when this occurs.

Programming in normal operation

■ Access to the programming menu in normal operation is gained by holding the "pK" key down for approximately 3 seconds.
■ The parameters that can be set by the user are the following, in order:

  • D a te/time
  • Relay output 1 programming (see page 8)
  • Relay output 2 programming (see page 8)
  • Integration time for the calculation of the integral mean of the power ratings
    • Display rear lighting management
    • Zeroing of active energy meters
    • Zeroing of reactive energy meters
  • Zeroing of peaks
  • Change of protection password
    ■ Press the “up” (▲) or “down” (▼) keys to scroll through the setting menus Press “T” from the end menu to leave the programming (this takes place automatically if no key is pressed for approximately 60 seconds)

■ Before entering the programming menu, the user is asked to enter the password (default "0000"). If an incorrect password is entered, the parameters will be displayed but it will not be possible to modify them.

Setting the date and time

15:24 12 02 02 pK 15:24 h 12 02 02

  • Press T from the "Time" menu to enter the time and date setting page
  • Press the “up” (▲) or “down” (▼) keys to select the value of the flashing digit required
  • Press "pK" to go to the next digit
  • Press "T" to return to the main programming page

Setting the integration time

15 AUE-RAGE 16 AUE-RAGE

  • Press T from the "Average" menu to enter the mean power rating integration time setting page
  • Press the “up” (▲) or “down” (▼) keys to select the value of the integration time required
  • It is possible to set an integration time from a minimum of 1' to a maximum of 60' (the default value is 15')
  • Press "T" to return to the main programming page

Rear lighting management

mQ LIGHT LINE YES LIGHT

  • Press T from the "Light" menu to enter the rear lighting setting page
  • Press the "up" (▲) or "down" (▼) keys to select one of the options "NO" (rear lighting deactivated), "YES" (activated) or "TIME" (activated for approximately 60 seconds after a key is pressed)
  • Press "T" to return to the main programming page

Zeroing the active/reactive energy and peak meters

mΩ ACTIVE ENERGY ,RESET pK

YES ACTIVE ENERGY -RESET

  • Press T from the "Reset" menu to enter the active energy reset page
  • Press the "up" (▲) or "down" (▼) keys to select one of the options "YES" (active energy zeroing) or "NO"
  • T o confirm the value set and go to the next window, press "T"
  • The same procedure is then used to zero the reactive energy and peak meters
  • Press "T" to return to the main programming page

Changing the password

OK OK CodE OK OK CodE

  • Press T from the "Code" menu to enter the password setting page
  • Press the "up" (▲) or "down" (▼) keys to select the first digit (flashing)
  • Press "pK" to go to the next digit
  • Press "T" to save the password and return to the main programming menu

Note: if you forget the password entered, the default password ("0000") can be reset by resetting the instrument (this may also occur accidentally if the power is cut off)

Relay programming

■ From the relay 1 (or 2) menu in normal programming, press “T” to gain access to the relay 1 (2) programming menu
■ The parameters that can be set by the user are the following, in order:
- Operating value
- Latching
- Alarm mode
- Relay operating mode
- Set-point value
- Differential value
- Relay activation delay
■ Press "T" to go from one menu to the next Press T from the "Delay" menu to return to the relay 1 (or 2) menu

Vemer ADR-D Out - Relay programming - 1

flowchart
graph LR
    A["VOLTAGE"] --> B["1"]
    B --> C["Power"]
    C --> D["pK"]
    D --> E["Active"]
    E --> F["2"]
    F --> G["T"]

- Press the “up” (▲) or “down” (▼) keys to select the value for which the relay is to intervene.

The values that can be selected are as follows, in order: voltage, current, active power, apparent power, reactive power, cos w, mean active power, mean apparent power, mean reactive power, active energy and concatenated voltage

- Press "pK" to select the phase (where possible)

The absence of the phase symbol at the centre of the display indicates the system value

- Press "T" to confirm the value set

MO LATCH

YES LATCH

- Press "up" (▲) or "down" (▼) to activate or deactivate "Latching" mode (maintenance of the alarm condition until a key is pressed), and confirm with "T"

- When “Latching” mode is enabled, the display will go to the measurement page for the value that has activated the relay (flashing) when the conditions that generated the alarm are removed

R11 ALAr Node

LO RLAr Nod

- Select the maximum alarm mode "Hi" or the minimum "Lo" with the "up" (▲) or "down" (▼) keys and confirm with "T"

d11 rEL Nod

rE rEL Rod

- Select the relay operating mode (direct "dl" or reverse "rE") with the "up" (▲) or "down" (▼) key and confirm with "T"

SELECT W ACTIVE POWER pK SELECT W ACTIVE POWER 0000003.0 T

- Set the set-point value for the measurement selected (visible on the display display). Use the "up" (▲) or "down" (▼) keys to set the flashing digit and "pK" to go to the next digit.

Press "T" to confirm

ACTIVE 995 W 1 3 2 994 995 → ACTIVE 2.98 k W POWER Active

- Set the differential value (hysteresis) with the same procedure as that for the set-point

ALAr Pod 4.0 ALAr Pod

- Set the relay activation delay value (in seconds) with the same procedure as that for the set-point

Note: if the energy operation is selected (active for relay 1 or reactive for relay 2), the set-up movements from latching mode onwards will not be displayed, as they serve no purpose In this case, the relays will not operate as alarms, but as consumption indicators for active/reactive energy

- A window will then be displayed for the setting of the energy value corresponding to each impulse

0020 k Win VARh PULSE OK 0021 k Wh VARh PULSE 1

  • Press the "up" (▲) or "down" (▼) keys to select the value of the flashing digit and pK to go to the next digit
  • By default, the weight of the impulse (set on calibration and on each modification of the TA/TV) is equivalent to:

  • 1 impulse every "20 x value primary TA" Wh/varh, for primary TV up to 230 V

  • 1 impulse every "40 x value primary TA" Wh/varh, for primary TV from 230 to 580 V
  • for the primary TV over 580 V, the impulse output is inactive These are the minimum values that can be set for the impulse weight The duration of the impulse is always constant and equivalent to 100ms

DISPLAYING THE MEASUREMENT PAGES

■ When the instrument is switched on (or after the programming stage), the first page (relay status) is displayed after approximately 3 seconds with the display completely on
■ When the “up” key (▲) is pressed from the first page, all the other measurement pages are displayed in sequence. Press the “up” key (▲) from the last page to return to the main page.

Note: in the event of incorrect entry (current polarity inverted or no correspondence between phase voltage and current), the phases involved are highlighted and the number for the group of symbols at the centre of the display is cancelled.

1) Relay status page

OFF 1 2 REL On

- The status of the two relays is displayed ("ON" or "OFF")

1b) Relay switching page

OFF 1 pK REL On 10:35 h 12 07 02 pK 0000 176.2 h pK ▲ ▼ T

  • Press the "pK" repeatedly from the relay status page to display the following, in order:
  • the instant when the last switching operation took place on the relay indicated (press "T" to move from one relay to another), expressed in time and date
  • the number of hours that has lapsed from the last reset of the instrument and the switching operation, expressed in hours and tenths of an hour
  • Press the "up" key (▲) at any time to go to the next page

Note: when “pK” and “T” are pressed and held down together for 3 seconds, the switching of both relays is forced for approximately 30 seconds (or a 100 ms impulse is forced if the relays are set as “consumption indicators”). This status is confirmed by the complete lighting up of the central symbol in the display.

2) Overall page

3.45 k W V A 400 8.66

  • The system voltage and current and the active system power rating are displayed
  • Press "pK" to display the value set for the TA primary. Press "T" to display the value set for the TV primary

Note: if the voltage V or the current I are >999, the words “Voltage” and/or “Current” will flash to indicate that the measurement unit is not complete (the prefixes 'k' or 'M' are missing)

3) Phase voltage page

VOLTAGE 230 v 230 230 3 2 1 VOLTAGE 400 v pK

• The phase voltages are displayed.

If the three phase system has no neutral, the voltages refer to a fictitious star delta centre

- Press "T" to display the system voltage page

3a) Phase voltage peak value page

VOLTAGE 237 v_v 1 2 3 237 231 pK VOLTAGE 1305 h pK 12 07 02 VOLTAGE h 0000 179.7 T

- If the "pK" is pressed repeatedly from one of the two phase voltage pages, the following are displayed in order:

- the voltage peak values (phase or system), with the "V" measurement unit flashing

- the instant when the peak occurred (time and date flashing if the clock has not yet been set)

- the number of hours lapsed between the start-up of the instrument and the occurrence of the peak, in hours and tenths of one hour

- Press "up" (▲) at any time to go to the next page

4) Concatenated voltage page

VOLTAGE 400 V 1² 1³ → 2³ 400 400 pK ▲ ▼ T

• The voltages concatenated between the phases are displayed

5) Phase current page

CURRENT 5.00 A 1 3 2 5.00 5.00 T

CURRENT 8.66 A pK

• The phase currents are displayed
- Press "T" to display the system current

5a) Phase current peak value pages

CURRENT 5.04 A_A 5.03 5.04

CURRENT 13:05 h 12 07 02

CURRENT 0000 179.7 h pK ▲ ▼ T

- The same procedure as the display of the phase voltage peak values

6) Active phase power rating page

W 995 W 1 POWER ACTIVE 3 2 994 995 T W 2.98 k W ACTIVE POWER pK

• The active phase power ratings are displayed
- Press "T" to display the active system power rating

6a) Active power rating peak value page

10.1 kW ACTIVE 3 POWER 0.98 1.02 13:20 h ACTIVE POWER 12 07 02 17:40 h ACTIVE POWER 0000 179.9 pK pK pK T

- The same procedure as the display of the phase voltage peak values

7) Apparent phase power rating page

1.15 k VA APPARENT 1 2 3 4 1.14 1.16 T APPARENT 3.45 k VA POWER pK

• The apparent phase power rating values are displayed
- Press "T" to display the apparent system power rating

7a) Apparent peak value pages

120 k VA APPARENT POWER 1.19 120 3 2 13:20 h APPARENT POWER 12 07 02 pK APPARENT POWER 0000 179.9 T

- The same procedure as the display of the phase voltage peak values

8) Reactive phase power rating page

580 VAR 1 POW. REACTIVE 3 2 579 581 174 VAR POWER pK

• The reactive phase power ratings are displayed
- Press "T" to display the reactive system power rating

8a) Reactive power peak value page

584 VAR VAR POWER REACTIVE 3 1 2 583 584 1320 h POWER REACTIVE 12 07 02 pK REACTIVE POWER 0000 179.9 T pK

- The same procedure as the display of the phase voltage peak values

9) Phase power factor page

0.87c 1 3 2 0.86c0.87c 0.87 cos φcos c

  • The phase power factors are displayed (the letter "C" indicates a capacity phase shift and the letter "L" an inductive phase shift)
  • Press "T" to display the system power factor

10) Voltage-current phase shift page

30.0c 30.1c 30.0c

- The voltage-current phase shifts are displayed in sixtieth degrees (the letter "C" indicates a capacity phase shift and the letter "L" an inductive phase shift)

11) Mean active system power rating page

2.99 k W POWER ACTIVE AVE-RAGE

- The active system power rating is displayed over a mean of N minutes (can be set from 1 to 60) The default value is 15 min

11a) Mean active power rating peak value page

301 k W ACTIVE POWER RUE-RGE 1305 h ACTIVE POWER 12 07 02 1305 h ACTIVE POWER 0000 179.7 pK pK T

- The same procedure as the display of the phase voltage peak values

12) Mean apparent system power rating page

3.44 k VA APPARENT POWER AUE-RAGE

- The apparent system power rating is displayed over a mean of N minutes (can be set from 1 to 60) The default value is 15 min

12a) Apparent mean power rating peak value page

3.44 k VA APPARENT POWER 88E-89E 1305 h 12 07 02 APPARENT POWER 0000 179.7 pK pK h pK T

- The same procedure as the display of the phase voltage peak values

13) Mean reactive system power rating page

1.75 k VAR POWER REACTIVE RUE-RAGE

- The reactive system power rating is displayed over a mean of N minutes (can be set from 1 to 60) The default value is 15 min

13a) Mean reactive power rating peak value page

176 k VAR PWR REACTIVE RUE-R9E 1305 h PWR REACTIVE 12 07 02 179.7 REACTIVE POWER A T

- The same procedure as the display of the phase voltage peak values

Note: If the “pK” and “T” keys are held down together for three seconds from display pages 11, 12 and 13, the integration of the mean active, reactive and apparent power ratings is obtained.

The central symbols in the display flash to confirm this operation, which can be used to synchronise the calculation of the power rating with the power supply company, such as ENEL, for example.

14) Total active energy page

k Wh ACTIVE ENERGY 000 1368.4

20.6 1 ACTIVE ENERGY 3 2 12 20.8 2 12 WR

• The total active energy is displayed

- Press “T” to display the partial active energy ratings for the single phases (these energy ratings are zeroed each time the total active energy is increased)

14a) Total absolute active energy page

ACTIVE ENERGY 000 1368.4 k Wh pK

0265 k Wh ACTIVE ENERGY 0000824.0

- If the "pK" key is pressed from the total active energy page, the value of the absolute active energy is displayed, with the symbol "AbS". This value cannot be zeroed, except due to meter overflow at 9999999.9kWh.

15) Total reactive energy page

k VARh REACTIVE ENERGY 000 : 126.4 T 20.2 k VARh REACTIVE ENERGY 3 2 19.8 16.9

• The total reactive energy is displayed
- Press "T" to display the partial reactive energy ratings for the single phases (these energy ratings are zeroed each time the total reactive energy is increased)

15a) Total absolute reactive energy page

k VARh pK REACTIVE ENERGY 000 1 126.4 865 k VARh REACTIVE ENERGY 000 1 108.2

- If the “pK” key is pressed from the total reactive energy page, the value of the absolute reactive energy is displayed, with the symbol “AbS”. This value cannot be zeroed, except due to meter overflow at 9999999.9 kvarh).

16) Frequency page

FREQUENCY 50.0 Hz

• The frequency of voltage V1 is displayed

17) Time and date page

16:20 16 07 02

16:20 0000278.9

  • The time and date are displayed in dd-mm-yy format
  • Press "pK" to display the time lapsed from the start-up of the instrument, expressed in hours and tenths of an hour
  • Press "up" (▲) to return to the starting page

Note: from the first setting onwards, the time and date will flash. These will also flash in the peak value pages.

MEASUREMENT/CALCULATION METHOD

  • The voltage and current measurements are taken in TRMS (True RMS) by means of sampling and analogue-digital conversion.
  • The following formulas are used to calculate the system values:

System voltage V =

$$ \frac {V _ {1} + V _ {2} + V _ {3}}{\sqrt {3}} $$

System current I =

$$ \frac {\mathrm{l} _ {1} + \mathrm{l} _ {2} + \mathrm{l} _ {3}}{\sqrt {3}} $$

Active system power P = P

$$ 1 ^ {+ P} 2 ^ {+ P} 3 $$

Reactive system power Q = Q

1^+Q 2^+Q_3 (algebraic sum)

Apparent system power

$$ \mathbf {A} = \sqrt {\mathbf {P} ^ {2} + \mathbf {Q} ^ {2}} $$

System power factor

$$ \mathbf {P F} = \frac {\mathbf {P}}{\mathbf {A}} $$

Total reactive energy

$$ \mathbf {E} = \mathrm{E} _ {1} + \mathrm{E} _ {2} + \mathrm{E} _ {3} $$

Mean active system power Er = Er

$$ 1 + \mathrm{Er} _ {2} + \mathrm{Er} _ {3} $$

Mean active system power

$$ \mathbf {P} _ {\text { Avg }} = \frac {1 ^ {0}}{\mathbf {T} _ {- T}} \int \mathbf {P d t} (T = 1 ^ {\prime} \div 6 0 ^ {\prime} \text { programme }) $$

Mean system Q Q

$$ \mathbf {A} \mathbf {v g} = \frac {\mathbf {1} ^ {0}}{\mathbf {T} _ {- T}} \int \mathbf {Q} \mathbf {d t} (T = 1 ^ {\prime} \div 6 0 ^ {\prime} \text { programme }) $$

Mean system A A

$$ \mathbf {A} \mathbf {v g} = \frac {\mathbf {1} ^ {0}}{\mathbf {T} _ {- T}} \int \mathbf {A} \mathbf {d t} (T = 1 ^ {\prime} \div 6 0 ^ {\prime} \text { programme }) $$

REFERENCE STANDARDS

■ Conformity to EU directives:

73/23/EEC modified by 93/68/EEC (safety)

89/336/EEC modified by 92/31/EEC and 93/68/EEC (EMC)

is declared with reference to the following harmonised standards:

Safety:

CEI-EN 61010-1: Safety provisions for electrical measurement, control and laboratory appliances;

Part I: general provisions

■ Electromagnetic compatibility:

CEI-EN 50082-2: General standard on equipment in an industrial environment CEI-EN 50081-1: General standard on emissions in household, commercial and light industrial environments

■ Measurement provisions:

CEI-EN 61036: Static active energy electricity meters for AC (classes 1 and 2) CEI-EN 61268: Static reactive energy electricity meters for AC (classes 2 and 3)

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Vemer

Model : ADR-D Out

Category : Analyseur réseau