BRUGSANVISNING VACN-N-K1-1-EX4-M Festo

natural_image
Technical line drawing of a mechanical component with a curved shaft and housing (no text or symbols)FESTO
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Operating instruction
8186786
2022-12c
[8186788]

8186786
Translation of the original instructions
© 2023 all rights reserved to Festo SE & Co. KG
1 Identification EX
| Marking Certificate | ||
| Ex mb IIC T6Ex mb tb IIIC T80°C | IECEx PTB 15.0016 X | |
| CE | II 2G Ex mb IIC T6 GbII 2D Ex mb tb IIIC T80°C Db | PTB 14 ATEX 2027 X |
| UKCA | II 2G Ex mb IIC T6 GbII 2D Ex mb tb IIIC T80°C Db | PTB 14 ATEX 2027 X |
| SegurangaINMETRO | Ex mb IIC T6 GbEx mb tb IIIC T80°C Db | DNV 15.0016X |
| Ex mb IIC T6 GbEx mb IIIC T80°C Db | GYJ21.1327X | |
Tab. 1: Identification EX
2 Applicable documents
NOTICE
Technical data for the product can have different values in other documents. For operation in an explosive atmosphere, the technical data in this document always have priority.

All available documents for the product → www.festo.com/sp.
3 Certified solenoid coils
| Voltage Cable length Type T. no. | ||
| 24 V DC 3 m VACN-N-K1-1-EX4-M 8029143 | ||
| 24 V DC 10 m VACN-N-K1-1-10-EX4-M 8141606 | ||
| 110 V AC 3 m VACN-N-K1-16B-EX4-M 8029142 | ||
| 230 V AC 3 m VACN-N-K1-3A-EX4-M 8029141 |
Tab. 2: Certified solenoid coils
4 Safety
4.1 General safety instructions
- The device can be used under the stated operating conditions in zones 1 and 2, explosive gas atmospheres, and in zones 21 and 22, explosive dust atmospheres.
- The device may only be used in the delivered configuration in a potentially explosive atmosphere.
- Use the device in its original status without any unauthorised modifications.
- All work must be carried out outside of potentially explosive areas.
4.2 Intended use
The solenoid coil is an actuator for Festo valves.
4.3 Identification X: special conditions
- Install a fuse or a motor protection switch appropriate for the rated current upstream of the solenoid coil as short-circuit protection.
- Short circuit protection for max. 3 times the rated current in accordance with IEC 60127-1.
- The fuse with the lowest current value in accordance with IEC 60127-1 is sufficient for very low rated currents of the solenoid coil.
- Select the fuse rated voltage equal to or greater than the nominal voltage of the solenoid coil.
- Motor protection switch with short circuit triggering and thermal quick triggering, adjustment to rated current.
- Install the fuse in the supply unit or wire it separately upstream.
- The interruption rating of the fuse unit must be greater than or equal to the maximum expected short-circuit current at the installation location, normally 1500 A.
- Max. permissible ripple with solenoid coils in direct current: 20%.
5 Function
When switching on the voltage, the solenoid is energised, and the valve is actuated.
6 Commissioning

WARNING
The discharge of electrostatically charged parts can lead to ignitable sparks.
- Prevent electrostatic charging by taking appropriate installation and cleaning measures.
- Include the device in the system equipotential bonding.
NOTICE
Installation and commissioning should only be carried out in accordance with operating instructions and by qualified personnel.
- Prevent short circuit or interruption resulting from bending the connecting cable too tightly.
- Observe the product labelling.
- Do not commission the solenoid coil until after mounting.
7 Maintenance and care

WARNING
The discharge of electrostatically charged parts can lead to ignitable sparks. If used in group IIC:
- Only clean the device with a damp cloth.
– Repairs to the solenoid coil are not permitted.
- The device is maintenance-free.
8 Technical data
Technical data
| Ambient temperature Ta | ||
| Individual mounting [°C] | -20 ≤ Ta ≤ +50 | |
| Block mounting | [°C] | -20 ≤ Ta ≤ +40 |
| Nominal voltage Un | ||
| VACN-N-K1-1-EX4-M | [V DC] | 24 |
| VACN-N-K1-1-10-EX4-M | [V DC] | |
| VACN-N-K1-16B-EX4-M | [V AC] | 110 (50 ... 60 Hz)120 (60 Hz) |
| VACN-N-K1-3A-EX4-M | [V AC] | 230 (50 ... 60 Hz) |
| Rated current In | ||
| VACN-N-K1-1-EX4-M | [mA] | 109 |
| VACN-N-K1-1-10-EX4-M | [mA] | |
| VACN-N-K1-16B-EX4-M | [mA] | 22 |
| VACN-N-K1-3A-EX4-M | [mA] | 9 |
| Duty cycle | [%] 100 (continuous operation) | |
| Degree of protection | IP65 | |
| Relative humidity | [%] 95 (non-condensing) | |
| Assembly | Individual mounting/block mounting | |
| Block mounting, minimum distance | ||
| VACN-N-K1-1-EX4-M | [mm] | 2 |
| VACN-N-K1-1-10-EX4-M | [mm] | |
| VACN-N-K1-16B-EX4-M | [mm] | 1 |
| VACN-N-K1-3A-EX4-M | [mm] | 1 |
| Mounting position | any | |
Tab. 3: Technical data